602 SOUTHWEST 38TH STREET

LAWTON, OK 73505

No Description Available

Tag No.: K0011

Based on observation and staff interview it was determined the facility failed to ensure the two hour fire resistance rated construction of the common wall with a nonconforming building was free of any penetrations. Findings:

On 11/04/15 at 9:45 a.m., the 2 hour fire barrier wall seperating the health occupancy from the business occupancy was obseved to have 7 penetrations. It was also observed that a white material was used to seal the gaps in the 2 hour fire wall barrier.

At 9:47 a.m., the supervisor of maintenance was interviewed. He acknowledged the penetrations in the fire wall.

No Description Available

Tag No.: K0062

Based on observation the facility failed to maintain their automatic sprinkler systems in reliable operating condition. FIndings:

On 10/04/15 at 11:55 a.m., a sidewall sprinkler head located in the lab room was observed to have paint on it.

At 11:58 a.m., the supervisor of maintanence acknowledged the paint on the sprinkler head.

No Description Available

Tag No.: K0147

Based on observation it was determined the facility failed to ensure no extension cords were being utilized within the facility. Findings:

On 11/04/15 at 11:43 a.m., an approximate 15 feet extension cord was observed in office A153. A power tap was plugged into the 3 hub extension cord.

At 11:43 a.m., the maintanence supervisor acknowledged the extension cord.

LIFE SAFETY CODE STANDARD

Tag No.: K0011

Based on observation and staff interview it was determined the facility failed to ensure the two hour fire resistance rated construction of the common wall with a nonconforming building was free of any penetrations. Findings:

On 11/04/15 at 9:45 a.m., the 2 hour fire barrier wall seperating the health occupancy from the business occupancy was obseved to have 7 penetrations. It was also observed that a white material was used to seal the gaps in the 2 hour fire wall barrier.

At 9:47 a.m., the supervisor of maintenance was interviewed. He acknowledged the penetrations in the fire wall.

LIFE SAFETY CODE STANDARD

Tag No.: K0062

Based on observation the facility failed to maintain their automatic sprinkler systems in reliable operating condition. FIndings:

On 10/04/15 at 11:55 a.m., a sidewall sprinkler head located in the lab room was observed to have paint on it.

At 11:58 a.m., the supervisor of maintanence acknowledged the paint on the sprinkler head.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation it was determined the facility failed to ensure no extension cords were being utilized within the facility. Findings:

On 11/04/15 at 11:43 a.m., an approximate 15 feet extension cord was observed in office A153. A power tap was plugged into the 3 hub extension cord.

At 11:43 a.m., the maintanence supervisor acknowledged the extension cord.