Tag No.: K0033
Based on observation and document review, the provider failed to maintain a one hour fire resistive path of egress from the basement to the exterior of the building. One of two basement stairways (west) discharged onto the main level. Findings include:
1. Observation at 11:30 a.m. revealed the west basement stairway discharged onto the main level adjacent to the waiting room. A continuous one hour enclosure was not provided to the exterior of the building. Review of the previous life safety code survey confirmed that finding.
The building meets the FSES. Please mark an "F" in the completion date column to indicate correction of the deficiencies identified in K000.