Bringing transparency to federal inspections
Tag No.: K0011
Based on observation, the facility failed to maintain a 2 hour fire wall separations between building separations.
Findings include:
The fire wall which separates the South Tower from the Surgical Tower was reviewed where it bypasses the women's bath on second floor. There is a portion of the fire wall which is incomplete as it is only sheeted on one surface of the metal studs near the back wall of the bath above the ceiling tile.
Tag No.: K0012
Based on observations, it was determined that the facility failed to ensure that all fire rated construction was complete.
Findings include:
On 07/31/2012 on the Fourth Floor at 8:40 a.m., there was a section of interior wall missing in room 483.
Tag No.: K0014
Based on observation, the facility failed to remove raw wood surfaces after completing construction between floors.
Findings include:
The interior spaces above the Reading Room #4 were observed at 11:30 a.m. on 7/31/2012. Wood construction had been used to enclose a chute between floors on first and second floor. The raw wood had not been removed after concrete was poured over the wood forms between the floors.
Tag No.: K0017
Based on observations, the facility did not maintain the fire resistive construction of all corridor walls to resist the passage of smoke.
Findings include:
On 7/31/2012 at 8:04 a.m., an unsealed pipe/conduit, approximately one and one-half inch in diameter, penetrated the corridor wall above the door and the ceiling tiles in G101 Communication room.
Tag No.: K0018
Based on observations, it was determined that the facility failed to ensure that all corridor doors were not impeded from closing.
Findings include:
1. On 07/31/2012 at 8:17 a.m. on Fourth Floor, a water bottle rack blocked the corridor door from closing.
2. On 07/31/2012 at 11:30 a.m. on the Second Floor, the corridor door with self-closing hardware to room 2420 (HVAC room) would not closing to positive latching.
3. On 07/31/2012 at 1:35 p.m., one of two main entrance doors to the cafeteria would not close to positive latching.
4. On 07/31/2012 at 4:15 p.m., one of two corridor doors to the Biomedical/Housekeeping Department did not close to positive latching.
20343
5. The corridor door to Room 4 labeled with (143) on the frame above the door in the Emergency Room hall which exits to the east near the heliport was observed to have roller latching hardware as observed at 1:30 p.m. on 7/1/2012.
There is an exception for only bathroom doors having roller latches in existing health care facilities.
Tag No.: K0020
Based on observations, the facility did not maintain the one-hour fire resistance rating of all vertical openings at stairways.
Findings include:
On 7/31/2012 at 8:30 a.m., the door to the stairway for the employee entrance at the ground level was exercised. The door was held by a magnetic device. The door did not latch when released from the magnetic device three times.
Tag No.: K0021
Based on observations, it was determined that the facility failed to ensure that all doors requiring self-closing hardware closed to positive latching.
Findings include:
1. On 07/31/2012 at 7:31 a.m. on the Fifth Floor, the self-closing door at the west end stairwell did not close to positive latching.
2. On 08/01/2012 at 8:17 a.m. on the First Floor, a stairway door would not close to positive latching.
Tag No.: K0022
Based on observations, it was determined that the facility failed to ensure that all exit locations are adequately identified.
Findings include:
In accordance with NFPA 101, Section 7.10.1.4; access to exits is marked by approved, readily visible signs in all cases where the exit or way to reach exit is not readily apparent to the occupants.
On 08/01/2012 at 6:30 a.m. in the Operating Room (OR) Suite, there is no visible exit sign from the internal corridor by OR #6 to identity means of exiting to the other side of the smoke barrier doors.
Tag No.: K0025
Based on observations, it was determined that the facility failed to ensure that all smoke barriers are intact.
Findings include:
In accordance with Section 8.3.6.1 of NFPA 101, 2000 Edition; pipes, conduits, bus ducts, cables, wires, air ducts, pneumatic tubes and ducts, and similar building service equipment that pass through floors and smoke barriers shall be protected as follows: (1) The space between the penetrating item and the smoke barrier shall meet one of the following conditions: a) It shall be filled with a material that is capable of maintaining the smoke resistance of the smoke barrier.
1. On 07/30/2012 at 3:05 p.m., the west door of the smoke barrier doors on Eighth Floor did not close to positive latching when the door was released.
2. On 07/30/2012 on the Seventh Floor, there was an unsealed smoke barrier penetration in the smoke barrier.
3. On 07/31/2012 at 8:15 a.m. on the Fourth Floor, there was an unsealed penetration above smoke barrier doors.
4.On 7/31/2012 at 8:15 a.m. on the Fourth Floor, there was a two to three inch unsealed penetration in the smoke barrier separating the "gutted section " from the rest of the Fourth Floor.
