Tag No.: K0351
The inspector observed, while accompanied by the CEO/Administrator during the hours of the inspection from 2:00 pm to 4:00 pm on 11/9/2016 that there were the following issues. They were: The fire inspector ' s test valve did not have the correct label. The sign must state ''Inspector's Test Valve'' .
Tag No.: K0900
The inspector observed, while accompanied by the CEO/Administrator during the hours of the inspection from 2:00 pm to 4:00 pm on 11/9/2016 that there were the following issues. They were: The hand wash hot water temperature in the patient rooms appeared to exceed 120 degrees Fahrenheit. The hot water temperature in clinical areas shall be between 105 and 120 degrees Fahrenheit
Tag No.: K0906
The inspector observed, while accompanied by the CEO/Administrator during the hours of the inspection from 2:00 pm to 4:00 pm on 11/9/2016 that there were the following issues. They were: In the outdoor medical gas tank storage area, the medical gas tanks were not adequately secured. They need to be provided with racks, chains, or other fastenings to individually secure all cylinders, whether connected, unconnected, full, or empty, from falling.
Tag No.: K0911
The inspector observed, while accompanied by the CEO/Administrator during the hours of the inspection from 2:00 pm to 4:00 pm on 11/9/2016 that there were the following issues. They were: The electrical room was used for storing carts and equipment. Dedicated electrical rooms may not be used for storage.
The inspector observed, while accompanied by the CEO/Administrator during the hours of the inspection from 2:00 pm to 4:00 pm on 11/9/2016 that there were the following issues. They were: There electrical panel boxes in the corridor that were not locked. They must be locked to prevent unauthorized tampering.
Tag No.: K0912
The inspector observed, while accompanied by the CEO/Administrator during the hours of the inspection from 2:00 pm to 4:00 pm on 11/9/2016 that there were the following issues. They were: The critical care receptacles (red) did not have permanent labels indicating panel and circuit number. All critical care area receptacles shall be identified. The face plate for the receptacle(s) shall have a non-removable label or be engraved indicating the panel and circuit number. Here, non-removable means that it cannot be peeled off with a fingernail.
Tag No.: K0918
The inspector observed, while accompanied by the CEO/Administrator during the hours of the inspection from 2:00 pm to 4:00 pm on 11/9/2016 that there were the following issues. They were: The emergency generator area was missing the required receptacle for use in the maintenance and repair of the generator.
Tag No.: K0923
The inspector observed, while accompanied by the CEO/Administrator during the hours of the inspection from 2:00 pm to 4:00 pm on 11/9/2016 that there were the following issues. They were: The repertory room contained supplies, desks, computers and a supply oxygen tanks. Oxygen is highly combustible. These tanks must be stored in a storage location that is specifically designed to safely store medical gas tanks.