Tag No.: K0012

One-story buildings of Type II (000) construction are required to be protected by an automatic sprinkler system. Without a sprinkler system, Type II (111) construction is required.

The facility failed to ensure one-hour fire resistive rated protection for the structural steel.

Observation determined the steel I-beams and columns were not protected as a one-hour fire rated assembly.

LIFE SAFETY CODE STANDARD

Tag No.: K0012

One-story buildings of Type II (000) construction are required to be protected by an automatic sprinkler system. Without a sprinkler system, Type II (111) construction is required.

The facility failed to ensure one-hour fire resistive rated protection for the structural steel.

Observation determined the steel I-beams and columns were not protected as a one-hour fire rated assembly.