Tag No.: K0011

*The facility failed to provide a two hour fire barrier separation between the existing conforming building and the new MRI addition nonconforming building per code. Findings include:

During the visit, the following is an example of what was observed:
Per observation and interview there was no two hour fire barrier separating the following nonconforming construction types:
1. Type II (000) - with no automatic sprinkler system
2. Type V (000) - with no automatic sprinkler system
from the conforming construction Type II (222)

___________________________

2000 NFPA 101, 8.2.1 Buildings or structures occupied or used in accordance with the individual occupancy chapters (Chapters 12 through 42) shall meet the minimum construction requirements of those chapters. NFPA 220, Standard on Types of Building Construction, shall be used to determine the requirements for the construction classification. Where the building or facility includes additions or connected structures of different construction types, the rating and classification of the structure shall be based on either of the following:
(1) Separate buildings if a 2-hour or greater vertically-aligned fire barrier wall in accordance with NFPA 221, Standard for Fire Walls and Fire Barrier Walls, exists between the portions of the building
Exception: The requirement of 8.2.1(1) shall not apply to previously approved separations between buildings.
(2) The least fire-resistive type of construction of the connected portions, if no such separation is provided
.

No Description Available

Tag No.: K0012

*The facility failed to provide a conforming construction type per code. Findings include:

During the visit, the following is an example of what was observed:
The following construction types were observed at the MRI addition:
1. Type II (000) - without an automatic sprinkler system
2. Type V (000) - without an automatic sprinkler system

_____________________

2000 NFPA 101, 18.1.6.2 Health care occupancies shall be limited to the types of building construction shown in Table 18.1.6.2. (See 8.2.1.)


Table 18.1.6.2 Construction Type Limitations

Construction Type Stories
1 2 3 4 or
More

I(443) X X X X
I(332) X X X X
II(222) X X X X
II(111) X X X NP
II(000) X NP NP NP
III(211) X NP NP NP
III(200) NP NP NP NP
IV(2HH) X NP NP NP
V(111) X NP NP NP
V(000) NP NP NP NP

X: Permitted type of construction.
NP: Not permitted.


2000 NFPA 101, 4.6.6 Additions shall conform to the provisions for new construction.
.

No Description Available

Tag No.: K0024

*The facility failed to provide a two hour fire barrier separation between the existing conforming building and the new MRI addition nonconforming building per code. Findings include:

During the visit, the following is an example of what was observed:
Per observation and interview there was no two hour fire barrier separating the following nonconforming construction types:
1. Type II (000) - with no automatic sprinkler system
2. Type V (000) - with no automatic sprinkler system
from the conforming construction Type II (222)

___________________________

2000 NFPA 101, 8.2.1 Buildings or structures occupied or used in accordance with the individual occupancy chapters (Chapters 12 through 42) shall meet the minimum construction requirements of those chapters. NFPA 220, Standard on Types of Building Construction, shall be used to determine the requirements for the construction classification. Where the building or facility includes additions or connected structures of different construction types, the rating and classification of the structure shall be based on either of the following:
(1) Separate buildings if a 2-hour or greater vertically-aligned fire barrier wall in accordance with NFPA 221, Standard for Fire Walls and Fire Barrier Walls, exists between the portions of the building
Exception: The requirement of 8.2.1(1) shall not apply to previously approved separations between buildings.
(2) The least fire-resistive type of construction of the connected portions, if no such separation is provided
.

No Description Available

Tag No.: K0040

*The facility failed to provide an exit door per code. Findings include:

During the visit, the following is an example of what was observed:
The MRI addition exit door measured 36".

________________

2000 NFPA 101, 18.2.3.5 The minimum clear width for doors in the means of egress from sleeping rooms; diagnostic and treatment areas, such as x-ray, surgery, or physical therapy; and nursery rooms shall be as follows:
(1) Hospitals and nursing homes - 41.5 in. (105 cm)
(2) Psychiatric hospitals and limited care facilities - 32 in. (81 cm)

.

No Description Available

Tag No.: K0056

*The facility failed to provide an automatic sprinkler system per code. Findings include:

During the visit, the following is an example of what was observed:
The new MRI addition did not have an automatic sprinkler system.

__________________

2000 NFPA 101, 18.3.5.1 Buildings containing health care facilities shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.

.