Bringing transparency to federal inspections
Tag No.: K0161
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Ground floor, sterile processing small closet next to environmental closet. The ceiling is not in good condition to maintain the required rating of the ceiling assembly. Reference 2012 NFPA 101 Sections 19.1.6.1, 8.2.1
This deficiency affected 1 of 16 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0161
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The ceiling has penetrations and is not in able to maintain the required rating of the ceiling assembly in the following areas.
a. Ground floor, mechanical room #4, aka old boiler room
b. Ground floor, ceiling tile room, behind the light fixture
c. First floor, imaging #2, 4"x 6" penetration in the wall
Reference 2012 NFPA 101 Sections 19.1.6.1, 8.2.1
This deficiency affected 1 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0211
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Ground floor, medical records exit discharge had a car in the discharge path to the public way.
Reference 2012 NFPA 101 Sections 19.2.1, 7.1.10.1 Aisles, passageways, corridors, exit discharges, exit locations, and accesses are in accordance with Chapter 7, and the means of egress is continuously maintained free of all obstructions to full use in case of emergency.
This deficiency affected 1 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0222
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The emergency department door E 4 hardware sticks. The door was equipped with delayed egress locking, once locking had released the door stuck and did not open with 15 lbs of pressure. Reference 2012 NFPA 101 Sections 19.2.2.2, 7.2.1.6.1 (a) The force shall not be required to exceed 15 lbf (67 N).
2. The emergency department doors, two doors, were equipped with delayed egress locking that would not release with fire alarm activation with smoke detectors. The door did release with delayed egress.
Reference 2012 NFPA 101 Sections 19.2.2.2, 7.2.1.6.1
(1) The door leaves shall unlock in the direction of egress upon actuation of one of the following: (a) Approved, supervised automatic sprinkler system in accordance with section 9.7 (b) Not more than one heat detector of an approved, supervised automatic fire detection system in accordance with section 9.6 (c) Not more than two smoke detectors of an approved, supervised automatic fire detection system in accordance with section 9.6
(2) The door leaves shall unlock in the direction of egress upon loss of power controlling the lock or locking mechanism.
(3) An irreversible process shall release the lock in the direction of egress within 15 seconds, or 30 seconds where approved by the authority having jurisdiction, upon application of a force to the release device required in 7.2.1.5.10 under all of the following conditions: (a) The force shall not be required to exceed 15 lbf (67 N). (b) The force shall not be required to be continuously applied for more than 3 seconds. (c) The initiation of the release process shall activate an audible signal in the vicinity of the door opening. (d) Once the lock has been released by the application of force to the releasing device, relocking shall be by manual means only.
(4) A readily visible, durable sign in letters not less than 1 in. (25mm) high and not less than 1/8" (3.2 mm) in stroke width on a contrasting background that reads as follows shall be located on the door leaf adjacent to the release device in the direction of egress: PUSH UNTIL ALARM SOUNDS
DOOR CAN BE OPENED IN 15 SECONDS
(5) The egress side of doors equipped with delayed-egress locks shall be provided with emergency lighting in accordance with section 7.9
This deficiency affected 2 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0225
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Second west stair C exit door did not latch in it's frame.
Reference 2012 NFPA 101 section 19.2.2.3, 19.2.2.4, 7.2
This deficiency affected 1 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0271
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Third floor exit from the roof to the stairwell, near sleep lab & elevators 4 & 5, had a padlock that was removed.
Reference 2012 NFPA 101 section 19.2.7 Discharge from exits, 7.7 Discharge from exits.
This deficiency affected 1 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0281
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The exit from the hyperbaric suite to the public way did not have emergency lighting installed.
Reference 2012 NFPA 101 section 7.8
This deficiency affected 1 of 1 smoke compartment.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0281
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Penthouse from 5th floor did not have emergency lighting. Reference 2012 NFPA 101 section 7.8
2. First floor from door 1-072, near elevator #4, exit egress did not have emergency lighting at the door.
Reference 2012 NFPA 101 section 19.2.8, 7.8 Reference NFPA 101 7.8.1.3 The minimum illumination for floors and walking surfaces shall be to values of at lease 1 ft-candle (10.8 lux), measured at the floor. Reference NFPA 101 7.8.1.4 Required illumination shall be arranged so that the failure of any single lighting unit does not result in an illumination level of less than 0.2 ft-candle (2.2 lux) in any designated area.
