HospitalInspections.org

Bringing transparency to federal inspections

695 N KELLOGG ST

GALESBURG, IL 61401

No Description Available

Tag No.: K0018

Based on random observation during the survey walk-through, not all doors in exit access corridors are in compliance with 19.3.6.3. These deficiencies could affect any patients, staff, or visitors in the building by allowing smoke or fire to enter the egress corridor.

Findings include:

A. On the afternoon of June 24, 2014, while the surveyor was accompanied by the provider's Chief Operating Officer and a Maintenance Technician, the door to the Fourth Floor C Wing Locker Room immediately north of Exit Stair D was observed to not be positive latching as required by 19.3.6.3.2.

NEW 10/01/2014: The required positive latching hardware for the Men's Locker Room door is not yet installed and this was confirmed during walk-through.

B. On the afternoon of June 24, 2014, while the surveyor was accompanied by the provider's Chief Operating Officer and a Maintenance Technician, the hold-open feature at the automatic door operator at the north pair of doors to the Fifth Floor AB Wing Prep/Recovery Unit was observed to not release upon activation of the building fire alarm as required by 19.3.6.3.2.

NEW 10/01/2014: Based from fire alarm testing on the morning of 10/01/14, while accompanied by the Director of the Facility and the Chief Quality Officer, the auto-open function at the north pair of doors to the Fifth Floor AB/Recovery Unit was observed to continue to operate and did not disable from fire alarm activation.

No Description Available

Tag No.: K0034

Based on random observation during the survey walk-through, not all stair shafts used as exits are constructed in accordance with 7.2. These deficiencies could affect any patients, staff, or visitors in the building by preventing them from evacuating the building under fire conditions.

Findings include:

A. On the mooring of June 24, 2014, while the surveyor was accompanied by the provider's Chief Operating Officer and a Maintenance Technician, the spaces between guard rail elements at C Wing Exit Stair E were observed to be far enough apart that a 4" sphere could pass through them as prohibited by 7.2.2.4.6(3). Throughout the course of the survey, this condition was also observed to exist at:
1. AB Wing Exit Stair A.

2. AB Wing Exit Stair B.

3. AB Wing Exit Stair C.

4. C Wing Exit Stair D.

B. On the mooring of June 24, 2014, while the surveyor was accompanied by the provider's Chief Operating Officer and a Maintenance Technician, the guard rails at all Exit Stairs cited in Item A. above were also observed to be less than 42" high as required by 7.2.2.4.6(2).

No Description Available

Tag No.: K0044

Based on random observation during the survey walk-through, not all designated or required fire barriers are constructed or maintained as fire resistive assemblies. These deficiencies could affect any patients, staff, or visitors in the building by allowing smoke or fire to pass between fire compartments.

Findings include:

A. On the afternoon of June 24, 2014,while the surveyor was accompanied by the provider's Chief Operating Officer and a Maintenance Technician, the automatic door operators at the Second Floor pair of doors in the designated 2 hour fire barrier between the AB Wing and the ER/ICU Wing were observed to continue to operate after the activation of the building fire alarm system, as prohibited by 8.2.3.2.3.1(1).

Update 10/01/2014: At the 2nd Floor the auto -open function on the pair of doors in the designated 2 hour fire barrier between the AB Wing and the ER/ICU Wing were observed and did not disable from fire alarm activation.

No Description Available

Tag No.: K0067

Based on random observation during the survey walk-through, not all portions of the facility's air conditioning and ventilating systems are installed in accordance with NFPA 90A. These deficiencies could affect any patients, staff, or visitors in the building by permitting smoke or fire to pass between building stories.

Findings include:

A. On the morning of June 25, 2014,while the surveyor was accompanied by the provider's Chief Operating Officer and a Maintenance Technician, access panels at ventilation shafts which connect 4 or more building stories were observed to not carry a minimum 1-1/2 hour fire rating as required by 8.2.3.2.3.1(1) and NFPA 90A 1999 3-3.4.1. Locations observed include:

1. AB Wing Second Floor Mechaincal Room 4207, in north side of ventilation shaft directly north of Elevators.

2. C Wing Second Floor Mechanical Room 117, in ventilation shaft at north side of room.

NEW 10/01/14: The work had not been completed on the date of the survey walk-through and the completion date noted on the PoC is not met.

