Bringing transparency to federal inspections
Tag No.: K0029
Based on observation the facility failed to provide adequate smoke barriers.
The inspector observed, while accompanied by the Director of the facility service during the hours of the inspection from 3:00 pm to 6:00 pm on 5/28/2013 that there were doors and frame fire rated labels missing at the following locations: 1) The storage room ( previously to be used as seclusion room) at the clinic.
Tag No.: K0056
Based on observation the facility failed to provide a complete sprinkler system.
The inspector observed, while accompanied by the Director of the facility service during the hours of the inspection from 3:00 pm to 6:00 pm on 5/28/2013 that there were the following issues: There were missing sprinkler head at the following locations: 1) Kitchen at the Clinic.
Tag No.: K0106
Based on observation the facility failed to provide adequate receptacles.
The inspector observed, while accompanied by the Director of the facility service during the hours of the inspection from 3:00 pm to 6:00 pm on 5/28/2013 that there was the following issue: (1). There was a missing battery powered lighting units at the essential automatic transfer switch at the electrical room. (2). FACP breaker was not provided in red breaker and labeled in red signage permanently.
" The emergency generator location shall have task illumination, battery charger for emergency battery powered lighting unit(s), and selected receptacles at the generator set location and essential automatic transfer switch location " - NFPA 99, 1999: 3-4.2.2.2.(b)5.
" NFPA 72, 2002: 4.4.1.4.2.2 -The electrical connection between the panel/breaker and the FACP must be cross referenced correctly. " The circuit breaker at the electrical panel board for the fire alarm shall have a red marking, shall be accessible only to authorized personnel, and shall be identified as "FIRE ALARM CIRCUIT CONTROL" " - NFPA 72, 2002: 4.4.1.4.2.2. " The location of the circuit disconnecting means shall be permanently identified at the fire alarm control unit. " - NFPA 72, 2002: 4.4.1.4.2.3 "