Tag No.: K0018
Based on observation during the morning of February 17, 2010, many corridor doors to rooms at the 100 wing had roller latches that are prohibited by CMS regulations.
Tag No.: K0027
Based on observation during the afternoon of February 17, 2010, the smoke-barrier door in the corridor near the ER waiting roomwas secured in the open position because the magnetic hold-open device was broken.
Tag No.: K0029
Based on observation during the afternoon of February 17, 2010, the door to the X-ray film storage room was not self-closing as required for a hazardous area.