Tag No.: K0018

Based on observation, it was determined that the facility failed to ensure no obstruction exist preventing doors protecting corridor openings from closing and latching.

Findings include:

1. On 2/4/15 in the presence of Staff #6, the following corridor doors were blocked open preventing the self-closing devises from operating and positive latching the doors:

a. At 11:35 AM one, 1 3/4 hour rated fire door to the Basement Elevator Room (#H007) was held open by a wet floor sign.

b. At 11:40 AM one, 1 3/4 hour rated fire door to the Shop was held open by a plastic cart.

c. At 11:50 AM one, 1 /3/4 hour rated fire door to the Cleaning Supply Room was held open by a cardboard box.

d. At 11:55 AM one, 1 3/4 hour fire rated Kitchen Door (#F005C) was held open by a plastic garbage can.

e. At 12:00 PM one, 1/3/4 hour fire rated Kitchen Door (#F016) was held open by a plastic garbage can.

No Description Available

Tag No.: K0029

Based on observation, it was determined that the facility failed to maintain a one-hour fire rated barrier with a 3/4 hour fire-rated door that is self-closing.

Findings include:

On 2/4/15 at 11:35 AM, in the presence of Staff #6, the 3/4 hour fire-rated door to the Repair Shop was held open by a plastic wedge.