Exit Signage

Tag No.: K0293

.

Based on observation, the facility failed to provide continuous illumination of the exit signage per the requirements of:

2012 NFPA 101, 19.2.10.1, and 7.10.5.2.1

This deficiency affects 1 of 6 smoke compartments.

Findings include:

On 05/03/2022, during a tour of the facility from 11:30 pm to 3:30 pm, the surveyor observed the exit sign at room 710 was not illuminated.

A member of the maintenance staff was present when the deficiency was identified.

.

Sprinkler System - Maintenance and Testing

Tag No.: K0353

.

Based on observation and interview, the facility failed to maintain an automatic sprinkler head per the requirements of:

2012 NFPA 101, 19.3.5.1, and 9.7.5
2011 NFPA 25, 5.2.1.1.1, and 5.2.1.1.2

This deficiency affects 1 of 6 smoke compartments.

Findings include:

On 05/03/2022, during a tour of the facility from 11:33 am to 3:30 pm, the surveyor observed the automatic sprinkler head in the Cooler had excessive dust and corrosion.

A member of the maintenance staff was present when this deficiency was identified.

.

Portable Fire Extinguishers

Tag No.: K0355

.

Based on observation, the facility failed to maintain a portable fire extinguisher per the requirements of:

2012 NFPA 101, 19.3.5.12, and 9.7.4.1
2010 NFPA 10, 5.5.5.3

This deficiency affects 1 of 6 smoke compartments.

Findings include:

On 05/03/2022, during a tour of the facility from 11:30 am to 3:30 pm, the surveyor observed the K- fire extinguisher in the kitchen without the required placard/sign, stating the fire protection system shall be actuated prior to using the fire extinguisher.

A member of the maintenance staff was present when this deficiency was identified.

.

Subdivision of Building Spaces - Smoke Barrie

Tag No.: K0372

.
Based on observation, the facility failed to maintain smoke barriers that would provide at least a half hour fire resistance rating and restrict the movement of smoke per the requirements of:

2012 NFPA 101, 19.3.7.3, 8.5.1, 8.5.6.2, and 8.5.6.3

This deficiency affects 2 of 6 smoke compartments.

Findings include:

On 05/04/2022, during a tour of the facility from 11:30 am to 3:30 pm, the surveyor observed a 2" unsealed conduit on both sides of the smoke barrier with 8 blue and black cables, above the ceiling near rooms 407 and 409.

A member of the maintenance staff was present when this deficiency was identified.