Bringing transparency to federal inspections
Tag No.: K0012
One-story buildings of Type II (000) construction are required to be protected by an automatic sprinkler system. Without a sprinkler system, Type II (111) construction is required.
The facility failed to ensure one-hour fire resistive rated protection for the structural steel.
Observation determined the steel I-beams and columns were not protected as a one-hour fire rated assembly.