Means of Egress - General

Tag No.: K0211

Based on observations during the tour of the facility on the morning of 01/11/2017, with Regional Facility Manager and the Director of Engineering, the Womens pavillion east ground door failed to lacth properly also door lacks proper hardware. Replace door to provide functional door with proper hardware;door closer, push bar from egress side and card access from outside.

Exit Signage

Tag No.: K0293

Based on observations during the tour of the facility on the morning of 01/11/2017, with Regional Facility Manager and the Director of Engineering, directional exit signs were missing on the 2nd and 3rd floor by nurse station.

Health Care Facilities Code - Other

Tag No.: K0900

Based on observations during the tour of the facility on the morning of 01/11/2017, with Regional Facility Manager and the Director of Engineering, the med gas storage room did not provide the required natural ventilation openings. room was missing the required low opening (12 in from floor). Opening shall be 72 sq in per NFPA 9.3.7.5.2

Gas and Vacuum Piped Systems - Central Supply

Tag No.: K0905

Based on observations during the tour of the facility on the morning of 01/11/2017, with Regional Facility Manager and the Director of Engineering, the med gas storage room exterior door did not provide the required signage.