1001 PINE STREET

RENOVO, PA 17764

No Description Available

Tag No.: K0012

Based on observation and interview it was determined the facility failed to properly maintain fire rated construction in one of four smoke compartments in this facility.

Findings include:

Observation on July 5, 2011, at 11:18 AM, revealed the one hour fire-rated suspended ceiling in room 203 had water stains.

Interview with maintenance representative #1 and facility administrator on July 5, 2011, between 11:45 AM and 12:00 PM, confirmed the water stained ceiling tiles.

No Description Available

Tag No.: K0147

Based on observation and interview it was determined the facility failed to properly maintain the installed electrical distribution system in one of four smoke compartments in this facility.

Findings include:

A. Observation on July 5, 2011, between 11:04 AM and 11:15 AM, revealed the following deficiencies:

1. 11:04 AM - Dietary department, main kitchen, an unauthorized surge suppressor power strip was being utilized to provide power to a commercial toaster and blender.

2. 1:05 AM - Dietary department, cafeteria, an unauthorized extension cord was being utilized to supply power to a cash register.

Interview with maintenance representative #1 and facility administrator on July 5, 2011, between 11:45 AM and 12:00 PM, confirmed the unauthorized use of a surge suppressor power strip and an extension cord.

LIFE SAFETY CODE STANDARD

Tag No.: K0012

Based on observation and interview it was determined the facility failed to properly maintain fire rated construction in one of four smoke compartments in this facility.

Findings include:

Observation on July 5, 2011, at 11:18 AM, revealed the one hour fire-rated suspended ceiling in room 203 had water stains.

Interview with maintenance representative #1 and facility administrator on July 5, 2011, between 11:45 AM and 12:00 PM, confirmed the water stained ceiling tiles.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation and interview it was determined the facility failed to properly maintain the installed electrical distribution system in one of four smoke compartments in this facility.

Findings include:

A. Observation on July 5, 2011, between 11:04 AM and 11:15 AM, revealed the following deficiencies:

1. 11:04 AM - Dietary department, main kitchen, an unauthorized surge suppressor power strip was being utilized to provide power to a commercial toaster and blender.

2. 1:05 AM - Dietary department, cafeteria, an unauthorized extension cord was being utilized to supply power to a cash register.

Interview with maintenance representative #1 and facility administrator on July 5, 2011, between 11:45 AM and 12:00 PM, confirmed the unauthorized use of a surge suppressor power strip and an extension cord.