HospitalInspections.org

Bringing transparency to federal inspections

187 HOSPITAL DRIVE

TYRONE, PA 16686

No Description Available

Tag No.: K0029

Based on observation and interview, it was determined the facility failed to maintain hazardous area room requirements in three instances on three of three floors.

Findings Include:

Observation on 6/28/11 and 6/29/11 revealed the following:

b) On 6/29/11 at 9:17 am, the storage room #2 door was not fully closing and latching. Based on a revisit on 8/16/11, this item found not to be corrected.
c) On 6/29/11 at 9:36 am, the storage room inside the conference room lacks a fire rated door and automatic door closer. Based on a revisit on 8/16/11, this item was found not to be corrected.

Interview with the facility representative on 6/29/11 at 12:30 pm confirmed the hazardous area door issues.

No Description Available

Tag No.: K0076

Based on observation and interview, it was determined the facility failed to maintain gas cylinder requirements.

Findings Include:

Observation on 6/29/11 at 10:01 am revealed the following:

There were nitrogen cylinders in the gas storage room that were painted red instead of the required color black. Based on a revisit on 8/16/11, this item was found not to be corrected.

Interview with the facility representative on 6/29/11 at 12:30 pm confirmed the presence of red nitrogen cylinders.

No Description Available

Tag No.: K0147

Based on observation and interview, it was determined the facility failed to maintain electrical requirements in one instance on one of three floors.

Findings Include:

Observation on 6/28/11 at 11:50 am revealed the following:

There was a toaster oven and a microwave plugged in with a surge protector in the first floor lab area break room. Based on a revisit on 8/16/11, this item was found not to be corrected.

Interview with the facility representative on 6/29/11 at 12:30 pm confirmed items plugged in with the surge protector.