5. On 07/31/2012 at 10:25 a.m., one of two smoke barrier doors located by the Security Office would not close to positive latching.
6. On 08/01/ 2012 at 6:30 a.m. in the OR Suite, one of two smoke barrier doors did not close to positive latching.
Tag No.: K0027
Based on observations, the facility did not ensure all smoke/fire rated construction was protected from the passage of smoke by rated doors.
Findings include:
In accordance with NFPA 101 and Section 19.3.7.3; any required smoke barrier shall be constructed in accordance with Section 8.3 and shall have a fire resistance rating of not less than 1/2 hour.
On 7/31/2012 at 8:45 a.m., the rated smoke barrier doors, found in the smoke/fire separation construction in the elevator corridor at Ground Level, were examined. The doors did not positively latch. At 3:55 p.m., the doors were examined again with the activation of the fire alarm. The doors failed to latch at this time also.
Tag No.: K0029
Based on observations, the facility failed to ensure that all corridor doors serving hazardous areas were equipped with with closing hardware.
Findings include:
In accordance with NFPA 101 and Section 19.3.2.1 Hazardous Areas; any hazardous areas shall be safeguarded by a fire barrier having a 1-hour fire resistance rating or shall be provided with an automatic extinguishing system in accordance with 8.4.1. The automatic extinguishing shall be permitted to be in accordance with 19.3.5.4. Where the sprinkler option is used, the areas shall be separated from other spaces by smoke-resisting partitions and doors. The doors shall be self-closing or automatic-closing. Hazardous areas shall include, but shall not be restricted to, the following:
(1) Boiler and fuel-fired heater rooms
(2) Central/bulk laundries larger than 100 ft2 (9.3 m2)
(3) Paint shops
(4) Repair shops
(5) Soiled linen rooms
(6) Trash collection rooms
(7) Rooms or spaces larger than 50 ft2 (4.6 m2), including repair shops, used for storage of combustible supplies and equipment in quantities deemed hazardous by the authority having jurisdiction
(8) Laboratories employing flammable or combustible materials in quantities less than those that would be considered a severe hazard.
Exception: Doors in rated enclosures shall be permitted to have nonrated, factory- or field-applied protective plates extending not more than 48 in. (122 cm) above the bottom of the door.
On 07/31/2012 at 8:35 a.m. on the Fourth Floor, it was observed that room 475 was being used for combustible storage. The corridor door to this room was not equipped with self-closing hardware.
Tag No.: K0033
Based on observations, the facility failed to ensure that all means of egress in stairwells were not obstructed.
Findings include:
In accordance with NFPA 101, Sections 19.3.1.1 and 8.2.5.2; exit components (such as stairways) are enclosed with construction having a fire resistance rating of at least one hour, are arranged to provide a continuous path of escape, and provide protection against fire or smoke from other parts of the building.
1. On 07/30/2012 at 4:35 p.m. on the Fifth Floor of the North Tower, the west end stairwell across from room #508 was obstructed by a five gallon bucket and a "rolled up" section of rope.
2. On 07/31/2012 at 7:35 a.m. in the East stairwell of the North Tower, the means of egress in the stairwell was partially blocked by the presence of a yellow five gallon bucket sitting on the floor of a landing.
Tag No.: K0038
Based on observations, the facility did not ensure that alternate exit discharges were clearly marked at all times at construction zones.
Findings include:
On 7/31/2012 at 10:50 a.m., the Roof Garden construction project was examined with staff member B. The first floor emergency exiting route was temporary closed. The public was directed from first floor to the ground level for emergency exiting at this juncture. However, the public was also directed to the first floor from the ground level for emergency exiting to the construction site where temporarily no emergency exiting was possible.
Tag No.: K0046
Based on observation, the facility did not ensure that a battery-powered emergency lighting was provided in the generator transfer switch room.
Findings include:
In accordance with NFPA 101 Life Safety Code 2000 Edition, Chapter 38, Section 38.2.9, emergency lighting shall be provided in accordance with Section 7.9 in any building where "the building is two or more stories in height above the level of discharge, the occupancy is subject to 50 or more occupants above or below the level of exit discharge. . . "
In accordance with 7.9 of the NFPA 101 Life Safety Code (LSC) 2000 Edition, the room housing the emergency generator and the generator transfer switches shall be provided with battery-powered emergency lighting. Additionally, in accordance with 7.9.3 of the LSC, a functional test shall be conducted on every required emergency lighting system at 30-day intervals for not less than 30 seconds. An annual test shall be conducted on every required battery-powered emergency lighting system for not less than one and one-half hours. Equipment shall be fully operational for the duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction.
