Tag No.: K0130

Receptacle Testing in Patient Care Areas - NFPA 99, 2002, 4.3.3.2.1, 4.3.2.2, 4.3.3.2.3 & 4.3.3.2.4:

4.3.3.2.1 The physical integrity of each receptacle shall be confirmed by visual inspection.

4.3.3.2.2 The continuity of the grounding circuit in each electrical receptacle shall be verified.

4.3.3.2.3 Correct polarity of the hot and neutral connections in each electrical receptacle shall be confirmed.

4.3.3.2.4 The retention force of the grounding blade of each electrical receptacle (except for locking-type receptacles) shall be not less than 115g (4 oz).

NFPA 99, 2002, 4.3.4.1 states that testing shall be performed after initial installation, replacement or servicing of a device, and that additional testing shall be performed at intervals defined by documented performance data. Since data is not typically available from the manufacturer, the facility may document the failure rates of the receptacles and provide a testing schedule that will safeguard their patients. This shall be done by the Safety Committee, approved by the Governing Board, and written into the safety policies and procedures. Title 25, Texas Administrative Code, Chapter 135 ASC Licensing Rules. Until this assessment has been done, receptacle testing shall be performed in all general care areas every 12 months and in critical care areas every 6 months. (NFPA 99, 1984).

Based on observation the facility failed to provide documentation for receptacle testing per NFPA 99: 4.3.4.1 in patient care areas.

No Description Available

Tag No.: K0145

Critical care emergency system receptacles shall be identified and shall also indicate the panelboard and circuit number supplying them. NFPA 70: 517-19

This STANDARD is not being met, as evidenced by: Based on observation during the Survey on the afternoon of 03/07/2013, with the Plant Services Manager and the Safety Officer, numerous critical care area emergency system electrical receptacles did not have non-removable labels identifying the electrical panelboard and circuit number supplying them.

LIFE SAFETY CODE STANDARD

Tag No.: K0130

Receptacle Testing in Patient Care Areas - NFPA 99, 2002, 4.3.3.2.1, 4.3.2.2, 4.3.3.2.3 & 4.3.3.2.4:

4.3.3.2.1 The physical integrity of each receptacle shall be confirmed by visual inspection.

4.3.3.2.2 The continuity of the grounding circuit in each electrical receptacle shall be verified.

4.3.3.2.3 Correct polarity of the hot and neutral connections in each electrical receptacle shall be confirmed.

4.3.3.2.4 The retention force of the grounding blade of each electrical receptacle (except for locking-type receptacles) shall be not less than 115g (4 oz).

NFPA 99, 2002, 4.3.4.1 states that testing shall be performed after initial installation, replacement or servicing of a device, and that additional testing shall be performed at intervals defined by documented performance data. Since data is not typically available from the manufacturer, the facility may document the failure rates of the receptacles and provide a testing schedule that will safeguard their patients. This shall be done by the Safety Committee, approved by the Governing Board, and written into the safety policies and procedures. Title 25, Texas Administrative Code, Chapter 135 ASC Licensing Rules. Until this assessment has been done, receptacle testing shall be performed in all general care areas every 12 months and in critical care areas every 6 months. (NFPA 99, 1984).

Based on observation the facility failed to provide documentation for receptacle testing per NFPA 99: 4.3.4.1 in patient care areas.

LIFE SAFETY CODE STANDARD

Tag No.: K0145

Critical care emergency system receptacles shall be identified and shall also indicate the panelboard and circuit number supplying them. NFPA 70: 517-19

This STANDARD is not being met, as evidenced by: Based on observation during the Survey on the afternoon of 03/07/2013, with the Plant Services Manager and the Safety Officer, numerous critical care area emergency system electrical receptacles did not have non-removable labels identifying the electrical panelboard and circuit number supplying them.