Tag No.: K0062

Based on record review and interview, the facility failed to maintain the automatic sprinkler system and its components.

The findings include:

Record review and interview with the maintenance director on 9/16/15 at 10:00 AM revealed the facility failed to conduct the 10 year dry sprinkler test.

This finding was verified by the maintenance director and acknowledged by the administrator during the exit conference on 9/16/15
NFPA 25 TIA 98-1 2-3.1.1 Exception No. 5