Bringing transparency to federal inspections
Tag No.: K0018
Based on interview and observation, the facility failed to ensure doors protecting corridor openings latched when closed. This has the potential to affect all staff, visitors, and patients in the building.
Findings:
On 06/19/12 at 10:00 A.M. a tour was conducted on the sixth floor with Staff P and R. This floor contained two in-patient sleeping units: a medical surgical unit and a hospice unit. Within the medical surgical unit the door of one patient room, designated 619, was observed at 11:41 A.M. to not latch when closed, and the door of the soiled linen room, designated 600.5, was observed at 11:38 A.M. not to latch when closed.
In interviews on 06/19/12 at 11:38 A.M. and 11:41 A.M., Staff P and R confirmed the observations.
Tag No.: K0020
Based on interview and observation, the facility failed to ensure all vertical openings, namely stairways had doors that latched when closed. This has the potential to affect all staff, visitors, and patients in the building.
Findings:
On 06/19/12 at 10:00 A.M. a tour was conducted on the sixth floor with Staff P and R. This floor contains two in-patient sleeping units: a medical surgical unit and a hospice unit. In the hospice unit, exit door designated 695.1 that led to the stairwell did not latch when allowed to close.
On 06/19/12 at 11:05 A.M. in an interview, Staff P and R confirmed the observation.
On 06/19/12 at 2:00 P.M. a tour was conducted with Staff P and R of the facility ' s fifth floor. The floor was observed to have on in-patient, medical surgical sleeping unit on the east side, and an outpatient clinic on the west side.
In the oncology exam rooms section of the oncology outpatient clinic door 595.1, which opens onto the exit stairwell, was observed at 3:13 P.M. to not latch when allowed to close.
On 06/19/12 at 3:13 P.M. in an interview, Staff P and R confirmed the observation.
On 06/21/12 at 2:40 P.M. a tour was conducted on the second floor area containing the cardiac care unit, the intensive care unit, and a step-down unit. At 2:50 P.M. the door to the western stairwell was observed not to latch when closed.
On 06/21/12 at 2:40 P.M. in an interview, Staff P and S confirmed the finding.
Tag No.: K0022
Based on facility tour and staff verification it was determined this facility failed to ensure all exit accesses were marked with visible signs in order to provide all occupants a readily available and safe access to exit discharges in the event of an emergency. This had the potential to affect all those utilizing these areas of the facility. The patient census at the beginning of the survey was 94.
Findings include:
Facility tour took place with staff member Q on 06/18/12 to 6/21/12. During tour of the lab observation was made from the southeast corner entrance facing west of no exit sign directing staff flow to the exit access stairwell located in the northwest section of the lab. This finding was verified by staff Q during tour of the lab.
Tag No.: K0025
21957
Based on facility tour and staff verification it was determined this facility failed to ensure smoke barriers were constructed with at least a one hour fire rated construction. This had the potential to affect all those utilizing these areas of the facility. The patient census was 94 at the beginning of the survey.
Findings include:
Facility tour took place with staff member Q on 06/18/12 to 6/21/12. During tour of the emergency department one hour fire rated smoke barriers observation was made of several penetrations above the ceiling tiles in the following locations:
*Four open end curved conduits in room #26
*Three open end curved conduits in room #1054
*Unsealed water line and one unsealed conduit above door 1120.5
*Gap greater than one eighth inch between doors leafs when in the closed position for door 1120.5
*Three unsealed conduits in the northwest corner of the staff breakroom 1134
*One unsealed green flex conduit just at the dividing wall between the vending area and cafe seating area
*One open end conduit with data wires passing through at southeast corner of room 1089
*One open end conduit with data wires passing through outside room 1087
*Within the waiting area, one unsealed green flex conduit around the annular space and one open end conduit located beside a cement beam.
*Outside room 1066 a curved conduit was not sealed around the annular space
*Above the door of room 1061, two open end conduits, additionally the door to room 1061 failed to close properly.
*Door of room 1059 failed to close properly.
*One three inch unsealed sleeve with wires was observed above door 1123.3.
*One inch square opening above door number 1136.
*Three unsealed conduits around the annular space to the left of door (electrical room) 1129, two unsealed three inch conduits with wires passing through above door number 1129.
*From within room 103.00D, one unsealed conduit around the annular space.
