Tag No.: K0025
Based on observation and interview with staff, the facility failed to constructed and provide smoke barriers that are at least a one half hour fire resistance rating in accordance with 8.3. Findings,
The smoke barrier separating the new wing from existing sleeping rooms had multiple voids and penetrations that were not sealed with material capable of maintaining the fire resistance rating of the smoke barrier.
Tag No.: K0052
Based on observation and interview with staff, the facility failed to provide a fire alarm system required for life safety that is installed, tested, and maintained in accordance with NFPA 70 National Electrical Code and NFPA 72. Findings,
Magnetic locks and combination fire and smoke dampers are not listed on the annual fire alarm inspection form. All equipment tied into the fire alarm system is required to be tested annually and shown on the inspection report form.
Tag No.: K0056
Based on observation and interview with staff, the facility failed to provide automatic sprinkler coverage that is installed in accordance with NFPA 13. Findings,
The front porch is constructed with combustible material and is not provided with fire suppression coverage.
Tag No.: K0025
Based on observation and interview with staff, the facility failed to constructed and provide smoke barriers that are at least a one half hour fire resistance rating in accordance with 8.3. Findings,
The smoke barrier separating the new wing from existing sleeping rooms had multiple voids and penetrations that were not sealed with material capable of maintaining the fire resistance rating of the smoke barrier.
Tag No.: K0052
Based on observation and interview with staff, the facility failed to provide a fire alarm system required for life safety that is installed, tested, and maintained in accordance with NFPA 70 National Electrical Code and NFPA 72. Findings,
Magnetic locks and combination fire and smoke dampers are not listed on the annual fire alarm inspection form. All equipment tied into the fire alarm system is required to be tested annually and shown on the inspection report form.
Tag No.: K0056
Based on observation and interview with staff, the facility failed to provide automatic sprinkler coverage that is installed in accordance with NFPA 13. Findings,
The front porch is constructed with combustible material and is not provided with fire suppression coverage.