Tag No.: K0018
Based on observation and interview, it was determined the facility failed to maintain corridor doors in one instance on one of three floors.
Findings Include:
Observation on 6/29/11 at 9:29am revealed the following:
The morgue door in the basement level lacked positive latching hardware.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the lack of hardware.
Tag No.: K0025
Based on observation and interview, it was determined the facility failed to maintain the smoke wall in two instances on one of three floors.
Findings Include:
Observation on 6/29/11 revealed the following:
a) At 10:47am, there was a smoke wall penetration above the ceiling in the first floor chapel.
b) At 11:17am, there was a smoke wall penetration above the ceiling in the first floor doctors' lounge area.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the smoke wall penetrations.
Tag No.: K0029
Based on observation and interview, it was determined the facility failed to maintain hazardous area room requirements in three instances on three of three floors.
Findings Include:
Observation on 6/28/11 and 6/29/11 revealed the following:
a) On 6/28/11 at 11:37am, the biohazard doors on the first and second floors and the storage room near the nurses' station on the first floor lack positive latching hardware.
b) On 6/29/11 at 9:17am, the storage room #2 door was not fully closing and latching.
c) On 6/29/11 at 9:36am, the storage room inside the conference room lacks a fire rated door and automatic door closer.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the hazardous area door issues.
Tag No.: K0066
Based on observation and interview, it was determined the facility failed to maintain smoking regulations in one instance on one of three floors.
Findings Include:
Observation on 6/28/11 at 11:59am revealed the following:
There was evidence of smoking in a non-designated area outside off of the first floor lab area.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the smoking policy violation.
Tag No.: K0072
Based on observation and interview, it was determined the facility failed to maintain clear exit access in one instance on one of three floors.
Findings Include:
Observation on 6/29/11 at 11:00am revealed the following:
There were chairs outside the first floor emergency department that were blocking exit access.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the presence of the chairs.
Tag No.: K0076
Based on observation and interview, it was determined the facility failed to maintain gas cylinder requirements.
Findings Include:
Observation on 6/29/11 at 10:01am revealed the following:
There were nitrogen cylinders in the gas storage room that were painted red instead of the required color black.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the presence of red nitrogen cylinders.
Tag No.: K0147
Based on observation and interview, it was determined the facility failed to maintain electrical requirements in one instance on one of three floors.
Findings Include:
Observation on 6/28/11 at 11:50am revealed the following:
There was a toaster oven and a microwave plugged in with a surge protector in the first floor lab area break room.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed items plugged in with the surge protector.
Tag No.: K0018
Based on observation and interview, it was determined the facility failed to maintain corridor doors in one instance on one of three floors.
Findings Include:
Observation on 6/29/11 at 9:29am revealed the following:
The morgue door in the basement level lacked positive latching hardware.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the lack of hardware.
Tag No.: K0025
Based on observation and interview, it was determined the facility failed to maintain the smoke wall in two instances on one of three floors.
Findings Include:
Observation on 6/29/11 revealed the following:
a) At 10:47am, there was a smoke wall penetration above the ceiling in the first floor chapel.
b) At 11:17am, there was a smoke wall penetration above the ceiling in the first floor doctors' lounge area.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the smoke wall penetrations.
Tag No.: K0029
Based on observation and interview, it was determined the facility failed to maintain hazardous area room requirements in three instances on three of three floors.
Findings Include:
Observation on 6/28/11 and 6/29/11 revealed the following:
a) On 6/28/11 at 11:37am, the biohazard doors on the first and second floors and the storage room near the nurses' station on the first floor lack positive latching hardware.
b) On 6/29/11 at 9:17am, the storage room #2 door was not fully closing and latching.
c) On 6/29/11 at 9:36am, the storage room inside the conference room lacks a fire rated door and automatic door closer.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the hazardous area door issues.
Tag No.: K0066
Based on observation and interview, it was determined the facility failed to maintain smoking regulations in one instance on one of three floors.
Findings Include:
Observation on 6/28/11 at 11:59am revealed the following:
There was evidence of smoking in a non-designated area outside off of the first floor lab area.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the smoking policy violation.
Tag No.: K0072
Based on observation and interview, it was determined the facility failed to maintain clear exit access in one instance on one of three floors.
Findings Include:
Observation on 6/29/11 at 11:00am revealed the following:
There were chairs outside the first floor emergency department that were blocking exit access.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the presence of the chairs.
Tag No.: K0076
Based on observation and interview, it was determined the facility failed to maintain gas cylinder requirements.
Findings Include:
Observation on 6/29/11 at 10:01am revealed the following:
There were nitrogen cylinders in the gas storage room that were painted red instead of the required color black.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed the presence of red nitrogen cylinders.
Tag No.: K0147
Based on observation and interview, it was determined the facility failed to maintain electrical requirements in one instance on one of three floors.
Findings Include:
Observation on 6/28/11 at 11:50am revealed the following:
There was a toaster oven and a microwave plugged in with a surge protector in the first floor lab area break room.
Interview with the facility representative on 6/29/11 at 12:30pm confirmed items plugged in with the surge protector.