Bringing transparency to federal inspections
Tag No.: K0021
Based on observation, it was determined that all fire doors do not close automatically during a Code Red fire drill and activation of the Fire Alarm System.
Findings include:
1. On 12/9/14 at 11:00 AM, Unit 4 North was toured in the presence of Staff #7, Staff #11, and Staff #15. At 11:13 AM, the fire alarm system activated and a Code Red [Fire] was called over the public address system.
a. The first set of double fire doors located at the end of 4 North [heading to 4 South] did not close during the Code Red.
b. The second set of fire doors, leading from a small hallway from 4 North to the 4 South bridge, did not close during the Code Red.
2. Staff #13 confirmed upon interview, that these doors should have closed automatically during the Code Red.
Tag No.: K0147
Based on observation, it was determined that the facility failed to ensure that electrical wiring and equipment are in accordance with NFPA 70, National Electric Code.
Findings include:
Reference #1: 1999 edition of NFPA 70, 70:110-26(b) Clear Spaces. Working space required by this section shall not be used for storage.
1. On 12/9/14 at 12:10 PM in the presence of Staff #4, two cardboard boxes and a plastic utility cart were located in the Electrical Room near Operating Room #4, in the Same Day Surgery Suite.