Building Construction Type and Height

Tag No.: K0161

Based on observation and interview, it was determined the facility exceeded maximum allowable story height for this type of construction.

Findings include:

1. Observation on November 17, 2021, at 9:35 a.m., revealed the facility exceeded the maximum allowable story height for three story, Type II (000), unprotected, noncombustible building.

Exit interview with facility representative #1 on November 17, 2021, at 12:15 p.m., confirmed the facility exceeds maximum allowable story height for this type of construction.

Portable Fire Extinguishers

Tag No.: K0355

Based on observation and interview, it was determined the facility failed to maintain portable fire extinguishers, affecting one of approximately ten fire extinguishers within the component level.

Findings include:

1. Observation on November 17, 2021, at 10:15 a.m., revealed the flush mounted fire extinguisher located in the 2nd floor Short Procedure Unit area lacked adequate signage.

Exit interview with facility representative #1 on November 17, 2021, at 12:15 p.m., confirmed the lack of fire extinguisher signage.

Subdivision of Building Spaces - Smoke Barrie

Tag No.: K0374

Based on observation and interview, it was determined the facility failed to maintain smoke barrier doors, affecting two of five smoke compartments.

Findings include:

1. Observation on November 17, 2021, at 11:00 a.m., revealed the smoke barrier doors located on the 3rd floor had unsealed penetrations in the door frame.

Exit interview with facility representative #1 on November 17, 2021, at 12:15 p.m., confirmed the penetrations.

Electrical Equipment - Other

Tag No.: K0919

Based on observation and interview, it was determined the facility failed to maintain electrical wiring and equipment, affecting one of six smoke compartments.

Findings include:

1. Observation on November 17, 2021, at 11:50 a.m., revealed the bed located in 2nd floor doctor lounge was placed against an electrical receptacle.

Exit interview with facility representative #1 on November 17, 2021, at 12:15 p.m., confirmed the bed placed against an electrical receptacle.