On 8/1/2012 at 9:38 a.m., the generator transfer switch room was inspected. The room did not have battery powered emergency lighting.
Tag No.: K0054
Based on observation, the facility failed to maintain the installed smoke detection system in accordance with the manufacturer's required specifications and NFPA 72, 1999 Edition.
Findings include:
In accordance with NFPA 72 and Section 7-3.1, visual inspection shall be performed in accordance with the schedules in Section 7-3 or more often if required by the authority having jurisdiction. The visual inspection shall be made to ensure that there are no changes that affect equipment performance.
Exception No. 1: Devices or equipment that is inaccessible for safety considerations (for example, continuous process operations, energized electrical equipment, radiation, and excessive height) shall be inspected during scheduled shutdowns if approved by the authority having jurisdiction. Extended intervals shall not exceed 18 months.
Exception No. 2: If automatic inspection is performed at a frequency of not less than weekly by a remotely monitored fire alarm control unit specifically listed for such application, the visual inspection frequency shall be permitted to be annual. Table 7-3.1 shall apply. Table 7-3.1 Visual Inspection Frequencies requires that smoke detectors shall be visually inspected at least semiannually.
1. The stair tower on the south side of the South Tower was observed at 1:30 p.m. on 7/30/2012. The smoke detector on the ceiling of the stair tower was covered with a paper bag.
2. Electrical room 6175 on the South Tower sixth floor was observed at 3:00 p.m. on 7/30/2012. The room smoke detector was covered with a rubber glove.
Tag No.: K0056
Based on observation, the facility did not ensure that all portions of the building were protected by the automatic sprinkler system.
Findings include:
Sprinklers shall be installed under fixed obstructions over 4 feet wide such as ducts, decks, open grate flooring cutting tables, and overhead doors per section 5-5.5.3.1 of NFPA 13, 1999 Edition.
On 7/30/2012 at 3:40 p.m., there was no sprinkler coverage under the air over flow duct, where it was approximately 11 feet wide in the West Campus building penthouse.
Tag No.: K0062
Based on observations, the facility failed to maintain the sprinkler system and its components in accordance with the standards of NFPA 13, 1999 Edition.
Findings include:
In accordance with NFPA 13 and Section 3-2.7.2, escutcheon plates used with a recessed or flush-type sprinkler shall be part of a listed sprinkler assembly.
1. On 7/31/2012 at 11:00 a.m., the escutcheon ring was missing from the ceiling sprinkler head in Clark room telephone room G238 ceiling.
2. On 7/31/2012 at 11:16 a.m., there was an annular space between the ceiling tile and the escutcheon ring in room G214B Information Systems.
Tag No.: K0064
Based on observations, it was determined that the facility failed to ensure that all requirements of NFPA 10 were being followed.
Findings include:
In accordance with 1-6.7 and 1-6.10 of NFPA 10, (1998 Edition); portable extinguishers other than wheeled types shall be securely installed on the hanger or bracket supplied with them or placed in cabinets or wall recesses. In no case shall the clearance between the bottom of the supported extinguisher and the floor be less than 4 inches. Extinguishers weighing less than or equal to 40 lb shall be installed so that the top of the extinguisher is not more than 5 feet (60 Inches) above the floor. Those extinguishers with a weight more than 40 lb shall be installed so that the top of the extinguisher is not more than 3 1/2 feet (42 inches) above the floor.
1. In the stairwell of "Stairway #2" which opens from the "gutted" section of the Fourth Floor, there were two unsecured fire extinguishers sitting on the stair landing.
29778
In accordance with 4-4.1 of NFPA 10 (1998 Edition) fire extinguishers shall be subject to maintenance at intervals of not more than 1 year. Furthermore, in accordance with 4-4.4 of NFPA 10, each extinguisher shall have a tag or label attached that indicates the month and year the maintenance was performed.
2. The two "K" type portable fire extinguishers located in the kitchen of the hospital had not received an annual service since July 2011.
Tag No.: K0072
Based on observations, the facility did not maintain exit corridors free from obstructions that would interfere with their instant use in case of fire or other emergency.