This deficiency affected 2 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0293
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Penthouse from 5th floor did not have exit signage. Reference 2012 NFPA 101 19.2.10.1, 7.10.1.5.1 Access to exits shall be marked by approved, readily visible signs in all cases where the exit or way to reach the exit is not readily apparent to the occupants.
2. Ground floor by door G 018 there was not an exit sign. Reference 2012 NFPA 101 19.2.10.1, 7.10.1.5.1 Access to exits shall be marked by approved, readily visible signs in all cases where the exit or way to reach the exit is not readily apparent to the occupants.
This deficiency affected 2 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0293
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. There were two illuminated exit signs that were not functioning properly in the exit from the hyperbaric suite to the public way.
Reference 2012 NFPA 101 section 7.10
This deficiency affected 1 of 1 smoke compartment.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0321
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The storage room doors in the following areas did not have a closure, nor confirmed as one hour rated. The room was greater than 50 square feet and is used for storage of combustible materials.
a. Fifth floor storage room door, near room 508
b. Fourth floor, room 404
c. First floor lab storage room across from the switch board
Reference 2012 NFPA 101, 19.3.2.1 Hazardous Areas. Any hazardous areas shall be safeguarded by a fire barrier having a 1-hour fire resistance rating or shall be provided with an automatic extinguishing system in accordance with 8.7.1.
Reference 2012 NFPA 101 19.3.2.1.3 The doors shall be self-closing or automatic-closing.
This deficiency affected 3 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0321
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. First floor, sterile corridor/storage, could not confirm all doors have closures. The room was greater than 50 square feet and is used for storage of combustible materials.
Reference 2012 NFPA 101, 19.3.2.1 Hazardous Areas. Any hazardous areas shall be safeguarded by a fire barrier having a 1-hour fire resistance rating or shall be provided with an automatic extinguishing system in accordance with 8.7.1.
Reference 2012 NFPA 101 19.3.2.1.3 The doors shall be self-closing or automatic-closing.
This deficiency affected 1 of 12 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0321
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Ground floor, central supply storage, confirm all doors have closures. The room was greater than 50 square feet and is used for storage of combustible materials.
Reference 2012 NFPA 101, 19.3.2.1 Hazardous Areas. Any hazardous areas shall be safeguarded by a fire barrier having a 1-hour fire resistance rating or shall be provided with an automatic extinguishing system in accordance with 8.7.1. Reference 2012 NFPA 101 19.3.2.1.3 The doors shall be self-closing or automatic-closing.
2. First floor, the operating room sterile core confirm all doors have closures. The room was greater than 50 square feet and is used for storage of combustible materials.
Reference 2012 NFPA 101, 19.3.2.1 Hazardous Areas. Any hazardous areas shall be safeguarded by a fire barrier having a 1-hour fire resistance rating or shall be provided with an automatic extinguishing system in accordance with 8.7.1. Reference 2012 NFPA 101 19.3.2.1.3 The doors shall be self-closing or automatic-closing.
This deficiency affected 2 of 16 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0347
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. There was a smoke detector within 3' of the supply or return in the following areas:
a. Fifth floor, near administration/stairwell
b. Fourth floor, near Dept of Social Services office
c. Second floor west, near room 272
d. Ground floor, by med staff lounge (mini space heater near detector)
Reference 2012 NFPA 101 section 19.3.6.1, 2010 NFPA 72 17.7.4.1 In spaces served by air-handling systems, detectors shall not be located where airflow prevents operation of the detectors. Detectors should not be located in a direct airflow or closer than 36 in. (910 mm) from an air supply diffuser or return air opening.
This deficiency affected 4 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0347
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. There was a smoke detector within 3' of the supply or return in the following areas:
a. Patient changing room
b. Electrical room in the hyperbaric lab area
Reference 2012 NFPA 101 section 19.3.6.1, 2010 NFPA 72 Sect 17.7.4.1 In spaces served by air-handling systems, detectors shall not be located where airflow prevents operation of the detectors. Detectors should not be located in a direct airflow or closer than 36 in. (910 mm)from an air supply diffuser or return air opening.
