Bringing transparency to federal inspections
Tag No.: K0211
Based on record review and interview, the facility failed to ensure that fire and smoke door assemblies were inspected in accordance with NFPA 80 and NFPA 105. Failure to inspect and test fire and smoke doors, could result in a lack of system performance as designed which could hinder the safe evacuation during a fire or other emergency. This deficient practice affected all patients, staff and visitors on the date of the survey. The facility is licensed for 11 beds and had a census of 3 on the day of the survey.
Findings include:
During record review on July 6, 2017, from approximately 10:45 AM to 1:00 PM, no record was available demonstrating an annual inspection and testing of the fire and smoke door assemblies had been completed. When asked about the missing documentation, the Maintenance Supervisor stated the facility was unaware of this requirement.
Actual NFPA standard:
NFPA 101
19.2.1 General.
Every aisle, passageway, corridor, exit discharge, exit location, and access shall be in accordance with Chapter 7, unless otherwise modified by 19.2.2 through 19.2.11.
7.2.1 Door Openings.
7.2.1.15 Inspection of Door Openings.
7.2.1.15.1* Where required by Chapters 11 through 43, the following door assemblies shall be inspected and tested not less than annually in accordance with 7.2.1.15.2 through 7.2.1.15.8:
(1) Door leaves equipped with panic hardware or fire exit hardware in accordance with 7.2.1.7
(2) Door assemblies in exit enclosures
(3) Electrically controlled egress doors
(4) Door assemblies with special locking arrangements subject to 7.2.1.6
7.2.1.15.2 Fire-rated door assemblies shall be inspected and tested in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives. Smoke door assemblies shall be inspected and tested in accordance with NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives.
NFPA 80
5.2* Inspections.
5.2.1* Fire door assemblies shall be inspected and tested not less than annually, and a written record of the inspection shall be signed and kept for inspection by the AHJ.
NFPA 105
5.2 Specific Requirements.
5.2.1* Inspections.
5.2.1.1 Smoke door assemblies shall be inspected annually.
5.2.1.2 Doors shall be operated to confirm full closure.
5.2.1.3 Hardware and gaskets shall be inspected annually, and any parts found to be damaged or inoperative shall be replaced.
Tag No.: K0325
Based on record review, observation and interview, the facility failed to ensure Alcohol Based Hand Rub Dispensers (ABHR) were maintained in accordance with NFPA 101. Failure to test and document the operation of ABHR dispensers in accordance with the manufacturer's care and use instructions each time a new refill is installed could result in inadvertently spilling flammable liquids, increasing the risk of fires. This deficient practice affected 3 residents, staff and visitors on the date of the survey. The facility is licensed for 11 beds and had a census of 3 on the day of the survey.
Findings include:
During the review of facility inspection records conducted on July 6, 2017 from approximately 10:45 AM to 1:00 PM, no records were available indicating ABHR dispensers are tested in accordance with manufacturer's care and use instructions when a new refill is installed. ABHR dispensers were observed throughout the facility and when asked, the Maintenance Supervisor stated the facility was not aware of the requirement to test ABHR dispensers each time a new refill is installed.
Actual NFPA standard:
NFPA 101
19.3.2.6* Alcohol-Based Hand-Rub Dispensers.
Alcohol-based hand-rub dispensers shall be protected in accordance with 8.7.3.1, unless all of the following conditions are met:
(1) Where dispensers are installed in a corridor, the corridor shall have a minimum width of 6 ft (1830 mm).
(2) The maximum individual dispenser fluid capacity shall be as follows:
(a) 0.32 gal (1.2 L) for dispensers in rooms, corridors, and areas open to corridors
(b) 0.53 gal (2.0 L) for dispensers in suites of rooms
(3) Where aerosol containers are used, the maximum capacity of the aerosol dispenser shall be 18 oz. (0.51 kg) and shall be limited to Level 1 aerosols as defined in NFPA30B, Code for the Manufacture and Storage of Aerosol Products.
(4) Dispensers shall be separated from each other by horizontal spacing of not less than 48 in. (1220 mm).
(5) Not more than an aggregate 10 gal (37.8 L) of alcohol-based hand-rub solution or 1135 oz (32.2 kg) of Level 1 aerosols, or a combination of liquids and Level 1 aerosols not to exceed, in total, the equivalent of 10 gal (37.8 L) or 1135 oz (32.2 kg), shall be in use outside of a storage cabinet in a single smoke compartment, except as otherwise provided in 19.3.2.6(6).
(6) One dispenser complying with 19.3.2.6 (2) or (3) per room and located in that room shall not be included in the aggregated quantity addressed in 19.3.2.6(5).
(7) Storage of quantities greater than 5 gal (18.9 L) in a single smoke compartment shall meet the requirements of NFPA 30, Flammable and Combustible Liquids Code.
(8) Dispensers shall not be installed in the following locations:
(a) Above an ignition source within a 1 in. (25 mm) horizontal distance from each side of the ignition source
(b) To the side of an ignition source within a 1 in. (25 mm) horizontal distance from the ignition source
(c) Beneath an ignition source within a 1 in. (25 mm) vertical distance from the ignition source
(9) Dispensers installed directly over carpeted floors shall be permitted only in sprinklered smoke compartments.