Findings include:
In accordance with the Centers for Medicare and Medicaid Services Survey and Certification letters S&C-04-41 and S&C-10-18, items not in use in exit corridors (i.e. left unattended for more than 30 minutes), such as linen carts, medication carts, janitorial equipment, chairs, wheelchairs, delivery items and other similar items must be stored properly or removed from the corridor.
On 7/31/2012 at 7:55 a.m., several furniture pieces, TVs and other cardboard boxes of stored items were observed on the Loading/Garbage exit corridor. When asked during the observation, one house keeping staff stated that these obstructions were in the exit corridor over a month.
Tag No.: K0076
Based on observation, the facility did not ensure that all oxidizing gases were stored properly.
Findings include:
Locations for storage of nonflammable gases, including oxygen, of less than 3000 cubic feet shall be vented to the outside by a dedicated mechanical ventilation system or by natural venting per section 4-3.1.1.2(c) of NFPA 99, 1999 Edition. If natural venting is used, the vent openings shall each be a minimum of 72 square inches in total free area. Where the location of the storage door opens onto an exit access corridor, louvered openings shall not be used.
On 7/31/2012 at 11:55 a.m., the oxygen storage room was examined and observed that the mechanical ventilation was not in operational condition. The motor to the ventilation unit was broken down. There were 44 E size cylinders stored in the room at the time of the observation.
Tag No.: K0077
Based on observation and interview with maintenance staff, the facility did not ensure that bulk medical gas systems that had been renovated or had components breached were inspected and tested in accordance with NFPA 99, 1999 Edition and NFPA 50, 1996 Edition.
Findings include:
In accordance with NFPA 99 and section (b) Additional Storage Requirements for Nonflammable Gases Greater Than 3000 ft3 (85 m3) the following applies:
1. Oxygen supply systems or storage locations having a total capacity of more than 20,000 ft3 (566 m3) (NTP), including unconnected reserves on hand at the site, shall comply with NFPA 50, Standard for Bulk Oxygen Systems at Consumer Sites. Further in accordance with NFPA 50, Chapter 4-2.1; each bulk oxygen system installed on consumer premises shall be inspected annually and maintained by a qualified representative of the equipment owner.
Further, in accordance with NFPA 99, 1999 Edition, and Section 4-3.4.1.1, inspection and testing shall be performed on all new piped gas systems, additions, renovations, temporary installations, or repaired systems, to assure the facility, by a documented procedure, that all applicable provisions of this document have been adhered to and system integrity has been achieved or maintained.
This inspection and testing shall include all components of the system or portions thereof including, but not limited to, gas bulk source(s), manifolds, compressed air source systems (e.g., compressors, dryers, filters, regulators), source alarms and monitoring safeguards, master alarms, pipelines, isolation valves, area alarms, zone valves, and station inlets (vacuum) and outlets (pressure gases).
All systems that are breached and components that are subject to additions, renovations, or replacement (e.g., new gas sources-bulk, manifolds, compressors, dryers, alarms) shall be inspected and appropriately tested.
Systems shall be deemed breached at the point of pipeline intrusion by physical separation or by system component removal, replacement, or addition. The breached portions of the systems subject to inspection and testing shall be confined to only the specific altered zone and components in the immediate zone or area that is located upstream for vacuum systems and downstream for pressure gases at the point or area of intrusion.
The inspection and testing reports shall be verified and a certificate and submitted directly to the party that contracted for the testing. That party shall then submit the report through channels to the responsible authority and any others that are required. These reports shall contain detailed listings of all findings and results.
The responsible facility authority shall review these inspection and testing records prior to the use of all systems. This responsible facility authority shall ensure that all findings and results of the inspection and testing have been successfully completed, and all documentation pertaining thereto shall be maintained on-site within the facility.
Before piping systems are initially put into use, the health care facility authority shall be responsible for ascertaining that the gas delivered at the outlet is that shown on the outlet label and that the proper connecting fittings are checked against their labels. This can be accomplished by accepting the results of 4-3.4.1.3, System Verification.
Manufactured assemblies shall, prior to arrival at the installation site, be pretested to comply with 4-3.4.1.2(a) through 4-3.4.1.2(e), except that 4-3.4.1.2(c) shall be permitted to be performed by any leak testing method that will assure a pressure decay of less than 1 percent in 24 hours. The manufacturer shall provide documentation attesting to the performance and successful completion of these tests.
Inspection and testing reports for the bulk medical gas system were reviewed on 7/31/2012. The most recent report was dated 6/16/2007 for the west campus building. NFPA 99, Chapter 4-2.1 requires bulk oxygen systems to be inspected annually by a certified verifier.