No Description Available

Tag No.: K0106

Based on random observation during the survey walk through the surveyor found that the generator installation did not meet all of the requirements of NFPA-110. This could affect all occupants of the building if the generator does not operate properly during a power outage.

Findings include:

A. The surveyor observed on the afternoon of 6/24/14 that the generators were not equipped with battery heaters as required by NFPA-110, Section 3-3.1.

NEW 10/01/14: The work had not been completed on the date of the survey walk-through and the completion date noted on the PoC is not met.

No Description Available

Tag No.: K0130

Based on random observation during the survey walk-through, document review, and staff interview, the facility is not in compliance with a series of Life Safety and other code requirements that are not documented under other K-Tags.

Findings include:

A. Due to the number, variety, and severity of the life safety deficiencies observed during the survey walk-through, the provider shall institute appropriate interim life safety measures until all cited deficiencies are corrected. The provider shall include, as an attachment to its Plan of Correction (PoC) and referenced therein, a detailed narrative and proposed schedule for all such measures. The narrative shall describe all measures to be implemented, as well as the frequency with which they are to be conducted, and shall indicate the manner in which the measures are to be documented. The narrative shall also include comments related to changes in the interim life safety measures to remain in place as work toward the completion of its PoC progresses.

No Description Available

Tag No.: K0145

Based on random observation during the survey walk through the surveyor found that the emergency electrical installation did not meet all of the requirements of NFPA-70. This could affect all occupants of the building if the emergency power system does not operate properly upon the loss of normal power.

Findings include:

A. The building was equipped with enough transfer switches for each branch of emergency power, but several of the panels served from the branch transfer switches were serving mixed loads and some of the transfer switches were serving panels from more than one branch as shown by some of the following examples:

1. The surveyor observed on the morning of 6/25/14 that critical panel 3CL1 on the 3rd floor, and panel BCL1 in the basement served elevator cab lighting which is required by Section 517-32 of NFPA-70 to be served from the life safety branch of emergency power.

2. The surveyor observed on the afternoon of 6/24/14 that panel EMPP in the elevator equipment room served a mixture of life safety, critical and equipment loads that are required by the 1999 edition of NFPA-70, Sections 517-30 through 517-35 to be separated into three separate branches.

3. The hospital staff was unable to locate life safety panels serving the loads required by NFPA-70, Section 517-32. They were not able to verify from the one-line diagram that there was a separate life safety transfer switch serving only life safety loads.

No Description Available

Tag No.: K0147

Based on random observation during the survey walk through the surveyor found that the electrical system installation did not meet all of the requirements of NFPA-70.

Findings include:

A. On the afternoon of 6/24/14 the surveyor observed that the cab lighting for the all elevators was not served from the life safety panel as required by NFPA-70, Section 517-32, and there was not a disconnect switch for cab lighting and controls within the elevator equipment room as required by NFPA-70, Section 620-22. This could affect any occupant of the building using the elevator during a power outage.

B. On the morning of 6/25/14, the surveyor observed that the C-section room was not equipped with normal power receptacles to meet the requirements of NFPA-70, Section 517-18, and 517-19.

C. Panel identification and panel schedules are not accurate or have not been updated to meet the requirements of NFPA-70, Section 110-22, and Section 384-13.

D. On the morning of 6/25/14, the surveyor observed that the critical outlets in the C-section room and the Angio room were not labeled and identified in accordance with NFPA-70, Section 517-19.

No Description Available

Tag No.: K0160

Based on random observation during the survey walk through the surveyor found that the elevators did not meet all of the requirements of ANSI/ASME A17.3. This could affect any occupants of the facility using the elevator if proper safety equipment is not installed on each elevator.

Findings include:

A. The surveyor observed on the afternoon of 6/24/14 that the elevator machine room in the 1961 portion of the building did not have a heat detector within 2' of each sprinkler head tied to a shunt trip as required by NFPA-72, Section 3-9.4, and ASME A17.1, Section 102.2(c)(3).

B. The elevators machine rooms were not equipped with smoke detectors to initiate elevator recall in accordance with ANSI A17.1/A17.3.