Tag No.: K0017
Facility failed to maintain corridors in accordance with the 2000 edition of the Life Safety Code, NFPA 101. Findings included the following:
Surveyor observed between 12:30 and 1:30 pm on 7/21/15 that IT room ( former surgery lounge) had air transfer grilles in corridor. This does not meet NFPA 101, 2003: 19.3.6.4 Transfer Grilles. Transfer grilles, regardless of whether they are protected by fusible-link dampers, shall not be used in these walls or doors. In addition the door was chocked open with waste basket due to heat build up.
Tag No.: K0018
Facility to maintain 4 doors to egress corridor in accordance with the 2000 edition of the Life Safety Code NFPA (National Fire Protection Association) 101. Findings included the following:
Surveyor observed between 12:30 and 1:30 pm on 7/21/15 that doors to IT, dining, pharmacy, and central supply were chocked open which is an impediment to closing the doors.
Tag No.: K0056
Facility failed to maintain sprinkler piping in accordance with NFPA 13, Standard for installation of Fire Sprinklers. Findings included the following:
Surveyor observed between 11:00 and 11:30 am on 7/21/15 that one fire sprinkler below ceiling in alcove leading to Maintenance Room and one in the kitchen near stove appeared to be bent.
Tag No.: K0067
Facility failed to maintain ventilation in accordance with ventilation table cross-referenced in
NFPA 90A, Findings included the following:
Surveyor observed between 1:00 and 1:30 pm that storage room had been coverted to use as janitor closet and exhaust required for this room was present.
Tag No.: K0130
Facility failed to maintain disaster policy in accordance with the Standard for Health Care Facilities, NFPA
99. Findings included the following:
Surveyor observed between 1:00 and 1:30 pm on 7/21/15 that disaster policy did not specifically require after-action reports of disaster drills.
Tag No.: K0147
Facililty failed to maintain electrical panels in accordance with the National Electrical Code, NFPA 70. Findings included the following:
Surveyor observed between 12:30 and 1:30 pm on 7/21/15 that 2 electrical panels in corridor including emergency panel near central supply were unlocked and not secure from unauthorized individuals.