(10) The alcohol-based hand-rub solution shall not exceed 95 percent alcohol content by volume.
(11) Operation of the dispenser shall comply with the following criteria:
(a) The dispenser shall not release its contents except when the dispenser is activated, either manually or automatically by touch-free activation.
(b) Any activation of the dispenser shall occur only when an object is placed within 4 in. (100 mm) of the sensing device.
(c) An object placed within the activation zone and left in place shall not cause more than one activation.
(d) The dispenser shall not dispense more solution than the amount required for hand hygiene consistent with label instructions.
(e) The dispenser shall be designed, constructed, and operated in a manner that ensures that accidental or malicious activation of the dispensing device is minimized.
(f) The dispenser shall be tested in accordance with the manufacturer's care and use instructions each time a new refill is installed.
Tag No.: K0907
Based on record review and interview, the facility failed to ensure that positive pressure gas central piping systems and medical-surgical vacuum systems have a documented maintenance program in accordance with manufacturers recommendations and NFPA 99. Failure to inventory, inspect, and maintain these systems, by a qualified person, could result in fire, explosion, or a lack of system performance as designed. This deficient practice affected all patients, staff and visitors on the date of the survey. The facility is licensed for 11 beds and had a census of 3 on the day of the survey.
Findings include:
During record review on July 6, 2017, from approximately 10:45 AM to 1:00 PM, no documentation of a maintenance program for the positive pressure gas central piping systems and medical-surgical vacuum systems could be located. When asked about the missing documentation, the Maintenance Supervisor stated the facility was unaware of this requirement.
Actual NFPA standard:
NFPA 99
5.1.14.2.1* General. Health care facilities with installed medical gas, vacuum,WAGD, or medical support gas systems, or combinations thereof, shall develop and document periodic maintenance programs for these systems and their subcomponents as appropriate to the equipment installed.
5.1.14.2.2 Maintenance Programs.
5.1.14.2.2.1 Inventories. Inventories of medical gas, vacuum, WAGD, and medical support gas systems shall include at least all source subsystems, control valves, alarms, manufactured assemblies containing patient gases, and outlets.
5.1.14.2.2.2* Inspection Schedules. Scheduled inspections for equipment and procedures shall be established through the risk assessment of the facility and developed with consideration of the original equipment manufacturer recommendations and other recommendations as required by the authority having jurisdiction.
5.1.14.2.2.3 Inspection Procedures. The facility shall be permitted to use any inspection procedure(s) or testing methods established through its own risk assessment.
5.1.14.2.2.4 Maintenance Schedules. Scheduled maintenance for equipment and procedures shall be established through the risk assessment of the facility and developed with consideration of the original equipment manufacturer recommendations and other recommendations as required by the authority having jurisdiction.
5.1.14.2.2.5 Qualifications. Persons maintaining these systems shall be qualified to perform these operations. Appropriate qualification shall be demonstrated by any of the following:
(1) Training and certification through the health care facility by which such persons are employed to work with specific equipment as installed in that facility
(2) Credentialing to the requirements of ASSE 6040, Professional Qualification Standard for Medical Gas Maintenance Personnel
(3) Credentialing to the requirements of ASSE 6030, Professional Qualification Standard for Medical Gas Systems Verifiers
5.1.14.2.3 Inspection and Testing Operations.
5.1.14.2.3.1 General. The elements in 5.1.14.2.2.2 through 5.1.15 shall be inspected or tested as part of the maintenance program as follows:
(1)*Medical air source, as follows:
(a) Room temperature
(b) Shaft seal condition
(c) Filter condition
(d) Presence of hydrocarbons
(e) Room ventilation
(f) Water quality, if so equipped
(g) Intake location
(h) Carbon monoxide monitor calibration
(i) Air purity
(j) Dew point
(2)*Medical vacuum source — exhaust location
(3) WAGD source — exhaust location
(4)*Instrument air source — filter condition
(5)*Manifold sources (including systems complying with 5.1.3.5.10, 5.1.3.5.11, 5.1.3.5.12, and 5.1.3.5.13), as follows:
(a) Ventilation
(b) Enclosure labeling
(6) Bulk cryogenic liquid source inspected in accordance with NFPA 55, Compressed Gases and Cryogenic Fluids Code
(7) Final line regulation for all positive pressure systems — delivery pressure
(8)*Valves — labeling
(9)*Alarms and warning systems—lamp and audio operation
(10) Alarms and warning systems, as follows:
(a) Master alarm signal operation
(b) Area alarm signal operation
(c) Local alarm signal operation
(11)*Station outlets/inlets, as follows:
(a) Flow
(b) Labeling
(c) Latching/delatching
(d) Leaks
5.1.14.2.3.2 Manufactured Assemblies Employing Flexible Connection(s) Between the User Terminal and the Piping System.
(A) Non-stationary booms and articulating assemblies, other than head walls utilizing flexible connectors, shall be tested for leaks, per manufacturer ' s recommendations, every 18 months or at a duration as determined by a risk assessment.
