Tag No.: K0018
Based on observation, it was determined that the facility failed to ensure there there was no impediment to closing the corridor door.
Findings include:
1. On 11/12/13 at 11:25 AM, in the presence of Staff #59, at Room #C119, the corridor door could not automatically close.
Tag No.: K0029
Based on observation, it was determined that the facility failed to provide a one hour rated construction for hazardous areas.
Findings include:
1. On 11/12/13 at 10:25 AM, in the presence of Staff #59, in Room #A213:
a. The wall between the storage room and the office was non rated.
b. There was a penetration in the corridor wall.
Tag No.: K0047
Based on observation, it was determined that, the facility failed to provide and illuminate exit signs at all exits.
Findings include:
1. On 11/12/13 at 1:45 PM, in the presence of Staff #59, in the C level corridor at C138, there was no exit sign.
2. On 11/13/13 at 2:15 PM, in the presence of Staff #59, in the G level corridor, there was no exit sign in front of the smoke door.
Tag No.: K0062
Based on observation, it was determined that the facility failed to maintain and inspect the sprinkler system.
Findings include:
1. On 11/12/13 at 10:35 AM in the presence of Staff #59, four boxes were stored within 18" of the sprinkler system in the shop.
2. On 11/13/13 at 11:20 AM in the presence of Staff #59, two boxes were stored within 18" of the sprinkler system in Room #D341.
Tag No.: K0076
Based on observation, it was determined that the facility failed to protect gas in storage in accordance with NFPA 99 4-3.1.1.1.
Findings include:
1. On 11/12/12 at 10:35 AM in the presence of Staff #59, four tanks of gas it were observed unsecured in the shop. NFPA 99 4-3.1.1.1 states cylinders in service and in storage shall be secured and located to prevent falling or being knocked over.
Tag No.: K0211
Based on observation, it was determined that the facility failed to ensure that Alcohol Based Hand Rubs (ABHR) are not located above ignition sources.
Findings include:
1. On 11/12/13 at 11:25 AM in the presence of Staff #59, two ABHRS were located on top of a computer tower.
Tag No.: K0018
Based on observation, it was determined that the facility failed to ensure there there was no impediment to closing the corridor door.
Findings include:
1. On 11/12/13 at 11:25 AM, in the presence of Staff #59, at Room #C119, the corridor door could not automatically close.
Tag No.: K0029
Based on observation, it was determined that the facility failed to provide a one hour rated construction for hazardous areas.
Findings include:
1. On 11/12/13 at 10:25 AM, in the presence of Staff #59, in Room #A213:
a. The wall between the storage room and the office was non rated.
b. There was a penetration in the corridor wall.
Tag No.: K0047
Based on observation, it was determined that, the facility failed to provide and illuminate exit signs at all exits.
Findings include:
1. On 11/12/13 at 1:45 PM, in the presence of Staff #59, in the C level corridor at C138, there was no exit sign.
2. On 11/13/13 at 2:15 PM, in the presence of Staff #59, in the G level corridor, there was no exit sign in front of the smoke door.
Tag No.: K0062
Based on observation, it was determined that the facility failed to maintain and inspect the sprinkler system.
Findings include:
1. On 11/12/13 at 10:35 AM in the presence of Staff #59, four boxes were stored within 18" of the sprinkler system in the shop.
2. On 11/13/13 at 11:20 AM in the presence of Staff #59, two boxes were stored within 18" of the sprinkler system in Room #D341.
Tag No.: K0076
Based on observation, it was determined that the facility failed to protect gas in storage in accordance with NFPA 99 4-3.1.1.1.
Findings include:
1. On 11/12/12 at 10:35 AM in the presence of Staff #59, four tanks of gas it were observed unsecured in the shop. NFPA 99 4-3.1.1.1 states cylinders in service and in storage shall be secured and located to prevent falling or being knocked over.