HospitalInspections.org

Bringing transparency to federal inspections

4600 38TH ST

COLUMBUS, NE 68601

No Description Available

Tag No.: K0064

Based on observation and staff interview the facility failed to provide a placard for the Class K fire extinguisher that stated that the fire protection system shall be activated prior to using the fire extinguisher. This deficient practice would lead to a misuse of the fire extinguisher preventing the fire from being extinguished. The facility census was 48.
Findings are:
Observation on 5-12-16 at 12:57 pm revealed the Class K fire extinguisher in the kitchen and in the cafeteria did not have a placard that stated that the fire protection system shall be activated prior to using the fire extinguisher.
During an interview on 5-12-16 at 12:57 pm observations were acknowledged and verified by Maintenance Staff A.

NFPA Standard:
NFPA 10 1998 ed. 2-3.2.1 A placard shall be conspicuously placed near the extinguisher that states that the fire protection system shall be activated prior to using the fire extinguisher.

No Description Available

Tag No.: K0072

Based on observation and interview, this facility did not provide unobstructed corridors that provide a clear path of egress. Exiting corridors shall be fee of obstructions to provide a reliable means of egress. This deficient practice can limit and/or delay evacuation in the event of an emergency. This facility census was 48 patients.

Findings are:
Observation on 5-12-16 at 1:45 pm of the C-Section corridor revealed the corridor was being obstructed by two metal carts, bassenette filled with pillows.

During an interview 5-12-16 at 1:45 pm, Maintenance A confirmed the findings

NFPA Standard:
Means of egress shall be continuously maintained free of all obstructions or impediments to full instant use in the case of fire or other emergency. 2000 NFPA 101, 7.1.10.1