Interview with maintenance staff at 4:35 p.m. on 8/1/2012, revealed that no further testing had been done on the medical gas system since the 6/16/2007 report. Many areas of the surgical tower had been renovated and a new inspection and testing certification had not been done on the updated medical gas system to ensure the systems integrity has been achieved and maintained.
Tag No.: K0130
Based on observation, the facility did not secure empty acetylene tanks and did not ensure an electric heater was safely used and stored away from combustibles.
Findings include:
Freestanding cylinders of nonflammable gases (such as oxygen) shall be properly chained or supported in a cylinder cart or stand or by means of racks or fastenings to protect them from falling over or being knocked down per sections 8-3.1.11.2(h) and 4-3.5.2.1(b27) of NFPA 99, 1999 Edition.
1. On 7/31/12 at 7:33 a.m., an acetylene tank was observed outside the boiler room. The pressurized tank was free standing in a corner of a fenced area and was not secured properly.
In accordance to NFPA 70, Chapter 4 -424-20(a) which states:
Thermostatically controlled switching devices and combination thermostats and manually controlled switches shall be permitted to serve as both controllers and disconnecting means, provided all of the following conditions are met:
1. Provided with a marked "off " position
2. Directly open all ungrounded conductors when manually placed in the " off " position
3. Designed so that the circuit cannot be energized automatically after the device has been manually placed in the "off" position
4. Located as specified in Section 424-19.
2. On 7/31/12, an observation of an electric heater in office 1514 revealed a foot rest pushed against the heater. The controls for the electric heater were attached to the front of the desk and the control knob was missing, making it visually impossible to determine if the heater was on or off.
Tag No.: K0140
Based on observations, it was determined that the facility failed to ensure that all gas/vacuum lines were properly deactivated.
Findings include:
On 07/31/2012 at 9:12 a.m. on the " vacated " Third Floor, a gas/vacuum panel was examined. Although gas /vacuums system were to have been deactivated, " Line Pressure Abnormal " was illuminated. The audible signal was active and needed to be silenced by staff personnel.
Tag No.: K0141
Based on observations, it was determined that the facility failed to ensure that all requirements for identifying the location of oxygen storage was properly labeled and identified.
Findings include:
In accordance with NFPA 99, 1999 Edition, Section 8-3.1.11.3 Signs; a precautionary sign, readable from a distance of 5 ft (1.5 m), shall be conspicuously displayed on each door or gate of the storage room or enclosure. The sign shall include the following wording as a minimum:
CAUTION
OXIDIZING GAS(ES) STORED WITHIN
NO SMOKING
All room locations of oxygen storage in the North Tower lack the mininum posting requirements.
Tag No.: K0147
Based on observations, it was determined that the facility failed to ensure that all requirements of the National Electrical Code (NFPA 70) were followed.
Findings include:
Flexible cords and cables shall be connected to devices and to fittings so that tension will not be transmitted to joints or terminals per Article 400-10 of NFPA 70.
1. On 07/30/2012 on the Sixth Floor at 4:03 p.m., there was an unsecured power strip hanging for an electrical outlet in the staff break room.
In accordance with Article 110-26 and table 110-26(a) of NFPA 70 there shall be maintained a clear working space of at least 36" around electrical equipment such as panel boards to permit ready and safe operations of such equipment. This working space can not be used for storage purposes.
2. On 08/01/2012 at 9:46 a.m. on the First Floor in room 1047A, electrical panel "D.W 1120/208 3PH OMB-1" had access blocked by cardboard boxes, metal equipment and other materials in front of the panel.
Each disconnecting means and each service at the point where it originates shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident per Article 110-22 of NFPA 70.
3. On 08/01/2012 at 9:13 a.m. on First Floor in room 1317 HVAC, there was no legend posted in electrical panel "Panel AG MSB-4."
4. On 08/01/2012 at 9:14 a.m. on First Floor in room 1227, there was wooden pallet blocking access to electrical panel "Panel EL 120/208V/30W"
In completed installations, each box shall have a cover, faceplate, or fixture canopy according to Artilce 370-25.
5. On 08/01/2012 at 9:15 a.m. on First Floor in room 1227, there was an uncovered electrical junction box exposing four unconnected wires.
6. On 7/31/2012 at 1:25 p.m. on the First Floor in room 2420, there was an electrical outlet which lacked a cover plate.
7. On 7/31/2012 at 4:25 p.m. on the First Floor in the Biomedical/Housekeeping Department, there was an electrical junction box which lacked a cover plate.