HospitalInspections.org

Bringing transparency to federal inspections

701 THIRD AVENUE SOUTH

CLEAR LAKE, SD 57226

No Description Available

Tag No.: K0012

Based on document record review and observation, the provider failed to meet the minimum construction standards of the 2000 Life Safety Code (LSC). The building construction type required a complete automatic sprinkler system. Findings include:

1. Review of the previous survey record dated 1/28/09 revealed the hospital building was a two story, noncombustible, Type II (111) structure with a partial basement and without a complete automatic sprinkler system. Observation of the building beginning at the time of record review and interview with the director of environmental services during the survey confirmed those findings.

The building meets the FSES. Please mark an "F" in the completion date column to indicate correction of the deficiencies identified in K000.

No Description Available

Tag No.: K0056

Based on document record review and observation, the provider failed to meet the minimum construction standards of the 2000 Life Safety Code (LSC). The building construction type required a complete automatic sprinkler system. Findings include:

1. Review of the previous survey record dated 1/28/09 revealed the hospital building was a two story, noncombustible, Type II (111) structure with a partial basement and without a complete automatic sprinkler system. Observation of the building beginning at the time of record review and interview with the director of environmental services during the survey confirmed those findings.

The building meets the FSES. Please mark an "F" in the completion date column to indicate correction of the deficiencies identified in K000.