Bringing transparency to federal inspections
Tag No.: K0029
Based on observation and staff interviews it was determined the facility failed to ensure proper fire stopping materials had been used to seal openings in rated walls.
The findings include:
On 03/13/13 between 9:00 am and 12:00 pm Observation revealed that non approved spray foam insulation had been used to seal around a pipe in HVAC Room 60A.
An interview with Staff M at the time of discovery and this interview revealed that the facility was unaware of the use of the non approved foam.
Tag No.: K0056
Based on observation and staff interviews it was determined the facility failed to ensure proper sprinkler coverage was provided throughout the building
The findings include:
On 03/12/13 between 1:00 pm and 4:00 pm Observation revealed that the skylight area was not properly protected by the sprinkler system.
An interview with Staff M at the time of discovery and this interview revealed that the facility was unaware of the requirement for sprinkler protection for the skylight area.
Tag No.: K0064
Based on observation and staff interviews it was determined the facility failed to ensure that the requirements of NFPA 10 were met throughout the building.
The findings include:
On 03/12/13 between 1:00 pm and 4:00 pm Observation revealed that the kitchen K-Type Extinguishers were not provided with the required instruction placard.
 An interview with Staff M at the time of discovery and this interview revealed that the facility was unaware that instruction placards were required.
Tag No.: K0069
Based on observation and staff interviews it was determined the facility failed to ensure that the requirements of NFPA 96 were met throughout the building.
The findings include:
On 03/12/13 between 1:00 pm and 4:00 pm Observation revealed that the kitchen vent hood filters were not installed properly.
 An interview with Staff M at the time of discovery and this interview revealed that the facility was unaware that filters had not been reinstalled properly.
On 03/12/13 between 1:00 pm and 4:00 pm Observation revealed that the vent hood for the grill in the serving line area was not protected by an automatic extinguishment system as required.
 An interview with Staff M at the time of discovery and this interview revealed that the facility was unaware that this vent hood was required to be protected by an automatic extinguishment system.
Tag No.: K0147
Based on observation and staff interviews it was determined the facility failed to ensure that the requirements of NFPA 70 National Electrical Code were met throughout the building.
The findings include:
On 03/12/13 between 1:00 pm and 4:00 pm Observation revealed that storage was blocking access to electrical panels in the kitchen area.
 An interview with Staff M at the time of discovery and this interview revealed that the facility was unaware that the storage was blocking the access to the electrical panels. 
On 03/12/13 between 1:00 pm and 4:00 pm Observation revealed that the cover was missing for the 240 volt receptacle in the serving line area.
 An interview with Staff M at the time of discovery and this interview revealed that the facility was unaware that the cover was missing for this receptacle.