Tag No.: K0200
K200 Means of Egress Requirements - General
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023, that there were the following issues:
1) Based on review of the records, facility failed to perform inspection of doors in means of egress annually.
Tag No.: K0222
K223 Doors with Self-Closing Devices
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023, that there were the following issues:
1) Observed during tour, the double door with magnetic hold opening into the inpatient unit was missing an astragal.
Tag No.: K0353
K353 Sprinkler System - Maintenance and Testing
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023, that there were the following issues:
1) Observed during tour in patient storage room, there was a sprinkler head with missing escutcheon cover
2) Observed during tour in seclusion anteroom, the sprinkler head protruded out too much and should be flush with the ceiling tile.
Tag No.: K0355
K355 Portable Fire Extinguishers
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023, that there were the following issues:
1) Observed during tour, facility failed to show records demonstrating fire extinguishers were subject to maintenance at yearly interval on a consistent basis.
2) The fire extinguisher monthly check failed to consistently note the date it was checked.
Tag No.: K0500
K500 Building Services - Other
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023, that there were the following issues:
1) Based on review of the records, facility failed to keep logs of when filters were changed for each air handler serving the facility.
Tag No.: K0700
K700 Emergency Preparedness Plan and Drills
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023:
1) Based on review of the records, facility failed to participate and provide written report on community mock disaster drill annually.
Tag No.: K0712
K712 Fire Drills
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023:
1) Based on review of the records, facility failed to perform fire drill on a consistent basis. For example, there was no record of fire drill from January to April of 2022. Even though facility indicated a change in leadership, there should be a systemic record keeping that persists through personnel change.
Tag No.: K0741
K741 Smoking Regulations
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023:
1) Observed during tour, "NO SMOKING" not prominently displayed at all major entrances.
Tag No.: K0901
K901 Fundamentals - Building System Categories
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023:
1) Based on review of the records, facility failed to date the annual risk assessment.
Tag No.: K0912
K912 Electrical Systems - Receptacles
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023, that there were the following issues:
1) Observed during tour in soiled utility room, there was a non-operational GFCI receptacle outlet near hopper sink that needed replacement.
Tag No.: K0921
K921 Biomedical electrical inspection reports
Findings:
The inspector observed, while accompanied by the CEO, during the hours of the inspection from 3:00 pm to 5:00 pm on 04/06/2023, that there were the following issues:
1) Based on review of the records, facility failed to perform biomedical equipment inspection annually.