Tag No.: K0011

Based upon observations made in the presence of the plant manager on 9/25/14, it was determined that the facility did not maintain fire barrier in accordance with NFPA 101: 19.1.1.4.1 and NFPA 80: 2-3.1.7.

Findings include:

The main double fire rated doors had ½ " opening between the double doors and would not resist the passage of smoke and fire.

No Description Available

Tag No.: K0029

Based upon staff interview and observations made in the presence of the plant manager on 9/25/14, it was determined that the facility did not maintain hazardous areas to be fire and smoke separated from other sections of the facility in accordance with NFPA 101: 19.3.2.1., 8.4 and 7.2.1.8.

Findings include:

The soiled utility room had 4 " opening on the wall from where the old nurse call system was.

No Description Available

Tag No.: K0050

Based upon review of fire drill documentation made in the presence of the plant manager on 9/25/14, it was determined that the facility did not conduct fire drills at unexpected times under varying conditions for each shift in accordance with Life Safety Code regulations and NFPA 101: 19.7.1.2.

Findings include:

The facility did not have documentation that the fire drill for the afternoon shift 4th quarter was conducted during the previous 12-month period.

No Description Available

Tag No.: K0070

Based upon staff interview and observations made in the presence of the plant manager on 9/25/14, it was determined that the facility had in use portable space heater in the facility in accordance with NFPA 101: 19.7.8.

Findings include:

The medical records area had two portable space heaters in use during survey. The heaters were removed during survey.

No Description Available

Tag No.: K0074

Based upon staff interview and observations made in the presence of the plant manager on 9/25/14, it was determined that the facility did not maintain flame retardant treatment on combustible decorations in accordance with NFPA101 19.3.5.5 and NFPA 701.

Findings include:

The main lobby area had a 4 ' x 26 ' carpeted display case. The carpet was lacking documentation that the display was either inherently flame retardant or treated to be flame resistant.