Tag No.: K0011
Based on observation and staff interview it was determined the facility failed to ensure the two hour fire resistance rated construction of the common wall with a nonconforming building was free of any penetrations. Findings:
On 11/04/15 at 9:45 a.m., the 2 hour fire barrier wall seperating the health occupancy from the business occupancy was obseved to have 7 penetrations. It was also observed that a white material was used to seal the gaps in the 2 hour fire wall barrier.
At 9:47 a.m., the supervisor of maintenance was interviewed. He acknowledged the penetrations in the fire wall.
Tag No.: K0062
Based on observation the facility failed to maintain their automatic sprinkler systems in reliable operating condition. FIndings:
On 10/04/15 at 11:55 a.m., a sidewall sprinkler head located in the lab room was observed to have paint on it.
At 11:58 a.m., the supervisor of maintanence acknowledged the paint on the sprinkler head.
Tag No.: K0147
Based on observation it was determined the facility failed to ensure no extension cords were being utilized within the facility. Findings:
On 11/04/15 at 11:43 a.m., an approximate 15 feet extension cord was observed in office A153. A power tap was plugged into the 3 hub extension cord.
At 11:43 a.m., the maintanence supervisor acknowledged the extension cord.
Tag No.: K0011
Based on observation and staff interview it was determined the facility failed to ensure the two hour fire resistance rated construction of the common wall with a nonconforming building was free of any penetrations. Findings:
On 11/04/15 at 9:45 a.m., the 2 hour fire barrier wall seperating the health occupancy from the business occupancy was obseved to have 7 penetrations. It was also observed that a white material was used to seal the gaps in the 2 hour fire wall barrier.
At 9:47 a.m., the supervisor of maintenance was interviewed. He acknowledged the penetrations in the fire wall.
Tag No.: K0062
Based on observation the facility failed to maintain their automatic sprinkler systems in reliable operating condition. FIndings:
On 10/04/15 at 11:55 a.m., a sidewall sprinkler head located in the lab room was observed to have paint on it.
At 11:58 a.m., the supervisor of maintanence acknowledged the paint on the sprinkler head.
Tag No.: K0147
Based on observation it was determined the facility failed to ensure no extension cords were being utilized within the facility. Findings:
On 11/04/15 at 11:43 a.m., an approximate 15 feet extension cord was observed in office A153. A power tap was plugged into the 3 hub extension cord.
At 11:43 a.m., the maintanence supervisor acknowledged the extension cord.