Tag No.: K0038

Based on observation, on March 13, 2012 at approximately 7:30am onward, exit access doors throughout the facility are equipped with deadbolt locks in addition to other latching devices; such arrangements create greater than a single motion of the hand to exit areas. Latching hardware on referenced doors exceeds forty-eight inch maximum height above finished floor.

Waiver remaining - waiver date August 1, 2012

No Description Available

Tag No.: K0038

Based on observation, on March 14, 2012 at approximately 7:30am onward, exit access doors throughout the facility are equipped with deadbolt locks in addition to other latching devices; such arrangements create greater than a single motion of the hand to exit areas. Latching hardware on referenced doors exceeds forty-eight inch maximum height above finished floor.


Waiver remaining - waiver date August 1, 2012

No Description Available

Tag No.: K0061

Based on observation, on March 13, 2012 at approximately 7:30am onward, there is no electrical supervision of main control valves located in above ground hot boxes near front entrance driveway, and rear driveway.


Waiver remaining - waiver date August 1, 2012

No Description Available

Tag No.: K0061

Based on observation, on March 13, 2012 at approximately 7:30am onward, there is no electrical supervision of main sprinkler control valves located in above ground valve box.


Waiver remaining - waiver date August 1, 2012