This deficiency affected 1 of 1 smoke compartment.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0351
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Ground floor, sterile processing small closet next to environmental closet. Sprinkler head within two inches of the wall.
Reference 2012 NFPA 101 section 19.3.5.1, 2010 NFPA 13 8.6.3.3 Sprinklers shall be located a minimum of 4 in. (102 mm) from a wall.
This deficiency affected 1 of 16 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0351
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Penthouse from 5th floor sprinkler head flush against an HVAC supply duct. Reference 2012 NFPA 101 section 19.3.5.1, 9.7, 2011 NFPA 25 section 5.2.1.1.3 sprinkler shall be installed in the correct orientation.
2. Ground floor beside quality insurance office at ladies bathroom had a sprinkler head within 1-3/4" from the wall. Reference 2012 NFPA 101 section 19.3.5.1, 2010 NFPA 13 8.6.3.3 Sprinklers shall be located a minimum of 4 in. (102 mm) from a wall.
This deficiency affected 2 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0351
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. There were two of four sprinkler systems that were not tied to the main fire alarm panel. The MRI and IT room sprinkler systems had annunciator panels in the mechanical room only and not in an area likely to heard 24/7. Confirm dry system for the canopy is on the main fire alarm system. Reference 2012 NFPA 101 section 19.3.5.1, 9.7, 9.7.2
2. First floor accelerated claims office had a sprinkler head drop that was several inches lower than the ceiling.
Reference 2012 NFPA 101 section 19.3.5.1, 9.7, 2011 NFPA 25 section 5.2.1.1.3 sprinkler shall be installed in the correct orientation.
This deficiency affected 12 of 12 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0352
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The supervisory signal for the electronically supervised tamper alarm on the sprinkler control valve could be silenced permanently at the Fire Alarm Control Panel (FACP) when the valve was in the closed position in the sprinkler riser room. Supervisory signals shall not be silenced permanently except by reopening/restoration of the valve to the normal operating position.
Reference 2012 NFPA 101 Section 19.3.5.1, 9.7.2.1 Where supervised automatic sprinkler systems are required by another section of this code, supervisory attachments shall be installed and monitored for integrity in accordance with NFPA 72, National Fire Alarm and Signaling Code, AND a distinctive supervisory signal shall be provided to indicate a condition that would impair the satisfactory operation of the sprinkler system. Supervisory signals shall sound and shall be displayed at a location within the protected building that is constantly attended by qualified personnel.
This deficiency affected all smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0352
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The supervisory signal for the electronically supervised tamper alarm on the sprinkler control valve could be silenced permanently at the Fire Alarm Control Panel (FACP) when the valve was in the closed position in the sprinkler riser room. Supervisory signals shall not be silenced permanently except by reopening/restoration of the valve to the normal operating position.
Reference 2012 NFPA 101 Section 19.3.5.1, 9.7.2.1 Where supervised automatic sprinkler systems are required by another section of this code, supervisory attachments shall be installed and monitored for integrity in accordance with NFPA 72, National Fire Alarm and Signaling Code, AND a distinctive supervisory signal shall be provided to indicate a condition that would impair the satisfactory operation of the sprinkler system. Supervisory signals shall sound and shall be displayed at a location within the protected building that is constantly attended by qualified personnel.
This deficiency affected 12 of 12 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0363
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Fourth floor equipment room door swings into the means of egress and in the fully open position projects more than 7 inches into the required width of an aisle without a closure.
Reference 2012 NFPA 101 section 7.2.1.4.3.1 During its swing, any door leaf in a means of egress shall leave not less than one-half of the required width of an aisle, or corridor, a passageway, or a landing unobstructed and shall project not more than 7 in (180 mm) into the required width of an aisle, a corridor, a passageway, or a landing, when fully open.
2. Fifth floor door, next to the CFO office, opened into the means of egress had the closure disconnected.
Reference 2012 NFPA 101 section 7.2.1.4.3.1 During its swing, any door leaf in a means of egress shall leave not less than one-half of the required width of an aisle, or corridor, a passageway, or a landing unobstructed and shall project not more than 7 in (180 mm) into the required width of an aisle, a corridor, a passageway, or a landing, when fully open.