*Gap greater than one eighth inch between door leafs when in the closed position on door 103.00E.
*From within room 1102, south wall, two small penetrations around the annular space and inside the conduit.
These findings were verified by staff Q during tour of this area.
On 06/21/12 at 9:00 A.M. a tour with Staff P and R was conducted of the second floor section containing the operating room suites and the post-anesthesia care units. At 9:03 A.M. the smoke barrier above the double doors perpendicular to room c1 was observed to be pierced by a communication conduit with an unsealed opening.
At 9:42 A.M. the smoke barrier above the double doors perpendicular to room 2032 was observed to contain a conduit (one of three), closest to room 13, to have unsealed openings.
At 10:26 A.M. smoke barrier dividing room 28 from the corridor was observed to be pierced with a communication conduit pipe that had an unsealed annular space surrounding it.
At 10:30 A.M. the smoke barrier above the double doors perpendicular to the soiled utility room 2040 was observed to be pierced by an unsealed communication conduit.
On 06/21/12 at 9:03 A.M., 9:42 A.M., 10:26 A.M., and at 10:30 A.M. in an interview, Staff P and R confirmed the observations.
Tag No.: K0027
21957
Based on facility tour and staff verification it was determined this facility failed to ensure the door openings in smoke barriers provided at least a half hour fire resistance rating and were equipped with a self-closing or automatic closing device and were fire rated for at least 20 minutes. This had the potential to affect all those utilizing these areas of the facility. The facility census at the beginning of the survey was 94.
Findings include:
Facility tour took place with staff member Q on 06/18/12 to 6/21/12. During tour of the smoke barriers, observation was made of doors which failed to close properly or lacked a closing device in the following locations:
Ground floor:
*Door G36.18 in the cafeteria failed to close properly.
*Door G37.1A lacked a closing device.
First floor:
*Door 135.2B failed to shut properly with two attempts.
These findings were verified by staff Q during tour of these areas.
On 06/19/12 at 2:00 P.M. a tour was conducted with Staff P and R of the facility ' s fifth floor. The floor was observed to have on in-patient, medical surgical sleeping unit on the east side, and an outpatient clinic on the west side. According to the schematic review completed on 06/20/12, the floor has a smoke barrier that runs north/south between the two units.
On 06/19/12 at 2:38 P.M. doors 591.3 automated medication dispensing machine 591.4 were observed to be in the smoke barrier and not unrated. It was uncertain as to whether they were 1.75 inch thick solid bonded core wood.
On 06/19/12 at 2:38 P.M. in an interview, Staff P and R confirmed the observation.
On 06/21/12 at 11:15 A.M. a tour was conducted with Staff P and R on the second floor area containing the cardiac care unit, the intensive care unit, and a step-down unit. At 11:43 A.M. the door of room 240.51 was to be in the smoke barrier. The door was not observed to have a self-closer.
On 06/21/12 at 2:40 P.M. in an interview, Staff P and R confirmed the observation.
Tag No.: K0029
Based on facility tour and staff verification it was determined this facility failed to ensure hazardous areas were constructed with at least a one hour fire rated construction. This had the potential to affect all those utilizing these areas of the facility. The patient census was 94 at the beginning of the survey.
Findings include:
Facility tour took place with staff member Q on 06/18/12 to 6/21/12. During tour of the emergency department one hour fire rated hazardous areas observation was made of several penetrations above the ceiling tiles in the following locations:
*Room 1021 hole in the north wall, two unsealed sleeves and one open end conduit above the door.
*Room 1028 two holes with wires passing through in the north wall, two water lines passing through unsealed sleeves in the east wall and two unsealed sleeves in the south wall.
*Room 1044 unsealed duct above the door.
*Room 1055 a total of 11 open end conduits around the walls
*Room 1068 two open end conduits with green wires passing through in the north and west walls.
*Room 1084 unsealed one curved conduit.
*Room 1005 unsealed water line around the annular space at both ends.
These findings were verified by staff Q during tour of these rooms.
Tag No.: K0038
Based on observation and interview, the facility failed to ensure each exit had a safe access from the exit discharge to a public way. This affected two of three exit pathways.
