Bringing transparency to federal inspections
Tag No.: K0048
Based on observation and review of Drill Critique Forms, the facility failed to provide in-service training for all staff to be familiar with procedures or to provide in-service training as required for all staff to be in compliance. 19-7.1.2 Findings:
For the drill conducted on June 12, 2009, the drill report indicated the fire location was in the Equipment Room, a staff member commented on the critique form that during the drill, he did not know where the room was located. The facility failed to provide documentation that there was a follow-up or in-service training provided for the staff member regarding this incident..
Tag No.: K0051
Based on observation, review of records, and interview with staff, the facility failed to maintain the Fire Alarm System in accordance with NFPA 72, 1999 edition, 19.3.4 Findings:
The annual fire alarm system test report was not signed by a representative of the facility for the test conducted on 4-21-10 and there was not a record of a re-acceptance test of the Fire Alarm System after the replacement of the system's mother board on August 27-09.
Tag No.: K0078
Based on observation and interview with staff on December 20, 2010 at 2:30 PM, the facility failed to protect anesthetizing locations in accordance with NFPA 99, Standard for Health Care Facilities.
Findings:
(1) Relative humidity is not maintained equal to or greater than 35%. The Fairview Regional Medical Center Nursing Policy #: SG-0073, Department: Surgery, revised 11-26-07, states that the Relative Humidity will be kept between 50-55%. The Surgery Temperature /Humidity Control Log depicts during January 1-31, 2010 through March 1, 2010, humidity was logged from less than 10% to a high of not greater than 32%. Many days were in the low 20% range.
(2) The facility failed to provide documentation that the OR Room was provided with a supply and exhaust system that is arranged to vent smoke and products of combustion automatically or is tied into the Emergency Power System.
Tag No.: K0130
Based on observation, review of records, and interview with staff, the facility failed to test Medical Patient Care Equipment in accordance with NFPA 99, 1999 edition, Chapter 9-2.1. Finding:
The INVIVO) MDE /Morton 6# located in the recovery room, first bay, was not tested within a yearly test cycle and was not removed from service. It was last tested March of 2009.
Tag No.: K0048
Based on observation and review of Drill Critique Forms, the facility failed to provide in-service training for all staff to be familiar with procedures or to provide in-service training as required for all staff to be in compliance. 19-7.1.2 Findings:
For the drill conducted on June 12, 2009, the drill report indicated the fire location was in the Equipment Room, a staff member commented on the critique form that during the drill, he did not know where the room was located. The facility failed to provide documentation that there was a follow-up or in-service training provided for the staff member regarding this incident..
Tag No.: K0051
Based on observation, review of records, and interview with staff, the facility failed to maintain the Fire Alarm System in accordance with NFPA 72, 1999 edition, 19.3.4 Findings:
The annual fire alarm system test report was not signed by a representative of the facility for the test conducted on 4-21-10 and there was not a record of a re-acceptance test of the Fire Alarm System after the replacement of the system's mother board on August 27-09.
Tag No.: K0078
Based on observation and interview with staff on December 20, 2010 at 2:30 PM, the facility failed to protect anesthetizing locations in accordance with NFPA 99, Standard for Health Care Facilities.
Findings:
(1) Relative humidity is not maintained equal to or greater than 35%. The Fairview Regional Medical Center Nursing Policy #: SG-0073, Department: Surgery, revised 11-26-07, states that the Relative Humidity will be kept between 50-55%. The Surgery Temperature /Humidity Control Log depicts during January 1-31, 2010 through March 1, 2010, humidity was logged from less than 10% to a high of not greater than 32%. Many days were in the low 20% range.
(2) The facility failed to provide documentation that the OR Room was provided with a supply and exhaust system that is arranged to vent smoke and products of combustion automatically or is tied into the Emergency Power System.
Tag No.: K0130
Based on observation, review of records, and interview with staff, the facility failed to test Medical Patient Care Equipment in accordance with NFPA 99, 1999 edition, Chapter 9-2.1. Finding:
The INVIVO) MDE /Morton 6# located in the recovery room, first bay, was not tested within a yearly test cycle and was not removed from service. It was last tested March of 2009.