Tag No.: K0061
Based on document review and observation, the facility failed to maintain required supervision of all shut-off valves and water supply for the sprinkler system. Tamper switches notify the facility of any interruption of the water supply to the sprinkler system.
The findings include:
During document review and observation during the revisit of the facility tour on 3/28/2013 with the Director of Maintenance, it was found that the backflow preventer was not supervised with the required tamper switch which are inspected and tested periodically. 19.7.6, 4.6.12, NFPA 13, NFPA 25, 9.7.5. The facility has gone through the bid selection and is awaiting scheduling from the contracted company to do the installation.