3. Second floor, door between rooms 205 & 207 storage room did not close and latch in it's frame.
Reference 2012 NFPA 101 section 19.3.6.3.4 Door shall be provided with a means for keeping the door closed.
4. First floor endoscopy workstation by day surgery had a kick down on the corridor door.
Reference 2012 NFPA 101 section 19.3.6.3.10 There is no impediment to the closing of the doors.
This deficiency affected 4 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0372
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Penetrations were not sealed in order to maintain the required fire resistance rating of the smoke barrier wall. UL approved fire stop application had not been supplied to the following areas.
a. Third floor, pharmacy back corridor separation between the old and new building
b. Second floor, IT room, pass the electrical room, 4" conduits
c. Second floor west, case management, above cross corridor doors
d. Second floor west, cardiac recovery, above doors, data cable bundle
e. Ground floor, above doors G 060 & G 057
Reference 2012 NFPA 101 19.3.7.3 Any required smoke barrier shall be constructed in accordance with section 8.5 and shall have a minimum 1/2 hour fire resistance rating.
This deficiency affected 10 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0372
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Second floor, Progressive Care Unit (PCU), above the doors, there were penetrations in the smoke barrier that are not sealed in order to maintain the required fire resistance rating of the wall.
Reference 2012 NFPA 101 19.3.7.3 Any required smoke barrier shall be constructed in accordance with section 8.5 and shall have a minimum 1/2 hour fire resistance rating.
This deficiency affected 1 of 16 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0511
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Fifth floor room 527 receptacle within 6' of a water source and not GFCI protected. Reference 2012 NFPA 101, 2011 NFPA 70 section 210.8 (7) GFCI protected circuits shall be located in areas other than kitchens where receptacles are installed within 1.8 m (6 ft) of the outside edge of the sink.
2. Fourth floor staff kitchen behind refrigerator receptacle within 6' of a water source and not GFCI protected. Reference 2012 NFPA 101, 2011 NFPA 70 section 210.8 (7) GFCI protected circuits shall be located in areas other than kitchens where receptacles are installed within 1.8 m (6 ft) of the outside edge of the sink.
3. Fifth floor copy room across from elevator #2 had a painted receptacle. Reference 2012 NFPA 101, 2011 NFPA 70 110.12 (b) Mechanical execution of work
4. Fourth floor near room 411 had a painted receptacle. Same receptacle had no tension when tested. Reference 2012 NFPA 101, 2011 NFPA 70 110.12 (b) Mechanical execution of work
5. Fifth floor room 527 E had a chipped receptacle. Reference 2012 NFPA 101, 2011 NFPA 70 110.12 (b) Mechanical execution of work
6. Penthouse panel PNLQHPA had four breakers removed without blank covers. Reference 2012 NFPA 101 Sections 19.5.1.1, 9.1.2 2011 NFPA 70 NEC Section 408.7
7. Second floor elevator lobby near utility room had a loose receptacle. Reference 2012 NFPA 101, 2011 NFPA 70 110.12 (b) Mechanical execution of work
8. Second floor west equipment room/data closet by nurses station, had a drop cord going through the ceiling. Reference 2012 NFPA 101, 2011 NFPA 70 110.12 (b) Mechanical execution of work
9. Second floor west cardiac recovery kitchen ice maker, exposed/frayed wiring/cord. Reference 2012 NFPA 101, 2011 NFPA 70 110.12 (b) Mechanical execution of work
10. Second floor west cardiac recovery kitchen receptacle within 6' of a water source and not GFCI protected. Reference 2012 NFPA 101, 2011 NFPA 70 section 210.8 (7) GFCI protected circuits shall be located in areas other than kitchens where receptacles are installed within 1.8 m (6 ft) of the outside edge of the sink.
11. Second floor room 211 receptacle within 6' of a water source and not GFCI protected. Reference 2012 NFPA 101, 2011 NFPA 70 section 210.8 (7) GFCI protected circuits shall be located in areas other than kitchens where receptacles are installed within 1.8 m (6 ft) of the outside edge of the sink.
