Bringing transparency to federal inspections
Tag No.: K0039
Based on observation, the facility failed to maintain clear and unobstructed corridors.
Findings include:
At 2:00 p.m., on 1-24-12, it was observed that the corridor in the Geriatrics Unit was obstructed with couches, chairs, tables, etc.
Tag No.: K0050
Based on record review, the facility failed to conduct fire drills as required.
Findings include:
At 1:00 p.m., on 1-24-12 the facility was unable to produce records of fire drills for the past 12 months.
Tag No.: K0052
Based on record review, the facility failed to conduct an annual inspection of the fire alarm system.
Findings include:
 At 1:15 p.m., on 1-24-12, the facility was unable to produce records of the annual inspection of the fire alarm system.
NFPA 72 Table 7-3-1 requires annual inspection of the fire alarm system.
Tag No.: K0054
Based on record review, the facility failed to maintain the smoke detectors as required.
Findings include:
At 1:30 p.m., on 1-24-12, the facility was unable to provide records for the sensitivity testing of the smoke detectors.
NFPA 72, 7-3.2.1 Smoke detector sensitivity shall be checked within one year after installation and every alternate year thereafter.
Tag No.: K0062
Based on record review, the facility failed to conduct required test of the sprinkler system.
Findings include:
At 1:30 p.m., on 1-24-12, the facility was unable to provide records for the quarterly testing of the fire alarm system.
NFPA 25, 2-1 requires the sprinkler alarm components shall be tested quarterly.
Tag No.: K0144
Based on record review, the facility failed to maintain the generator as required.
Findings include:
(1) At 1:40 p.m., on 1-24-12, the facility was unable to provide documentation of the monthly load testing of the generator.  NFPA 110, 6-4.2 requires generator to be exercised under load for 30 minutes monthly.
(2) At 2;30 p.m., on 1-24-12 it was observed that no task illumination was provided for the emergency generator.  NFPA 99 3-4.2.2.2 requires emergency battery light for task illumination for emergency power at the generator set location.
(3) At 2:30 p.m., on 1-24-12 it was observed that there was no remote common audible alarm for the emergency generator.  NFPA 110 sect. 3-5.6.1 requires a remote, common audible alarm powered by the storage battery.  This remote alarm shall be located outside the EPS service room at a work station readily observable by personnel.