Tag No.: K0018

Based on observation and interview, it was determined the facility failed to maintain corridor doors in one instance on one of three floors.

Findings Include:

Observation on 6/29/11 at 9:29am revealed the following:

The morgue door in the basement level lacked positive latching hardware.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the lack of hardware.

No Description Available

Tag No.: K0025

Based on observation and interview, it was determined the facility failed to maintain the smoke wall in two instances on one of three floors.

Findings Include:

Observation on 6/29/11 revealed the following:

a) At 10:47am, there was a smoke wall penetration above the ceiling in the first floor chapel.
b) At 11:17am, there was a smoke wall penetration above the ceiling in the first floor doctors' lounge area.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the smoke wall penetrations.

No Description Available

Tag No.: K0029

Based on observation and interview, it was determined the facility failed to maintain hazardous area room requirements in three instances on three of three floors.

Findings Include:

Observation on 6/28/11 and 6/29/11 revealed the following:

a) On 6/28/11 at 11:37am, the biohazard doors on the first and second floors and the storage room near the nurses' station on the first floor lack positive latching hardware.
b) On 6/29/11 at 9:17am, the storage room #2 door was not fully closing and latching.
c) On 6/29/11 at 9:36am, the storage room inside the conference room lacks a fire rated door and automatic door closer.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the hazardous area door issues.

No Description Available

Tag No.: K0066

Based on observation and interview, it was determined the facility failed to maintain smoking regulations in one instance on one of three floors.

Findings Include:

Observation on 6/28/11 at 11:59am revealed the following:

There was evidence of smoking in a non-designated area outside off of the first floor lab area.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the smoking policy violation.

No Description Available

Tag No.: K0072

Based on observation and interview, it was determined the facility failed to maintain clear exit access in one instance on one of three floors.

Findings Include:

Observation on 6/29/11 at 11:00am revealed the following:

There were chairs outside the first floor emergency department that were blocking exit access.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the presence of the chairs.

No Description Available

Tag No.: K0076

Based on observation and interview, it was determined the facility failed to maintain gas cylinder requirements.

Findings Include:

Observation on 6/29/11 at 10:01am revealed the following:

There were nitrogen cylinders in the gas storage room that were painted red instead of the required color black.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the presence of red nitrogen cylinders.

No Description Available

Tag No.: K0147

Based on observation and interview, it was determined the facility failed to maintain electrical requirements in one instance on one of three floors.

Findings Include:

Observation on 6/28/11 at 11:50am revealed the following:

There was a toaster oven and a microwave plugged in with a surge protector in the first floor lab area break room.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed items plugged in with the surge protector.

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on observation and interview, it was determined the facility failed to maintain corridor doors in one instance on one of three floors.

Findings Include:

Observation on 6/29/11 at 9:29am revealed the following:

The morgue door in the basement level lacked positive latching hardware.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the lack of hardware.

LIFE SAFETY CODE STANDARD

Tag No.: K0025

Based on observation and interview, it was determined the facility failed to maintain the smoke wall in two instances on one of three floors.

Findings Include:

Observation on 6/29/11 revealed the following:

a) At 10:47am, there was a smoke wall penetration above the ceiling in the first floor chapel.
b) At 11:17am, there was a smoke wall penetration above the ceiling in the first floor doctors' lounge area.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the smoke wall penetrations.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on observation and interview, it was determined the facility failed to maintain hazardous area room requirements in three instances on three of three floors.

Findings Include:

Observation on 6/28/11 and 6/29/11 revealed the following:

a) On 6/28/11 at 11:37am, the biohazard doors on the first and second floors and the storage room near the nurses' station on the first floor lack positive latching hardware.
b) On 6/29/11 at 9:17am, the storage room #2 door was not fully closing and latching.
c) On 6/29/11 at 9:36am, the storage room inside the conference room lacks a fire rated door and automatic door closer.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the hazardous area door issues.

LIFE SAFETY CODE STANDARD

Tag No.: K0066

Based on observation and interview, it was determined the facility failed to maintain smoking regulations in one instance on one of three floors.

Findings Include:

Observation on 6/28/11 at 11:59am revealed the following:

There was evidence of smoking in a non-designated area outside off of the first floor lab area.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the smoking policy violation.

LIFE SAFETY CODE STANDARD

Tag No.: K0072

Based on observation and interview, it was determined the facility failed to maintain clear exit access in one instance on one of three floors.

Findings Include:

Observation on 6/29/11 at 11:00am revealed the following:

There were chairs outside the first floor emergency department that were blocking exit access.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the presence of the chairs.

LIFE SAFETY CODE STANDARD

Tag No.: K0076

Based on observation and interview, it was determined the facility failed to maintain gas cylinder requirements.

Findings Include:

Observation on 6/29/11 at 10:01am revealed the following:

There were nitrogen cylinders in the gas storage room that were painted red instead of the required color black.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed the presence of red nitrogen cylinders.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on observation and interview, it was determined the facility failed to maintain electrical requirements in one instance on one of three floors.

Findings Include:

Observation on 6/28/11 at 11:50am revealed the following:

There was a toaster oven and a microwave plugged in with a surge protector in the first floor lab area break room.

Interview with the facility representative on 6/29/11 at 12:30pm confirmed items plugged in with the surge protector.