HospitalInspections.org

Bringing transparency to federal inspections

1305 W 18TH ST POST OFFICE BOX 5039

SIOUX FALLS, SD 57117

General Requirements - Other

Tag No.: K0100

The Edith Sanford Breast Center at 1309 W. 17th Street was found not in compliance due to the following:

Observation at 9:00 a.m. on 10/31/17 revealed a storage room over 100 square feet in area with large amounts of combustibles (cardboard, paper, plastic, and latex gloves). The corridor door was not equipped with a self-closing device.

Interview with the construction project manager at the time of the observation confirmed that finding. He stated the room was a result of a construction separation of a larger room into two creating that storage area approximately two years ago.

Multiple Occupancies - Construction Type

Tag No.: K0133

Based on observation and interview, the provider failed to provide a two-hour fire-rated construction between the healthcare occupancy and the basement level business occupancy. Findings Include:

1. Inspection in the north east corner of mechanical room (L501) on 11/01/17 at 12:45 p.m. revealed two steel beams supporting the floor above. Those steel beams were not covered with fire proofing. Unprotected floor beams are not allowed in a two-hour fire rated floor construction. The mechanical room was on a floor level that was classified as a business occupancy and the floor level above the mechanical room was classified as a healthcare occupancy. Those occupancies must be separated by two-hour fire-rated construction.

Interview with the facilities director at the time of the observation confirmed that finding.

This deficiency had the potential to affect the smoke compartment located above the mechanical room.

Building Construction Type and Height

Tag No.: K0161

Based on observation and interview, the provider failed to meet the minimum construction standards of the 2012 Life Safety Code (LSC).The 5000 level ceiling system and roof assembly were wood framed construction (Type III). Findings include:

1. Observation at 9:00 a.m. on 10/31/17 revealed the 5000 level ceiling system and roof assembly was wood framed construction (Type III) that was not permitted in a five story building. Interview with the senior director of construction services at the time of observation revealed that was the original construction of the building.

The building meets the FSES. Please mark an "F" in the completion date column to indicate the provider's intent to correct the deficiencies identified in K000.

Means of Egress - General

Tag No.: K0211

Based on observation, measurement, and interview, the provider failed to maintain the correct exit height in corridors. Randomly observed corridors revealed ceiling heights were not conforming to the exit height required by the Life Safety Code. Findings include:

1. Observation on at 10:30 a.m. 10/31/17 revealed the ceiling height in Corridor- GC2 and CG6 were low. Measurement at the time of observation revealed those ceilings ranged in height from 6 feet 6 inches to 6 feet 8 inches. Interview at the time of observation with the senior director of construction services confirmed those heights. He that condition had existed for a number of years and the ceiling could not be raised because of other obstructions.

The building meets the FSES. Please mark an "F" in the completion date column to indicate the provider's intent to correct the deficiencies identified in K000.

Egress Doors

Tag No.: K0222

A. Based on observation, testing, and interview, the provider failed to ensure exit egress doors equipped with special locking arrangements were properly installed in one of many randomly observed doors (00-07.1245 door assembly for stair enclosure 4800-S02). Findings include:

1. Observation at 8:30 a.m. on 10/31/17 revealed door assembly #00-07.1245 was marked as an exit and was equipped with a magnetic lock, motion sensor, and side release button indicating it was an access-controlled door. Testing of the motion sensor at the time of the observation revealed the light on the sensor was active, but the magnetic lock did not release. Testing of the side release button after testing the motion sensor revealed the side release button did release the magnetic lock.

Interview with the construction project manager at the time of the observation revealed he was unaware both the motion sensor and the side release button were required to release the door magnet.

The special locking arrangement would classify as an access-controlled egress locking and should have been installed in accordance with section 7.2.1.6.2 of NFPA 101 Life Safety Code.

B. Based on observation, testing, and interview, the provider failed to ensure exit egress doors equipped with special locking arrangements were properly installed in two of many randomly observed doors (4800 C14A and the exit from the Heart Hospital to the East Patient Building). Findings include:

1. Observation at 9:15 a.m. on 10/31/17 revealed a magnetically locked door 4800 C14A. Testing of the door at the time of the observation revealed the magnetic lock released at almost thirty seconds delay time. There was not a sign mounted to indicate the magnetic lock was delayed egress (and to note a fifteen second release delay).

2. Observation at 10:30 a.m. on 10/31/17 revealed a magnetically locked door at the exit from the Heart Hospital to the East Patient Building with signage indicating it was a delayed egress lock with a thirty second delayed release. Testing of the door at the time of the observation revealed the magnetic lock did release at the thirty second delay time indicated. The magnetic delayed egress door lock time delay can not be longer than fifteen seconds without a waiver from the Department of Health, Office of Licensure and Certification.

Interview with the construction project manager at the time of the above observations confirmed those conditions. He indicated he was unaware the delayed egress time could not be longer than fifteen seconds and issued a work order to reset the delays and have the correct signage mounted to indicate the correct delay time.

Stairways and Smokeproof Enclosures

Tag No.: K0225

Based on observation, measurement, and interview, the provider failed to maintain conforming exit stairs. Two randomly observed stair enclosures did not have adequate width at the landings. Findings include:

1. Observation and measurement at 9:45 a.m. on 10/31/17 revealed the ground floor landing in the south stair enclosures intermediate landing was reduced down to 34 inches in width. Interview with the director of facilities revealed that condition had existed since the stair enclosure was constructed.

