10500 QUIVIRA ROAD

OVERLAND PARK, KS 66215

Building Rehabilitation

Tag No.: K0111

Building Rehabilitation
Repair, Renovation, Modification, or Reconstruction
Any building undergoing repair, renovation, modification, or reconstruction complies with both of the following:
* Requirements of Chapter 18 and 19
* Requirements of the applicable Sections 43.3, 43.4, 43.5, and 43.6
18.1.1.4.3, 19.1.1.4.3, 43.1.2.1
Change of Use or Change of Occupancy
Any building undergoing change of use or change of occupancy classification complies with the requirements of Section 43.7, unless permitted by 18.1.1.4.2 or 19.1.1.4.2
18.1.1.4.2 (4.6.7 and 4.6.11), 19.1.1.4.2 (4.6.7 and 4.6.11), 43.1.2.2 (43.7)
Additions
Any building undergoing an addition shall comply with the requirements of Section 43.8. If the building has a common wall with a nonconforming building, the common wall is a fire barrier having at least a 2-hour fire resistance rating constructed of materials as required for the addition.
Communicating openings occur only in corridors and are protected by approved self-closing fire doors with at least a 1 1/2-hour fire resistance rating. Additions comply with the requirements of Section 43.8.
18.1.1.4.1 (4.6.7 and 4.6.11), 18.1.1.4.1.1 (8.3), 18.1.1.4.1.2, 18.1.1.4.1.3, 19.1.1.4.1 (4.6.7 and 4.6.11), 19.1.1.4.1.1 (8.3), 19.1.1.4.1.2, 19.1.1.4.1.3, 43.1.2.3(43.8)
This STANDARD is not met as evidenced by:

Based upon observation, a review of records and staff interview, the facility fails to assure that a building undergoing, repair, renovation, modification, or reconstructions complies with the requirements of Chapter 18 and 19. The deficient practice increases the risk of fire or smoke spreading to other areas of the building, affecting all patients, visitors and staff.

During the 50% inspection on 8/27/19 it is observed:

1. At 9:00 AM during an inspection of the prep/recovery area it is observed that the ceiling tiles and grid have been completely removed from the area. Multiple walls have either been added or removed from this area. This is leaving rooms of the suite without sprinkler protection. Areas where the existing sprinkler heads remain, are observed greatly impaired due to the approximate 8-foot gap between the ceiling deck and the sprinkler deflectors. Many of the sprinklers are on flex piping with the pendant sprinkler head positioned parallel with the floor. In its present condition, the sprinkler system is significantly impaired. Acetylene cylinders used for hot work, and large amounts of combustible storage are observed throughout the suite. It is also observed that there is not proper 1-hour fire rated construction separating the on-going construction from the occupied portion of the building. The temporary partition walls that have been put in place to separate the two areas are one layer of ½ drywall with exposed metal studs on the construction side. Plastic sheeting is observed near the roof deck to also separate the two areas. These walls are being used to separate the construction area from a corridor, and a pre/post op patient area. There is also non ducted supply air being run through the work site into the corridor through grates that do not contain fire dampers.
2. At 9:20 AM during an inspection on the EP lab renovation project the ceiling grid is observed removed throughout the space. This creates an approximate 8-foot gap between the sprinkler deflectors and the ceiling deck. In the two procedure rooms, where there is drywall ceiling, the sprinklers are observed with the protective caps stills covering the sprinkler heads. There are not proper 1-hour fire rated walls separating the construction from the occupied portion of the building. Many of the previous door openings have had the doors removed and one layer of ½ inch drywall has been placed over the openings. No fire rated door frame is provided at the door to enter/exit the construction zone from the corridor, and there are two non-ducted air supply vents running to the corridor from the work zone.
Construction personnel and hospital EHS staff were present and acknowledged the findings and state that this situation has been in place for approximately 4 weeks, starting in late July.

NFPA Standard: Buildings shall be permitted to be occupied during construction, repair, alterations, or additions only when required means of egress and required fire protection features are in place and continuously maintained for the portion occupied or where alternative life safety measures acceptable to the AHJ are in place. 2012 NFPA 101, 4.6.10.1

NFPA Standard: Corridor walls shall be continuous from the floor to the underside of the floor or roof deck above; through any concealed spaces, such as those above suspended ceilings; and through interstitial structural and mechanical spaces, unless otherwise permitted by 19.3.6.2.4 through 19.3.6.2.8.
Corridor walls shall have a minimum 1?2-hour fire resistance rating.
Corridor walls shall form a barrier to limit the transfer of smoke.
In smoke compartments protected throughout by an approved, supervised automatic sprinkler system in accordance with 19.3.5.7, a corridor shall be permitted to be separated from all other areas by non-fire-rated partitions and shall be permitted to terminate at the ceiling where the ceiling is constructed to limit the transfer of smoke. 2012 NFPA 101, 19.3.6.2.1, 19.3.6.2.2, 19.3.6.2.3, 19.3.6.2.4

