Tag No.: K0011
Based on observations and staff interviews, the facility failed to provide 2-hour rated construction at building separation walls between the hospital building and the non-conforming building construction as required by NFPA 101" Life Safety Code " 2000 edition, sections 18.1.1.4.1. The deficient practice could negatively impact 11 patients of the facility by allowing a fire to spread from one building to another.
Findings include:
On facility tour between 9:00 AM and 2:00 PM on 9/08/2014, observation revealed on 1st floor, the 2 hour building separation wall from hospital to the emergency vehicle garage. The 90 minute fire rated doors did not positively latch when closed as required by 1999 NFPA 80 2-4.7.1.
This deficient practice was confirmed by the Maintenance Supervisor at the time of discovery.
Tag No.: K0130
Heliotropes shall be maintained in accordance with the 2007 MN State Fire Code. Section 1107.
Findings include:
On facility tour between 9:00 AM and 2:00 PM on 9/08/2014, it was observed that the helistop, which is located at ground level, away from the building, did not have an 80-BC fire extinguisher located in the helistop area as required by the 2007 MN State Fire Code, Section 1107.7.
Tag No.: K0011
Based on observations and staff interviews, the facility failed to provide 2-hour rated construction at building separation walls between the hospital building and the non-conforming building construction as required by NFPA 101" Life Safety Code " 2000 edition, sections 18.1.1.4.1. The deficient practice could negatively impact 11 patients of the facility by allowing a fire to spread from one building to another.
Findings include:
On facility tour between 9:00 AM and 2:00 PM on 9/08/2014, observation revealed on 1st floor, the 2 hour building separation wall from hospital to the emergency vehicle garage. The 90 minute fire rated doors did not positively latch when closed as required by 1999 NFPA 80 2-4.7.1.
This deficient practice was confirmed by the Maintenance Supervisor at the time of discovery.
Tag No.: K0130
Heliotropes shall be maintained in accordance with the 2007 MN State Fire Code. Section 1107.
Findings include:
On facility tour between 9:00 AM and 2:00 PM on 9/08/2014, it was observed that the helistop, which is located at ground level, away from the building, did not have an 80-BC fire extinguisher located in the helistop area as required by the 2007 MN State Fire Code, Section 1107.7.