No Description Available

Tag No.: K0050

Based upon record review and staff interviews on 01/21/14 between approximately 1300 and 1600 hours the facility has failed to provide fire drill records reflecting drills being conducted on all shifts for the past 12 months. This could potentially result in the staff not responding in a coordinated manner in the event of a fire or other emergency and endangering residents, staff and/or visitors.

The findings include, but are not limited to:
The facility has not conducted the required fire drills of once per shift per quarter since July 2013.

The above was discussed and acknowledged by the Chief Executive Officer.

No Description Available

Tag No.: K0052

Based upon record review and staff interviews on 01/21/14 between approximately 1300 and 1600 hours the facility has failed to have appropriate testing of the fire alarm system which result in the failure of notification to staff of a water supply problem to the fire sprinkler system and endanger the residents, staff and/or visitors within the facility.

The findings include, but are not limited to:
The fire alarm system has not been tested in the past 12 months.

The above was discussed and acknowledged by the Chief Executive Officer.

No Description Available

Tag No.: K0062

Based upon record review and staff interviews on 01/21/14 between approximately 1300 and 1600 hours the facility has failed to conduct testing of the fire sprinkler system as required. This could result in the failure of the fire sprinkler system to operate properly in the event of a fire which would endanger the residents, staff and/or visitors within the facility.
The findings include, but are not limited to:
There are no records for the quarterly or annual tests.

The above was discussed and acknowledged by the Chief Executive Officer.

No Description Available

Tag No.: K0064

Based upon record review and observation on 01/21/14 between approximately 1300 and 1600 hours the facility has failed to assure proper maintenance of the facilities portable fire extinguishers. This potentially delays a quick response to contain a fire from spreading which could expose and endanger residents, staff and/or visitors within the facility.

The findings include, but are not limited to:
The last service done on the fire extinguishers was in November 2012.
The above was discussed and acknowledged by the Chief Executive Officer.

No Description Available

Tag No.: K0069

Based upon record review and staff interviews on 01/21/14 between approximately 1300 and 1600 hours the facility has failed to conduct testing of the hood and duct fire suppression equipment protecting the commercial cooking equipment in the kitchen. This could result in the failure of the system to operate properly which would endanger the residents, staff and/or visitors within the facility.

The findings include, but are not limited to:
Need to have the hood cleaned every six months. Provide documentation of cleanings.

The above was discussed and acknowledged by the Chief Executive Officer.

No Description Available

Tag No.: K0144

Based upon record review and staff interviews on 01/21/14 between approximately 1300 and 1600 hours the facility has failed to have annual testing and maintenance conducted on the emergency generator. This could result in a failure of the emergency power system which would leave the facility without egress and work lighting in the event of a power failure which would endanger the residents, staff and/or visitors within the facility.

The findings include, but are not limited to:
The last testing was done at the initial set up in October 2012.

The above was discussed and acknowledged by the Chief Executive Officer.