Findings:
On 06/21/12 at 9:00 A.M. a tour of the building with Staff P and R was completed. The tour revealed the path of egress from the exit door perpendicular to room 15/6 had a concrete pad that terminated to grass that then led to a public way.
At 9:50 A.M. the path of egress from the exit door perpendicular to room 29 had a concrete pad that terminated to grass (without a ramp) that then led to a public way.
The concrete pad was observed to be surrounded by a wooden fence approximately 10 feet high surrounding the pad's perimeter. The pad had a handleless door, electronically locked. In spite of repeated attempts to open the fence's door, the door would not open until a staff member opened it from the outer side.
At 9:50 A.M. Staff P and R confirmed the findings.
Tag No.: K0042
Based on observation and interview, the facility failed to maintain a suite of rooms for the intensive care unit on the second floor to less than 5000 square feet according to National Fire Protection Association 101 Chapter 19.2.5.6.
Findings:
On 06/21/12 at 11:15 A.M. a tour was conducted with Staff P and R on the second floor area containing the cardiac care unit, the intensive care unit, and a step-down unit.
On 06/21/12 at 4:30 P.M. in an interview, Staff Q confirmed the intensive care unit suite of rooms had a combined square footage of greater than 5000 square feet.
Tag No.: K0046
Based on interview, the facility failed to ensure the building's emergency lighting was tested.
Findings:
On 06/21/11 at 4:30 P.M. in an interview Staff Q confirmed there wasn't any documentation of testing of the building's emergency lighting system.
Tag No.: K0047
Based on facility tour and staff verification it was determined this facility failed to ensure the exit and directional signs were illuminated continuously as required by the National Fire Protection Association. This had the potential to affect all those utilizing these areas of the facility. The patient census at the beginning of the survey was 94.
Findings include:
Facility tour took place with staff member Q on 06/18/12 to 6/21/12. During tour of the basement observation was made of an exit sign which was not lit. This sign was located at the double doors of the chiller room on the west end of the basement.
During tour of the ground floor electrical and mechanical rooms, observation was made of of approximately six exit signs which were not illuminating to the extent that this writer was able to discern if they were illuminated at all. The staff member present also verified they were unable to determine the same.
During tour of the ground floor boiler room number G36.1A, observation was made of an exit sign which was broken.
During tour of the first floor lab, observation was made of an exit sign located in the northwest section which was not illuminated.
These findings were verified by all staff members present during tour of these areas.
Tag No.: K0062
Based on observation during tour and staff verification it was determined this facility failed to ensure the automatic sprinkler system was maintained in reliable operating condition at all times, specifically in regards to dust and debris. This had the potential to affect all those utilizing these areas of the facility. The patient census at the beginning of the survey was 94.
Findings include:
Facility tour took place with staff member Q on 06/18/12 to 6/21/12. During tour of the ground floor observation was made of dirty sprinkler heads in rooms G13, staff breakroom within the pharmacy, and in the corridor G83 nearest the dock area.
During tour of the first floor observation was made of dirty sprinkler heads in rooms 122.2 and 135.16.
These findings were verified by staff Q during tour of these areas of the facility.
Tag No.: K0064
Based on observation during tour and staff verification it was determined this facility failed to ensure all portable fire extinguishers were readily accessible in the event of an emergency. This had the potential to affect all those utilizing this facility. The patient census was 94 at the beginning of the survey.
Findings include:
Facility tour took place with staff member Q on 06/18/12 to 6/21/12. During tour of the ground floor maintenance and garage area this writer observed one fire extinguisher located on the floor of room G11.4 with the inspection tag missing monthly inspections for April and May of 2012.
Another fire extinguisher was observed to mounted above the five foot limit on the west wall of the garage.
On the east wall of the garage another fire extinguisher was missing the May monthly inspection. Additionally, access to it was blocked by a metal frame leaning against it.
These observations were verified by staff Q during tour of this area.
Tag No.: K0070
Based on interview and observation, the facility failed to ensure there weren ' t any portable space heating devices in patient care areas. This has the potential to affect all staff, visitors, and patients in the building.
Findings:
On 06/19/12 at 10:00 A.M. a tour was conducted on the sixth floor with Staff P and R. Within the in-patient medical surgical unit, located on the East side of the building, a space heater was located in room designated as 645.4. (This was not a patient room.)
