Tag No.: K0018

Based on observation, it was determined that the facility failed to ensure there was no impediment to the closing of corridor doors.

Findings include:

On 1/30/14 at 9:35 AM, in the presence of Staff #35, the Children's Hospital electrical room door would not close due to an uneven floor.

No Description Available

Tag No.: K0039

Based on observation, it was determined that the facility failed to ensure widths of exits are at least 4 feet.

Findings include:

On 1/31/14 at 9:40 AM, in the presence of Staff #35, the northeast Emergency Department exit corridor was reduced to 2 feet wide by a wheelchair, trash can and chair.

No Description Available

Tag No.: K0047

Based on observation, it was determined that the facility failed to ensure exit signs are continuously illuminated.

Findings include:

On 1/31/14 at 3:45 PM, in the presence of Staff #35, the exit light at the Same Day Surgery corridor was not lit.

No Description Available

Tag No.: K0072

Based on observation, it was determined that the facility failed to ensure that means of egress are maintained free of obstructions or impediments.

Findings include:

On 1/30/14 at 10:50 AM, in the presence of Staff #35, the Cardiac Rehabilitation Gym exit stair and landing were covered in snow.

No Description Available

Tag No.: K0074

Based on observation, it was determined that the facility failed to ensure that cubical curtains were in accordance with NFPA 13.

Findings include:

On 1/30/14 at 10:00 AM, in the presence of Staff #35, in the Pediatric Emergency Department isolation room, the curtain mesh was too small for a sprinklered environment.

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on observation, it was determined that the facility failed to ensure there was no impediment to the closing of corridor doors.

Findings include:

On 1/30/14 at 9:35 AM, in the presence of Staff #35, the Children's Hospital electrical room door would not close due to an uneven floor.

LIFE SAFETY CODE STANDARD

Tag No.: K0039

Based on observation, it was determined that the facility failed to ensure widths of exits are at least 4 feet.

Findings include:

On 1/31/14 at 9:40 AM, in the presence of Staff #35, the northeast Emergency Department exit corridor was reduced to 2 feet wide by a wheelchair, trash can and chair.

LIFE SAFETY CODE STANDARD

Tag No.: K0047

Based on observation, it was determined that the facility failed to ensure exit signs are continuously illuminated.

Findings include:

On 1/31/14 at 3:45 PM, in the presence of Staff #35, the exit light at the Same Day Surgery corridor was not lit.

LIFE SAFETY CODE STANDARD

Tag No.: K0072

Based on observation, it was determined that the facility failed to ensure that means of egress are maintained free of obstructions or impediments.

Findings include:

On 1/30/14 at 10:50 AM, in the presence of Staff #35, the Cardiac Rehabilitation Gym exit stair and landing were covered in snow.

LIFE SAFETY CODE STANDARD

Tag No.: K0074

Based on observation, it was determined that the facility failed to ensure that cubical curtains were in accordance with NFPA 13.

Findings include:

On 1/30/14 at 10:00 AM, in the presence of Staff #35, in the Pediatric Emergency Department isolation room, the curtain mesh was too small for a sprinklered environment.