Tag No.: K0012

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. FAHC Garden Pavilion Surv Room - Inspection revealed that the spray fire proofing has been removed from the steel beam.

No Description Available

Tag No.: K0018

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that the Fire Barrier wall next to room 793 on Baird 7 has penetrations that must be sealed with approved fire stopping material.

2. Inspection revealed that a conduit within a fire barrier wall near Stair F on Baird 3 needs to be sealed with approved fire stopping material.

No Description Available

Tag No.: K0027

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that self-closing devices were missing from the following locations:

FAHC Main Campus McClure Wing 5th Floor- East pantry door missing self-closing device.
FAHC Main Campus ACC West Pavilion 2nd Floor Room WP2-271 missing self-closing device.
FAHC Main Campus ACC West Pavilion 1st Floor Room WP1-194 missing self-closing device.
FAHC Main Campus Shepardson North 3rd Floor room 378 - door missing self-closing device.

2. Inspection of Baird 5 revealed that a Fire Barrier door near room 524B drags and needs adjustment.

3. Inspection of Baird 3 revealed that the Fire Barrier door near Room 310 does not latch properly.

4. Inspection of Shepardson 6 revealed that the Fire door near room 636 is not closing and must be adjusted.

No Description Available

Tag No.: K0029

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that in the FAHC Fanny Allen Campus Cafeteria, door G009 was missing from corridor.

No Description Available

Tag No.: K0033

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there was storage at the bottom landing of the egress stairway located in the MRI (Magnetic Resonance Imaging) wing of the FAHC (Fletcher Allen Health Care) Main Campus.

2. Inspection revealed that the Sprinkler system Pre-action valve cabinet was installed at the top of the MRI wing egress stairway located in the MRI wing of FAHC Main Campus.

No Description Available

Tag No.: K0033

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there was storage at the bottom landings of egress stairways (GS03 & GS02) located at the FAHC Fanny Allen Campus.

No Description Available

Tag No.: K0034

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that the South egress stairway exit door for Shepardson 3 South has a delayed egress lock that was installed without authorization of the City of Burlington Fire Marshal.

2. Inspection of Shepardson 5 revealed that the Exit door at the west end of the corridor is on an automatic release set for 30 seconds, but the door is labeled with a 15 second delay.

No Description Available

Tag No.: K0046

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection of Baird 5 revealed that Emergency light unit PNL LM#50 would not operate.

No Description Available

Tag No.: K0051

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that the fire alarm system has violations. These violations are listed below with the location of the violation:

FAHC ACC Main Pavilion 3rd floor at main entrance doors. The fire alarm system pull stations are blocked by wheel chairs and not readily accessible.
FAHC ACC West Pavilion 5th Floor by room WP5-204 - Inadequate smoke detector coverage.
FAHC ACC West Pavilion Room 2nd Floor WP2-237 - Smoke detector less than 3 feet from supply air diffuser.
FAHC Garden Pavilion - Smoke Detector #M3-49 at entrance door less than 3 feet from supply air diffuser.
FAHC ACC Main Pavilion 4th Floor Room MP4-108 - Smoke detector missing.
FAHC Garden Pavilion near Room 2324 - Smoke detector less than 3 feet from supply air diffuser.
FAHC Baird Wing Main Kitchen fire alarm system horn strobe in rear storage room blocked by storage rack.
FAHC ACC Emergency Department Room WP1-186 - Smoke detector less than 3 feet from supply air diffuser.
FAHC ACC East Pavilion 2nd Floor near door EP2-115 - Smoke detector less than 3 feet from supply air diffuser.
FAHC McClure 1 Inergen Fire Suppression System circuit breaker-lock missing. This was written up during the last two annual inspections and was not corrected.

2. Inspection of Baird 4 revealed that smoke detectors in corridors exceed standard spacing with as much as 74 inches between detectors. Additional smoke detectors must be provided.

3. Inspection of Shepardson 6 revealed that four smoke detectors on the unit are located within 1 foot of supply air grill and must be located at least 3 feet from the supply air. Also, the Fire alarm conduit needs approved fire stopping material in the wall next to room 637.

4. Inspection of Shepardson 5 revealed that the Fire Alarm panel shows lobby 401 smoke detector as dirty and needs cleaning. This detector had a solid light on, indicating a trouble.

5. Inspection of Shepardson 4 revealed a smoke detector near room 446 is located within 1 foot of supply air grill and must be located at least 3 feet from the supply air. Also, all smoke detectors in "On-Call Wing Bedrooms" are located within 1 foot of supply air grill.

4.

No Description Available

Tag No.: K0051

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that the fire alarm system has violations. These violations are listed below with the location of the violation:

FAHC/UHC Medical Records Department Room G409 - Smoke detectors not properly spaced.

No Description Available

Tag No.: K0056

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that was storage to close to sprinkler heads and that that are locations with sprinkler heads missing. The following is a list locations where these violations occurred:
FAHC ACC Wing West Pavilion Room EP4-215 has no sprinkler head.

2. Inspection of Baird 3 revealed that the Nurses station has a new suspended lighting system that blocks the sprinkler heads from protecting the area properly. Two additional sprinkler heads are needed in this area.