On 06/19/12 at 11:20 A.M. in an interview, Staff P and R confirmed the observation.
Within the in-patient hospice unit located on the West side of the building, at 10:20 A.M. a space heater was located in room designated as 632. (This room was not in use as a patient room.)
On 06/19/12 at 10:20 A.M. in an interview, Staff P and R confirmed the observation.
Tag No.: K0071
Based on observation during facility tour and staff verification it was determined this facility failed to ensure the trash and laundry chute was constructed to proved at least a one hour fire resistance rating, specifically in regards to the chute discharge doors. This had the potential to affect all those utilizing the floors in which the chute penetrated. The facility census at the beginning of the survey was 94.
Findings include:
Facility tour took place with staff member Q on 06/18/12 to 6/21/12. During tour of the ground floor laundry and trash chute discharge rooms observation was made of each chute door when in the closed position, having a one to two inch gap between the door and the bottom of the chute. This would enable smoke or fire to travel up the chute in the event of an emergency.
Additionally, within the mechanical room a laundry chute was observed. This chute had a door that was closed and latched shut. Staff Q stated this chute was not used any longer. This writer had staff Q open and close the chute door. When the door was tested, it failed to latch shut.
These findings were verified by staff Q during tour of these areas.
Tag No.: K0078
Based on operating room (OR) and labor and delivery (L & D) room relative humidity (RH) documentation review and staff verification it was determined this facility failed to ensure the RH was maintained at the required 35% or greater in all 10 operating rooms and the labor and delivery room. This had the potential to affect all those who utilized these areas of the facility. The patient census was 94 at the beginning of the survey.
Findings include:
The documentation review for the operating room and labor and delivery room RH levels were reviewed on 06/18/12 with staff members P and Q. During review observation was made of several days during the months of November 2011 through March 2012 where the RH levels were below the required 35%. The number of days below the required 35% RH were:
OR # 1:
November 2011, 13 days.
December 2011, 16 days
January 2012, 18 days.
February 2012, 19 days.
March 2012, 11 days.
OR #2:
November 2011, 11 days.
December 2011, 16 days.
January 2012, 18 days.
February 2012, 20 days.
March 2012, 13 days.
OR #3:
November 2011, 7 days.
December 2011, 12 days.
January 2012, 17 days.
February 2012, 14 days.
March 2012, 10 days.
OR #4:
November 2011, 10 days.
December 2011, 12 days.
January 2012, 18 days.
February 2012, 16 days.
March 2012, 9 days.
OR #5:
November 2011, 12 days.
December 2011, 13 days.
January 2012, 18 days.
February 2012, 18 days.
March 2012, 12 days.
OR #6:
November 2011, 11 days.
December 2011, 14 days.
January 2012, 19 days.
February 2012, 20 days.
March 2012, 11 days.
OR #7:
November 2011, 12 days.
December 2011, 14 days.
January 2012, 19 days.
February 2012, 18 days.
March 2012, 11 days.
OR #8:
November 2011, 11 days.
December 2011, 14 days.
January 2012, 20 days.
February 2012, 18 days.
March 2012, 11 days.
OR #9:
November 2011, 12 days.
December 2011, 14 days.
January 2012, 19 days.
February 2012, 20 days.
March 2012, 11 days.
OR #10:
November 2011, 10 days.
December 2011, 15 days.
January 2012, 18 days.
February 2012, 19 days.
March 2012, 10 days.
L & D:
January 2012, 28 days.
February 2012, 29 days.
March 2012, 7 days.
These findings were verified by both staff members during the documentation review of the RH levels in the OR's and L& D rooms.
Tag No.: K0130
Based on documentation review and staff verification it was determined this facility failed to ensure quarterly sprinkler tests according to NFPA 25 Chapter 2-1. This facility failed to ensure the testing of the emergency battery operated lights were documented monthly and annually as required by NFPA 101 Chapter 7.9.3. This facility failed to ensure the testing of smoke detectors as required by NFPA 72, Chapter 7-3.2.1 This had potential to affect all those utilizing this facility.
Findings:
On 06/21/11 at 4:30 P.M. in an interview Staff Q confirmed there wasn ' t any documentation of testing on the building ' s smoke detectors, the sprinkler system was not tested quarterly, and there wasn ' t any documentation of the building ' s emergency lighting system being tested.