Tag No.: K0050
Based on record review and interview, the facility failed to conduct the required number of fire drills.
Findings include:
At 10:30 a.m., on 11-10-11, record review revealed that only one (1) fire drill was conducted on the 11-7 shift in the past twelve months and one (1) drill on the 3-11 shift. Interview with the maintenance person revealed that conducting fire drills was assigned to other staff and not available during the Life Safety Code survey.
Tag No.: K0069
Based on record review and interview, the facility failed to inspect and maintain the kitchen hood extinguishing system as required.
Findings include:
At 11:00 a.m., on 11-10-11, it was observed that the last recorded kitchen hood extinguishing system inspection was conducted in May of 2009.
Actual NFPA standard: Requires inspection and servicing at least every six months by properly trained and qualified persons. 1998 NFPA 17, 9-3
Tag No.: K0050
Based on record review and interview, the facility failed to conduct the required number of fire drills.
Findings include:
At 10:30 a.m., on 11-10-11, record review revealed that only one (1) fire drill was conducted on the 11-7 shift in the past twelve months and one (1) drill on the 3-11 shift. Interview with the maintenance person revealed that conducting fire drills was assigned to other staff and not available during the Life Safety Code survey.
Tag No.: K0069
Based on record review and interview, the facility failed to inspect and maintain the kitchen hood extinguishing system as required.
Findings include:
At 11:00 a.m., on 11-10-11, it was observed that the last recorded kitchen hood extinguishing system inspection was conducted in May of 2009.
Actual NFPA standard: Requires inspection and servicing at least every six months by properly trained and qualified persons. 1998 NFPA 17, 9-3