2. Observation at 10:00 a.m. on 10/31/17 revealed the north stair enclosure door on the mezzanine level encroached into the required width of the stair landing. Measurement at the time of observation reviewed that door reduced the required width of the stair landing to 16 inches. Interview with the director of facilities confirmed that condition and indicated it had existed since the stairs were constructed.

The building meets the FSES. Please mark an "F" in the completion date column to indicate correction of the deficiencies identified in K000.

Horizontal Exits

Tag No.: K0226

Based on observation and interview, the provider failed to maintain the ninty minute fire resistive rating of horizontal exit doors. One randomly observed fire door (door #00-70.0155) would not latch into the frame. Findings include:

1. Observation at 11:15 a.m. on 10/31/17 revealed the north leaf of the pair of ninty minute fire rated separation door on the 5000 level would not latch into the frame. Interview with the senior director of construction services at the time of the observation confirmed the door would not latch. Following the observation it was revealed the door was connected to the fire alarm system, so latching only occurred during fire alarm activation. Observation at 8:50 a.m. on 11/01/17 revealed during the simulated fire drill conducted in the east patient building the door leaf would not latch while the fire alarm was active. Interview with the senior director of construction services at the time of that observation confirmed the latching mechanism was not operating correctly.

This deficiency could affect patients within the adjacent smoke compartment on the east patient building and staff within the adjacent smoke compartment of the heart center.

Exit Signage

Tag No.: K0293

Based on observation and interview, the provider failed to install exit signs for one randomly observed location in the lower level (elevator lobby - 1836 guest area). Findings include:

1. Observation at 10:00 a.m. on 10/31/17 revealed one exit sign located in the lower level elevator lobby for the west door. The north door to the 1836 guest area from the elevator lobby was not marked to identify the second required path of egress.

Interview with the construction project manager at the time of the observation confirmed that finding.

The deficiency affected one location required to be provided with a marked and identifiable path of egress.

Cooking Facilities

Tag No.: K0324

Based on observation, document review, and interview, the provider failed to ensure proper testing and maintenance were maintained on the commercial kitchen hood fire suppression systems installed in three separate kitchen hoods located on the ground level food service area. Findings include:

1. Observation at 3:40 p.m. on 10/31/17 revealed a food service area located on the ground level. Further observation revealed maintenance and testing documentation located on the side of the kitchen hood. Review of the inspection documentation prepared by Sigler Fire Equipment Company dated 7/25/17 revealed a comment stating the tank, cartridge, and chemical agent due for 12 year hydrostatic testing.

Interview with the safety director at the time of the above observation confirmed that condition. She indicated she was unaware those fire suppression systems were overdue for the 12 year hydrostatic testing.

Smoke Detection

Tag No.: K0347

Based on observation and interview, the provider failed to ensure spaces open to exit egress corridors were provided in three randomly observed locations (vending areas on 1000, 2000, and 3000 levels) Findings include:

1. Observation 9:15 a.m. on 10/31/17 revealed a vending area on the 3000 level. Further observation revealed that area was open to the corridor and was not provided with smoke detection. Further observation revealed similar conditions on the 2000 and 1000 level.

Interview with the safety director at the time of the above observations confirmed those conditions. She indicated she was not aware smoke detection should have been provided in those vending areas.

Portable Fire Extinguishers

Tag No.: K0355

Based on observation and interview, the provider failed to conspicuously mark the locations for four randomly observed fire extinguishers (adjacent to patient rooms 5103, 5156, 5166, and 5215). Findings include:

1. Observations beginning at 8:55 a.m. on 11/1/17 during the fire drill revealed four fire extinguishers located adjacent to patients' rooms 5103, 5156, 5166, and 5215 in the corridors were in recessed cabinets with only a one inch lip protruding from the wall. The cabinets were identified with a decal sign on the front of the cabinet that could not be seen from the side of the cabinet a distance down the corridor. Fire extinguishers shall be conspicuously marked.

Interview with the construction project manager at the time of the observations confirmed those conditions.

The deficiency affected one of numerous requirements for installing and maintaining fire extinguishers.

Corridor - Doors

Tag No.: K0363

Based on observation, testing, and interview, the provider failed to ensure one randomly observed corridor door (4814 - Staff Lounge) would resist the passage of smoke. Findings include:

1. Observation and testing at 8:55 a.m. on 10/31/17 revealed the corridor door for room 4814 - staff lounge would not latch into the frame. The striker was recessed into the door and would not extend outward to engage the strike plate in the side of the frame.

Interview with the construction project manager at the time of the observation confirmed that finding.

The deficiency could affect one of the four smoke compartments on that floor.

Electrical Equipment - Power Cords and Extens

Tag No.: K0920

Based on observation and interview, the provider failed to ensure electrical service equipment was appropriately provided in one randomly observed location (lower level food service area). Findings include:

1. Observation at 10:45 a.m. on 10/31/17 revealed power strips in-use in the food service area used to supply power to miscellaneous devices. The use of the power strips was not justified as the availability of a power supply to provide permanent power was readily available for the select few items using the power strips.

Interview with the dietary manager at the time of the above observation confirmed that condition. She indicated the power strips were not a temporary use device and used a permanent power supply. Further interview with the maintenance manager at the time of the above observation revealed the electrical service tray the power strips were plugged into could be utilized to add permanent outlets.