Tag No.: K0281
Based on observations during the tour of the hospital, the exit light in the administration wing is partially burned out.
Tag No.: K0321
Based on observations during the tour of the hospital, signage was missing from a few rooms. If the rooms are being used for storage adn are more than 100 square feet, that room should be rated.
Tag No.: K0344
Based on observations during the tour of the hospital, there is a piece of cardboard installed at the roof protecting fire alarm wires from rubbing against a piece of metal..
Based on review of the hospital's records, 2 quarterly inspections of the fire alarm system in 2020 and 2021 appeared to be missing. Please include the fire alarm testing as part of this plan of corrections.
Tag No.: K0353
Based on observations during the tour of the hospital, in the dietary department, several sprinkler heads are corroded in the kitchen work area.
Based on observations during the tour of the hospital, it appeared that several sprinkler heads that need to be lowered to proper height to provide adequate protection.
Based on observations during the tour of the hospital, fire sprinkler risers did not appear to have the correct inspection tags on them.
Based on review of the hospital's records, 2 quarterly inspections of the fire sprinkler system in 2020 and 2021 appeared to be missing. Please include the fire sprinkler testing as part of this plan of corrections.
Tag No.: K0521
Based on observations during the tour of the hospital, boxes stack against a piece of HVAC equipment, which may create a fire load.
Tag No.: K0900
Based on observations during the tour of the hospital, in the dietary department, the main kitchen cooking hoods were missing hood filters.
Based on observations during the tour of the hospital, in the dietary department, one of the kitchen cooking hoods has a large build up of grease on the filters