12. First floor radiology staff locker room north wall had a chipped receptacle. Reference 2012 NFPA 101, 2011 NFPA 70 110.12 (b) Mechanical execution of work
13. First floor radiology north bay had 3 chipped receptacles. Reference 2012 NFPA 101, 2011 NFPA 70 110.12 (b) Mechanical execution of work
14. First floor speech pathology workstation near sink had a chipped receptacle. Reference 2012 NFPA 101, 2011 NFPA 70 110.12 (b) Mechanical execution of work
15. First floor Women's Pavilion physicians lounge on call bedroom #2 light switch loose and not functioning properly. Reference 2012 NFPA 101, NFPA 70, 2011 NEC 110.12 (b) Mechanical execution of work.
16. First floor Women's Pavilion server room had a wire mold to equipment hanging. Reference 2012 NFPA 101, 2011 NFPA 70 110.12 (b) Mechanical execution of work
This deficiency affected 15 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0511
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The clean utility light switch was loose and not functioning properly. Reference 2012 NFPA 101, NFPA 70, 2011 NEC 110.12 (b) Mechanical execution of work
2. The ground fault circuit interrupter circuit (GFCI) was chipped and the box housing loose from the wall in the following rooms: 1,3,6 and 7. Reference 2012 NFPA 101, NFPA 70
This deficiency affected 1 of 1 smoke compartment.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0511
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. First floor, short stay, 14 rooms had a normal and critial branch circuits within six foot of a water source that was not GFCI protected.
Reference 2012 NFPA 19.5.1.1, 9.1.1, 9.1.2, NFPA 70, National Electric Code
2. First floor, EVS floor care room had a receptacle within six foot of a water source that was not GFCI protected.
Reference 2012 NFPA 19.5.1.1, 9.1.1, 9.1.2, NFPA 70, National Electric Code
3. Third floor, storage room receptacle did not have power when tested.
Reference 2012 NFPA 19.5.1.1, 9.1.1, 9.1.2, NFPA 70, National Electric Code
4. Second floor, receptacle between rooms 214 and 215 identified as CRL-2A-16 show open neutral when tested.
Reference 2012 NFPA 19.5.1.1, 9.1.1, 9.1.2, NFPA 70, National Electric Code
This deficiency affected 4 of 12 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0521
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The smoke dampers located at the employee entrance and at the birth center elevator did not close with fire alarm activation nor smoke detector activation. Reference 2012 NFPA 101, 2010 NFPA 90A: 6.4.3.1
This deficiency affected 2 of 12 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0521
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Fifth floor rooms 526 E and 527 E bathroom exhausts was not functioning. Reference 2012 NFPA 101 19.7.7, 4.6.12 , 2011 NFPA 70 National Electric Code
2. First floor above the bronchscopy room near the switchboard the smoke damper did not function. Reference 2012 NFPA 101, 19.5.2.1, 9.2, 2012 NFPA 90A section 5.4.8.1
3. Ground floor, old ceiling tile room, emergency air handler shut down switch to AHU#3 did not shut down the unit. Reference 2012 NFPA 101, 19.5.2.1, 9.2, 2012 NFPA 90A section 6.4.3
This deficiency affected 4 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0914
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Receptacle annual testing was not available at the time of the survey.
Reference 2012 NFPA 99 section 6.3.4.1 Receptacles shall be test at intervals not exceeding 12 months.
2. First floor Women's Pavilion near door #6 had a GFCI receptacle when tripped the electrical panel NL1A-70 was not properly labeled so to reset the GFCI receptacle. Label panel as to circuits served. NFPA 101: 19.5.1
NFPA 99: 6.3.3.2
3. First floor Women's Pavilion electrical panel NCR1A-1 circuit #1 and #9 were not functioning properly. When #1 was tripped #9 went out as well and vise versa, when #9 was tripped #1 went out as well.
This deficiency affected all smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0914
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Receptacle annual testing was not available at the time of the survey.
Reference 2012 NFPA 99 section 6.3.4.1 Receptacles shall be test at intervals not exceeding 12 months.
