Tag No.: K0018
Based on observation, it was determined that the facility failed to ensure there was no impediment to the closing of corridor doors.
Findings include:
On 1/30/14 at 9:35 AM, in the presence of Staff #35, the Children's Hospital electrical room door would not close due to an uneven floor.
Tag No.: K0039
Based on observation, it was determined that the facility failed to ensure widths of exits are at least 4 feet.
Findings include:
On 1/31/14 at 9:40 AM, in the presence of Staff #35, the northeast Emergency Department exit corridor was reduced to 2 feet wide by a wheelchair, trash can and chair.
Tag No.: K0047
Based on observation, it was determined that the facility failed to ensure exit signs are continuously illuminated.
Findings include:
On 1/31/14 at 3:45 PM, in the presence of Staff #35, the exit light at the Same Day Surgery corridor was not lit.
Tag No.: K0072
Based on observation, it was determined that the facility failed to ensure that means of egress are maintained free of obstructions or impediments.
Findings include:
On 1/30/14 at 10:50 AM, in the presence of Staff #35, the Cardiac Rehabilitation Gym exit stair and landing were covered in snow.
Tag No.: K0074
Based on observation, it was determined that the facility failed to ensure that cubical curtains were in accordance with NFPA 13.
Findings include:
On 1/30/14 at 10:00 AM, in the presence of Staff #35, in the Pediatric Emergency Department isolation room, the curtain mesh was too small for a sprinklered environment.
Tag No.: K0018
Based on observation, it was determined that the facility failed to ensure there was no impediment to the closing of corridor doors.
Findings include:
On 1/30/14 at 9:35 AM, in the presence of Staff #35, the Children's Hospital electrical room door would not close due to an uneven floor.
Tag No.: K0039
Based on observation, it was determined that the facility failed to ensure widths of exits are at least 4 feet.
Findings include:
On 1/31/14 at 9:40 AM, in the presence of Staff #35, the northeast Emergency Department exit corridor was reduced to 2 feet wide by a wheelchair, trash can and chair.
Tag No.: K0047
Based on observation, it was determined that the facility failed to ensure exit signs are continuously illuminated.
Findings include:
On 1/31/14 at 3:45 PM, in the presence of Staff #35, the exit light at the Same Day Surgery corridor was not lit.
Tag No.: K0072
Based on observation, it was determined that the facility failed to ensure that means of egress are maintained free of obstructions or impediments.
Findings include:
On 1/30/14 at 10:50 AM, in the presence of Staff #35, the Cardiac Rehabilitation Gym exit stair and landing were covered in snow.
Tag No.: K0074
Based on observation, it was determined that the facility failed to ensure that cubical curtains were in accordance with NFPA 13.
Findings include:
On 1/30/14 at 10:00 AM, in the presence of Staff #35, in the Pediatric Emergency Department isolation room, the curtain mesh was too small for a sprinklered environment.