Tag No.: K0145
An electrical receptacle at the emergency generator is required, powered from the Life Safety Branch of the emergency system. NFPA 99; 4.4.2.2.2.2(5)
This STANDARD is not being met, as evidenced by: Based on observation during the Survey on the morning of 04/22/2014, with the hospital's Director of Plant Operations, the required electrical receptable was not in place.