This deficiency affected 12 of 12 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0916
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The remote generator annunciator located at the emergency department did not provide a signal for loss of battery charger AC failure when checked. Generator #1 and #2. Reference 2012 NFPA 99 section 6.4.1.1.16.2 (Table item O)
2. The remote generator annunciator located at the emergency department did not provide a signal for EPS supplying load when checked. Generator #3 for the women's center. Reference 2012 NFPA 99 section 6.4.1.1.16.2 (Table item J)
This deficiency affected all smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0916
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The remote generator annunciator located at the emergency department did not provide a signal for loss of battery charger AC failure when checked. Generator #2. Reference 2012 NFPA 99 section 6.4.1.1.16.2 (Table item O)
This deficiency affected 12 of 12 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0918
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The transfer switch to Generator #3 did not transfer from normal to emergency connected load within 10 sec. Transfer took approximately 14 seconds.
Reference 2012 NFPA 101 Sections 19.2.9.1 Emergency lighting shall be provided in accordance with section 7.9
Reference 2012 NFPA 101 Section 7.9.1.3 Where maintenance of illumination depends on changing from one energy source to another, a delay of not more than 10 seconds shall be permitted.
2. There was not an emergency light located in the transfer switch room for Generator #3.
Reference 2012 NFPA 101, 2010 NFPA 110 section 7.3.1 The level 1 or level 2 EPS equipment location (s) shall be provided with battery-powered emergency lighting.
3. The generator fuel test for Generator #1, #2, and #3 from 2019 showed fuel test had failed in quality.
Reference 2012 NFPA 101, 2010 NFPA 110 section 8.3.8 A fuel quality test shall be performed at least annually using test approved by ASTM standards.
This deficiency affected all smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0923
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Second floor across from ICU #11, Empty E-sized oxygen storage was within five foot of combustibles.
Reference 2012 NFPA 99 Section 11.3.2.3 Oxidizing gases such as oxygen and nitrous oxide shall be separated from combustibles or materials by one of the following:
(1) Minimum distance of 6.1 m (20 ft)
(2) Minimum distance of 1.5 m (5 ft) if the entire storage location is protected by an automatic sprinkler system designed in accordance with NFPA 13.3
(3) Enclosed cabinet of noncombustible construction having a minimum fire protection rating of 1/2 hour.
This deficiency affected 1 of 16 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0923
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Zone valves located in the intervening hallway were not labeled. The label was located on the removable box cover but not on the valve itself. Reference 2012 NFPA 99 Section 5.1.4.8.8 Zone valves shall be labeled in accordance with 5.1.11.2
2. Zone valve, to medical air, located in the intervening hallway was open but there was no pressure on the analog gauge.
Reference 2012 NFPA 99 Section 14.3.4.1.1 The hyperbaric safety director shall ensure that all valves, regulators, meters, and similar equipment used in the hyperbaric chamber are compensated for use under hyperbaric conditions and tested as part of the routine maintenance program of the facility.
This deficiency affected 1 of 1 smoke compartment.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0923
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. Fifth floor, near room 525 E, zone valves were not labeled. The label was located on the removable box cover but not on the valve itself. Reference 2012 NFPA 99 Section 5.1.4.8.8 Zone valves shall be labeled in accordance with 5.1.11.2
2. Second floor, near room 225, zone valves were not labeled. The label was located on the removable box cover but not on the valve itself. Reference 2012 NFPA 99 Section 5.1.4.8.8 Zone valves shall be labeled in accordance with 5.1.11.2
3. First floor med gas storage room had H size oxygen tanks gang chained together. Reference 2012 NFPA 19.3.2.4, 99 11.6.2.3 (11) Freestanding cylinders shall be properly chained or supported in a proper cylinder stand or cart.
This deficiency affected 3 of 26 smoke compartments.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.
Tag No.: K0924
Based on observations, staff interview, and/or documentation on February 4, 2020 at approximately 10 AM onward the following deficiencies were noted: The standard is non-compliant, specific findings include:
1. The hyperbaric chamber blow off on the roof was not properly labeled.
Reference 2012 NFPA 99 14.2.9.2.5 The point of exhaust shall be identified as an oxygen exhaust by a sign prohibiting smoking or open flame.
2. The hyperbaric chamber blow off on the roof did not have a screen/cover.
Reference 2012 NFPA 99 14.2.9.2.4 The point of exhaust shall be protected by the provision of a minimum of 0.3 cm (0.12 in.) mesh screen and situated to prevent the intrusion of rain, snow, or airborne debris.
This deficiency affected 1 of 1 smoke compartment.
Failure to comply with minimum standards as referenced increases the risk of death or injury due to smoke and or fire.