Bringing transparency to federal inspections
Tag No.: K0324
Based on observation it was determined that the facility failed to maintain the kitchen hood suppression system as required by NFPA 96, (Chapter 12, Section 12.1.2.3.1) and cooking appliance restraint as required by NFPA 54, 9.6.1.2. 
Commercial cooking equipment under suppression system does not have wheel blocks installed
NFPA 96, 12.1.2.3 The fire-extinguishing system shall not require reevaluation where the cooking appliances are moved for the purposes of maintenance and cleaning, provided the appliances are returned to approved design location prior to cooking operations.
NFPA 54 -2012 Fuel and Gas Code 9.6.1.2 Restraints.  Movement of appliances with casters shall be limited by a restraining device installed in accordance with the connector and appliance manufacturer installation instructions.
This deficiency has the potential to affect occupants, who might include residents, staff, and visitors within the entire facility. Deficient items were discussed with the Administrator at the exit conference.
Tag No.: K0345
Based on a record review it was determined that the facility failed to maintain the fire alarm system components and devices in accordance with the Life Safety Code Section 9.6 and NFPA 72.
1.No Semi-Annual report available for review 
2.No 2 year smoke detector sensitivity report available for review
NFPA 101, Section 9.6.1.5* To ensure operational integrity, the fire alarm system shall have an approved maintenance and testing program complying with the applicable requirements of 
NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm and Signaling Code.
NFPA 72- 14.4.2.2* Systems and associated equipment shall be tested according to Table 14.4.2.2. (15). Alarm notification appliances (a) Audible: Test shall be performed in accordance with the manufacturer ' s published instructions. Appliance locations shall be verified to be per approved layout, and it shall be confirmed that no floor plan changes affect the approved layout. It shall be verified that the candela rating marking agrees with the approved drawing. It shall be confirmed that each appliance flashes.
Failure to maintain the fire alarm system has the potential to harm all occupants, staff, and visitors within the building should a delay occur in locating a fire throughout the facility.
These deficiencies have the potential to affect occupants, who might include residents, staff, and visitors within the entire facility. Deficient items were discussed with the Administrator and Maintenance director at the exit conference.
Tag No.: K0363
Based on observation it was determined the facility failed to maintain corridor doors  in accordance with NFPA 101.
1.Roll down fire door need to be inspected | Cafe Fire door x 2, Medical records 
2. Pair of fire doors by laundry did not close fully 
NFPA 80 5.2.1*  Fire door assemblies shall be inspected and tested not less than annually, and a written record of the inspection shall be signed and kept for inspection by the AHJ.
NFPA 101, 19.3.6.3.1*  Doors protecting corridor openings in other than required enclosures of vertical openings, exits, or hazardous areas shall be doors constructed to resist the passage of smoke and shall be constructed of materials such as the following:
(1) 13/4 in. (44 mm) thick, solid-bonded core wood
(2) Material that resists fire for a minimum of 20 minutes
NFPA 101, 19.3.6.3.5* 
Doors shall be provided with a means for keeping the door closed that is acceptable to the authority having jurisdiction, and the following requirements also shall apply:
(1) The device used shall be capable of keeping the door fully closed if a force of 5 lbf (22 N) is applied at the latch edge of the door.
(2)Roller latches shall be prohibited on corridor doors in buildings not fully protected by an approved automatic sprinkler system in accordance with 19.3.5.7.
This deficiency has the potential to affect occupants, who might include residents, staff, and visitors within the entire facility. Deficient items were discussed with the administrator and  maintenance director at the exit conference.
Tag No.: K0521
Based on observation and staff interview, it was determined that the facility failed to maintain smoke dampers in accordance with Life Safety Code Section NFPA 105
Fire Dampers was overdue for facility (6 year)
NFPA 105, 6.5.1 Smoke dampers for dedicated and non-dedicated smoke control systems shall be inspected and tested in accordance with NFPA 92A, Standard for Smoke-Control Systems Utilizing Barriers and Pressure Differences.
6.5.2* Each damper shall be tested and inspected one year after installation. The test and inspection frequency shall then be every 4 years, except in hospitals, where the frequency shall
be every 6 years.
6.5.3 Care shall be exercised that all tests are completed in a safe manner wearing the appropriate personal protective equipment.
6.5.4 Full unobstructed access to the damper shall be verified and corrected as required.
LSC 19.5.2.1 requires air conditioning, heating, ventilating ductwork and related equipment to be installed in accordance with NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems. NFPA 90A, 2012 Edition, Section 4.3.12.1.1 states egress corridors shall not be used as a portion of a supply, return, or exhaust air system serving adjoining areas unless otherwise permitted by 4.3.12.1.3.1 through 4.3.12.1.3.4
This deficiency has the potential to affect occupants, who might include residents, staff, and visitors within the entire facility. Deficient items were discussed with the administrator and  maintenance director at the exit conference.
Tag No.: K0712
Based on record review, it was determined that the facility failed to conduct fire drills in accordance with the Life Safety Code, Section 19.7.1.6
 1.Fire Drills | Missed 2nd shift 3 qrt of 2023 
NFPA 101, 19.7.1.6 Drills shall be conducted quarterly on each shift to familiarize facility personnel (nurses, interns, maintenance engineers, and administrative staff) with the signals and emergency action required under varied conditions.
This deficiency has the potential to affect occupants, who might include residents, staff, and visitors within the entire facility. Deficient items were discussed with the administrator and  maintenance director at the exit conference.