Tag No.: K0078

Based on Temperature and Humidity Log review and interview, it was determined the humidity levels in two of two operating rooms in the facility was regularly maintained below 35% from December 2009 to March 2010; the facility did not take corrective actions. The failed practice had the potential to affect 4 of 4 surgical patients on the day of the survey and all patients admitted for surgery. The findings follow:

A. Review of the Temperature and Humidity Log on 04/05/10 at 1000 revealed humidity levels below 35% were recorded for each operating room as follows:
1) In Operating Room #604, humidity levels below 35% were recorded for 65 of 130 days from December 2009 to March 2010.
2) In Operating Room #605, humidity levels below 35% were recorded for 68 of 130 days from December 2009 to March 2010.
B. In an interview conducted on 04/06/10 at 1515, the Maintenance Director stated he was aware of low humidity levels in the operating rooms, but there were no work orders to correct the problem available for review.

LIFE SAFETY CODE STANDARD

Tag No.: K0078

Based on Temperature and Humidity Log review and interview, it was determined the humidity levels in two of two operating rooms in the facility was regularly maintained below 35% from December 2009 to March 2010; the facility did not take corrective actions. The failed practice had the potential to affect 4 of 4 surgical patients on the day of the survey and all patients admitted for surgery. The findings follow:

A. Review of the Temperature and Humidity Log on 04/05/10 at 1000 revealed humidity levels below 35% were recorded for each operating room as follows:
1) In Operating Room #604, humidity levels below 35% were recorded for 65 of 130 days from December 2009 to March 2010.
2) In Operating Room #605, humidity levels below 35% were recorded for 68 of 130 days from December 2009 to March 2010.
B. In an interview conducted on 04/06/10 at 1515, the Maintenance Director stated he was aware of low humidity levels in the operating rooms, but there were no work orders to correct the problem available for review.