HospitalInspections.org

Bringing transparency to federal inspections

1220 NORTH GLENN ENGLISH STREET

CORDELL, OK 73632

No Description Available

Tag No.: K0017

Based on observation and interview with staff, the facility failed to provide corridors separated from use areas by walls constructed with at least 1/2 hour fire resistance rating. Section 19.3.6.2.1, Exception No. 1 reads "in smoke compartments protected throughout by an approved, supervised automatic sprinkler system in accordance with 19.3.5.2, a corridor shall be permitted to be separated from all other areas by non-fire-rated partitions and shall be permitted to terminate the the ceiling where the ceiling is constructed to limit the transfer of smoke." Findings:

1) The suspended acoustical ceiling was found to have cracked, broken, warped, and water damaged tiles at various locations in the facility.

No Description Available

Tag No.: K0018

Based on observation and interview with staff, the facility failed to provide corridor doors with a means suitable for keeping the door closed. Findings:

1) The dutch door between the corridor and the storeroom does not meet the requirements of 19.3.6.3.6. The upper leaf and lower leaf are required to both have a latching device, and the meeting edges of the upper and lower leaves shall be equipped with an astragal, a rabbet, or a bevel. This door does not meet these requirements.

No Description Available

Tag No.: K0029

Based on observation and interview with staff, the facility failed to provide hazardous areas protected in accordance with 19.3.2.1, which requires doors to be self-closing or automatic-closing. Findings:

1) The storeroom, lab, and soiled linen are each considered a hazardous area per 19.3.2.1, having an area greater than 50 square feet used for storage of combustible supplies. The doors into these rooms are not self-closing or automatic-closing.

No Description Available

Tag No.: K0067

Based on observation and interview with staff, the facility failed to provide ventilation complying with NFPA 101, Section 9.2 Heating, Ventilating, and Air Conditioning; NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems; and ASHRAE Handbook - HVAC System and Equipment, 1996. Findings:

1) The exhaust fans in the toilet rooms were not operable.

No Description Available

Tag No.: K0145

Based on observation and interview with staff, the facility failed to provide a Type I EES divided into the critical branch, life safety branch and the emergency branch in accordance with NFPA 99, 3.4.2.2.2. Findings:

1) The emergency electrical system does not meet the requirements for a Type I EES and is not divided into the critical branch, life safety branch and the emergency branch, as required by 3.4.2.2.2.

No Description Available

Tag No.: K0147

Based on observation and interview with staff, the facility failed to provide electrical wiring in accoradance with NFPA 70, National Electical Code. Findings:

1) Three junction boxes without cover plates were found above the ceiling in the Nurse Report Room. Cover plates are required by 314.28(C).

LIFE SAFETY CODE STANDARD

Tag No.: K0017

Based on observation and interview with staff, the facility failed to provide corridors separated from use areas by walls constructed with at least 1/2 hour fire resistance rating. Section 19.3.6.2.1, Exception No. 1 reads "in smoke compartments protected throughout by an approved, supervised automatic sprinkler system in accordance with 19.3.5.2, a corridor shall be permitted to be separated from all other areas by non-fire-rated partitions and shall be permitted to terminate the the ceiling where the ceiling is constructed to limit the transfer of smoke." Findings:

1) The suspended acoustical ceiling was found to have cracked, broken, warped, and water damaged tiles at various locations in the facility.

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on observation and interview with staff, the facility failed to provide corridor doors with a means suitable for keeping the door closed. Findings:

1) The dutch door between the corridor and the storeroom does not meet the requirements of 19.3.6.3.6. The upper leaf and lower leaf are required to both have a latching device, and the meeting edges of the upper and lower leaves shall be equipped with an astragal, a rabbet, or a bevel. This door does not meet these requirements.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on observation and interview with staff, the facility failed to provide hazardous areas protected in accordance with 19.3.2.1, which requires doors to be self-closing or automatic-closing. Findings:

1) The storeroom, lab, and soiled linen are each considered a hazardous area per 19.3.2.1, having an area greater than 50 square feet used for storage of combustible supplies. The doors into these rooms are not self-closing or automatic-closing.

LIFE SAFETY CODE STANDARD

Tag No.: K0067

Based on observation and interview with staff, the facility failed to provide ventilation complying with NFPA 101, Section 9.2 Heating, Ventilating, and Air Conditioning; NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems; and ASHRAE Handbook - HVAC System and Equipment, 1996. Findings:

1) The exhaust fans in the toilet rooms were not operable.

LIFE SAFETY CODE STANDARD

Tag No.: K0145

Based on observation and interview with staff, the facility failed to provide a Type I EES divided into the critical branch, life safety branch and the emergency branch in accordance with NFPA 99, 3.4.2.2.2. Findings:

1) The emergency electrical system does not meet the requirements for a Type I EES and is not divided into the critical branch, life safety branch and the emergency branch, as required by 3.4.2.2.2.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation and interview with staff, the facility failed to provide electrical wiring in accoradance with NFPA 70, National Electical Code. Findings:

1) Three junction boxes without cover plates were found above the ceiling in the Nurse Report Room. Cover plates are required by 314.28(C).