Bringing transparency to federal inspections
Tag No.: K0052
Based on observation during the afternoon of March 14, 2012: The "Life Safety" electrical panelboard directory indicates the fire alarm control panel (FACP) is powered by circuit #7. However, the adjacent "Critical" electrical panelboard directory indicates the the FACP is powered by circuit #3. The source of power for the FACP must be a dedicated circuit on the "Life Safety" branch of the Essential Electrical System. Therefore, it must be verified the FACP is not powered by the "Critical" panel, and is powered by the "Life Safety Panel."
Tag No.: K0056
Based on observation during the afternoon of March 14, 2012: A fire sprinkler is not installed at the room where the main sprinkler riser pipes and valves are installed which does not comply with NFPA 13. ( A new door was recently installed at this room to provide access for maintenance and repairs to the sprinkler system.) NFPA 13 requires that this room be protected by the fire sprinkler system.