Tag No.: K0130

Based on observations during the survey walk of the facility on the morning of 5/26/2016, accompanied by the Director of plant operation, the facility failed to properly label ESS panels.
" Emergency panels shall be distinctively marked so that they are readily identifiable as a component of the essential electrical system. " - NFPA 70, 2002: 110-22 and 700-9(a). They shall be labeled "LIFE SAFETY", "CRITICAL", or "EQUIPMENT" as applicable.

No Description Available

Tag No.: K0155

Based on observations during the survey walk of the facility on the morning of 5/26/2016, accompanied by the Director of plant operation, the facility staff was under fire watch due to the FACP not working. Provide documentation that problem has been corrected, tested and approved by fire marshall .