HospitalInspections.org

Bringing transparency to federal inspections

718 TEANECK RD

TEANECK, NJ 07666

No Description Available

Tag No.: K0062

Based on observation, it was determined that the facility failed to ensure the sprinkler system was continuously maintained.

Findings include:

1. On 1/23/14 at 10:50 AM, in the presence of Staff #43, in the wood shop, trim pieces were stored within 18" of the sprinkler.

No Description Available

Tag No.: K0076

Based on observation, it was determined that the facility failed to ensure the protection of compressed gas from being knocked over was maintained.

Findings include:

1. On 1/23/14 at 11:40 AM, in the presence of Staff #43, it was observed that in the Lab, one tank of gas was not secured. NFPA 99 4-3.1.1.1 states cylinders in service and in storage shall be secured and located to prevent falling or being knocked over.

No Description Available

Tag No.: K0134

Based on observation, it was determined that the facility failed to ensure eye washes were available for immediate use.

Findings include:

1. On 1/23/14 at 10:30 AM, in the presence of Staff #43, in the lab hazardous waste room, the eye wash station was blocked by boxes.