(B) The system pressure to non-stationary booms and articulating arms shall be maintained at operating pressure until each joint has been examined for leakage by effective means of leak
detection that is safe for use with oxygen.
(C) Safe working condition of the flexible assemblies shall be confirmed.
(D) D.I.S.S. connectors internal to the boom and assemblies shall be checked for leakage.
(E) Leaks, if any, shall be repaired (if permitted), or the components replaced (if required), and the equipment retested prior to placing the equipment back into service.
(F) Additional testing of non-stationary booms or articulating arms shall be performed at intervals defined by documented performance data.
5.1.14.3 Medical Gas and Vacuum Systems Information and Warning Signs.
5.1.14.3.1 The gas content of medical gas and vacuum piping systems shall be labeled in accordance with 5.1.11.1.
5.1.14.3.2 Labels for shutoff valves shall be in accordance with 5.1.11.2 and updated when modifications are made changing the areas served.
5.1.14.4 Medical Gas and Vacuum Systems Maintenance and Record Keeping. See B.5.2.
5.1.14.4.1 Permanent records of all tests required by 5.1.12.3.1 through 5.1.12.3.14 shall be maintained in the organization ' s files.
5.1.14.4.2 The supplier of the bulk cryogenic liquid system shall, upon request, provide documentation of vaporizer(s) sizing criteria to the facility.
5.1.14.4.3 An annual review of bulk system capacity shall be conducted to ensure the source system has sufficient capacity.
5.1.14.4.4 Central supply systems for nonflammable medical gases shall conform to the following:
(1) They shall be inspected annually.
(2) They shall be maintained by a qualified representative of the equipment owner.
(3) A record of the annual inspection shall be available for review by the authority having jurisdiction.
5.1.14.4.5 A periodic testing procedure for nonflammable medical gas and vacuum and related alarm systems shall be implemented.
5.1.14.4.6 Whenever modifications are made that breach the pipeline, any necessary installer and verification test specified in 5.1.12 shall be conducted on the downstream portions of
the medical gas piping system.
5.1.14.4.7 Procedures, as specified, shall be established for the following:
(1) Maintenance program for the medical air compressor supply system in accordance with the manufacturer ' s recommendations
(2) Facility testing and calibration procedure that ensures carbon monoxide monitors are calibrated at least annually or more often if recommended by the manufacturer
(3) Maintenance program for both the medical–surgical vacuum piping system and the secondary equipment attached to medical–surgical vacuum station inlets to ensure the continued good performance of the entire medical–surgical vacuum system
(4) Maintenance program for the WAGD system to ensure performance
5.1.14.4.8 Audible and visual alarm indicators shall meet the following requirements:
(1) They shall be periodically tested to determine that they are functioning properly.
(2) Records of the test shall be maintained until the next test is performed.
5.1.14.4.9 Medical–surgical vacuum station inlet terminal performance, as required in 5.1.12.3.10.4, shall be tested as follows:
(1) On a regular preventive maintenance schedule as determined by the facility maintenance staff
(2) Based on flow of free air (Nl/min or SCFM) into a station inlet while simultaneously checking the vacuum level
5.1.15* Category 1 Maintenance. Facilities shall have a routine maintenance program for their piped medical gas and vacuum systems.
5.2 Category 2 Piped Gas and Vacuum Systems.
5.2.1* Applicability. These requirements shall apply to health care facilities that qualify for Category 2 systems as referenced in Chapter 4.
5.2.1.1 Section 5.2 through 5.2.12 shall apply to new health care facilities or facilities making changes that alter the piping. 5.2.1.2 Subsection 5.2.13
5.2.14* Category 2 Maintenance. Facilities shall have a routine maintenance program for their piped medical gas and vacuum systems.
5.3.13.4.2 A periodic testing procedure for Category 3 gas and vacuum systems and related alarm systems shall be implemented.
Tag No.: K0908
Based on record review and interview, the facility failed to ensure that positive pressure gas central piping systems, medical-surgical vacuum systems are inspected and tested annually. Failure to test and inspect these systems could result in fire, explosion, or a lack of system performance as designed. This deficient practice affected all patients, staff and visitors on the date of the survey. The facility is licensed for 11 beds and had a census of 3 on the day of the survey.
Findings include:
During record review on July 6, 2017, from approximately 10:45 AM to 1:00 PM, no documentation for an annual inspection and testing of the positive pressure gas central piping systems and medical-surgical vacuum systems could be located. When asked about the missing documentation, the Maintenance Supervisor stated the facility was unaware of this requirement.
Actual NFPA standard:
NFPA 99
5.1.14.4.4 Central supply systems for nonflammable medical gases shall conform to the following:
(1) They shall be inspected annually.
(2) They shall be maintained by a qualified representative of the equipment owner.
(3) A record of the annual inspection shall be available for review by the authority having jurisdiction.