Sprinkler System - Out of Service

Tag No.: K0354

Where the sprinkler system is impaired, the extent and duration of the impairment has been determined, areas or buildings involved are inspected and risks are determined, recommendations are submitted to management or designated representative, and the fire department and other authorities having jurisdiction have been notified. Where the sprinkler system is out of service for more than 10 hours in a 24 hour period, the building or portion of the building affected are evacuated or an approved fire watch is provided until the sprinkler system has been returned to service.
18.3.5.1, 19.3.5.1, 9.7.5, 15.5.2 (NFPA 25)

This STANDARD is not met as evidenced by:
Based on observation, record review and interview the facility does not assure the fire watch procedure and policy is followed as required for implementation when the fire sprinkler system is out of service or impaired for more than 10 hours in a 24 hour period. This deficient practice would prevent proper notification of insurance carrier, the alarm company, property owner or designated representative, and other authorities having jurisdiction as required, affecting all visitors, patients, and staff.

Findings include:

During interview and policy review on 8/27/19 at 11:00 PM, and 1:00 PM, it is revealed that the facility's written policy for implementing a fire watch for sprinkler system impairment is to have taken affect anytime the sprinkler system is out of service for more than 10 hours. The policy states under the purpose heading, " During periods of maintenance, construction, or renovation the fire alarm or fire suppression system may be taken out of service for short periods of time. The purpose of this process is to allow OPRMC to determine when the fire watch will be required and for what duration." The policy also states under the scope heading, "Actions must be taken prior to taking the fire alarm or fire suppression system out of service and the recommendations are identified in the scope. This process must be placed in effect if one of the two following conditions are scheduled or unscheduled:1. Where a required fire alarm system is out of service for more than 4 hours in a 24-hour period. 2. Where a required fire protection system is out of service for more than 10 hours in a 24-hour period." Under the hospitals fire watch worksheet point 1 states, "A fire watch must be in place anytime a fire protection system is impaired. However, at the time of the 50% inspection, a portion of the sprinkler system had been significantly impaired for approximately 30 days, and walls had been rearranged creating areas without sprinkler protection without a fire watch being performed.

Construction personnel and hospital EHS staff were present and acknowledged the findings.

Review of the following NFPA Standard revealed: Sprinkler System Impairments. Sprinkler impairment procedures shall comply with NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water Based Fire Protection Systems. 2012 NFPA 101, 9.7.6

Review of the following NFPA Standard revealed: All preplanned impairments shall be authorized by the impairment coordinator. 2011 NFPA 25, 15.5.1

Review of the following NFPA Standard revealed: Before authorization is given, the impairment coordinator shall be responsible for verifying that the following procedures have been implemented:
(1) The extent and expected duration of the impairment have been determined.
(2) The areas or buildings involved have been inspected and the increased risks determined.
(3) Recommendations have been submitted to management or the property owner or designated representative.
(4) Where a required fire protection system is out of service for more than 10 hours in a 24 hour period, the impairment coordinator shall arrange for one of the following:
(a) Evacuation of the building or portion of the building affected by the system out of service
(b) An approved fire watch
(c) Establishment of a temporary water supply
(5) The fire department has been notified.
(6) The insurance carrier, the alarm company, property owner or designated representative, and other authorities having jurisdiction have been notified.
(7) The supervisors in the areas to be affected have been notified.
(8) A tag impairment system has been implemented. (See Section 15.3.)
(9) All necessary tools and materials have been assembled on the impairment site. 2011 NFPA 25, 15.5.2

Review of the following NFPA Standard revealed: Emergency impairments shall include, but are not limited to, system leakage, interruption of water supply, frozen or ruptured piping, and equipment failure. When emergency impairments occur, emergency action shall be taken to minimize potential injury and damage.
The coordinator shall implement the steps outlined in Section 15.5. 2011 NFPA 25, 15.6.1, 15.6.2 & 15.6.3

Review of the following NFPA Standard revealed: Restoring Systems to Service. When all impaired equipment is restored to normal working order, the impairment coordinator shall verify that the following procedures have been implemented:
(1) Any necessary inspections and tests have been conducted to verify that affected systems are operational. The appropriate chapter of this standard shall be consulted for guidance on the type of inspection and test required.
(2) Supervisors have been advised that protection is restored.
(3) The fire department has been advised that protection is restored.
(4) The property owner or designated Establishment and implementation of an approved program to eliminate potential ignition sources and limit the amount of fuel available to the fire
representative, insurance carrier, alarm company, and other authorities having jurisdiction have been advised that protection is restored.
(5) The impairment tag has been removed 2011 NFPA 25, 15.7