No Description Available

Tag No.: K0056

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that was storage to close to sprinkler heads and that that are locations with sprinkler heads missing. The following is a list locations where these violations occurred:
FAHC Fanny Allen Campus-Sprinkler head missing above trash compactor door located near the emergency exit on the ground floor.

No Description Available

Tag No.: K0056

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that was storage to close to sprinkler heads and that that are locations with sprinkler heads missing. The following is a list locations where these violations occurred:
a. FAHC/UHC Medical Records Department has storage within 18 inches of sprinkler heads.
b. O ' Brien Community Center in Winooski is missing a sprinkler head in the Aquatic Pool Closet.

No Description Available

Tag No.: K0069

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there is frying being conducted in the Fanny Allen Campus Rehab Dining Rooms without a kitchen hood or fire suppression system.

2. Inspection revealed that the kitchen staff did not know how to manually activate the kitchen hood fire suppression system in the FAHC Fanny Allen Campus Cafeteria.

No Description Available

Tag No.: K0069

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there is frying being conducted without a kitchen hood or suppression system on the customer serving line in the FAHC Main Street Café on Baird 3.

No Description Available

Tag No.: K0106

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there was not an emergency light mounted in the emergency generator room at FAHC Fanny Allen Campus.

No Description Available

Tag No.: K0147

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there are electrical power strips that are interconnected into one another in the ACC Wing of the FAHC Main Campus. The following is a list of locations where this occurs:
ACC West Pavilion 5th floor Room WP5-238
ACC Main Pavilion 4th floor Vascular Team Station
ACC Main Pavilion 3rd floor West storage room
ACC West Pavilion 1st floor GT Nurses Station & Acute Care Desk
ACC Main Pavilion 2nd Floor Breast Care Reception Desk
ACC East Pavilion 2nd floor rooms EP2-130 & EP2-130A

2. Inspection revealed the use of extension cords as a permanent power supply to equipment. The following is a list of the locations where this occurs:
FAHC Main Campus ACC Wing East Pavilion Room EP5-135
FAHC Main Campus Baird Wing Main Street Café-Extension cord for small freezer
FAHC Main Campus Baird Wing Baird 3 Elevator Lobby near Main Street Café-Extension cord for the wall mounted television.

3. In the FAHC Main Campus ACC Main Pavilion 4th Floor room MP4-198, there are wires above the ceiling return air grill that are not properly supported.

4. Inspection revealed that there are outlets that are outlets that are within 6 feet of a water source that are not the Ground Fault Circuit Interruption type outlets. The following is a list of the areas involved.
McClure 7 Room 7066 outlet to close to sink
McClure 6 Room 664A outlet to close to sink
McClure 4 Room 403G Staff Lounge-GFCI outlet at sink broken
McClure 3 PSCU outlet #3LC1(2) -17
McClure 1 Room 1026 Outlet behind ice machine to close to sink
ACC West Pavilion WP5-186 Breakroom-outlet at sink
ACC West Pavilion 4th floor-outlet #2142-77 at the Nurses Station
ACC West Pavilion 2nd floor-Rooms WP2-456 & WP2-238 outlets to close to sink
ACC West Pavilion 4th floor-Room WP4-231 outlets # ' s R2142(2)-70 & R2141(1)-38
ACC West Pavilion 4th floor-Room WP4-224 outlet #R2141(2)53
ACC East Pavilion 1st floor-Room EP1-115 Clinical Lab outlet #LR2212(1)-6&5
ACC East Pavilion 4th floor-EP4-151 outlet #R2241-23
ACC East Pavilion 4th floor-EP4-141 outlet #R2241-31
ACC East Pavilion 4th floor-EP4-127 outlet #R2242(1)-32
ACC East Pavilion 4th floor-EP4-126 outlet #R2242(1-)31
ACC East Pavilion 2nd floor-HEMOC Waiting Room outlet at water cooler
ACC East Pavilion 2nd floor-outlet #R2222(1)-28
ACC East Pavilion 2nd floor breakroom #R2222(1)-4 near room EP2-212

5. Inspection of Baird 7 revealed the following:
Electrical panel PD1 is not properly labeled (R2-7-4-BRD)
Electrical panel in Room 7012 is not properly labeled.
Electrical panel LS2-7-1-BRD is not properly labeled.
Electrical panel R2-8-1B-BRD has a broken latch. This condition was found on several electrical panels. (Near Stair F)

6. Inspection of Baird 6 revealed the following:
Electrical panel EQ2-6-1BRD is not properly labeled.
Electrical panel R2-6-2B-BRD is not properly labeled.

7. Inspection of Baird 5 revealed the following:
There is a broken outlet cover over the counter in the kitchenette, Room 591B.

8. Inspection of Baird 4 revealed the following:
Electrical panel R2-4-1A-BRD has open spaces that must be filled with breakers or plastic blanks.
Room 451 is a small office and has a metal cabinet pressed against electrical outlet/cords. Outlet must be relocated away from cabinet.

9. Inspection of the Baird Penthouse revealed the following:
Electrical panel R2-8-2B-BRD has open spaces that must be filled with breakers or plastic blanks.
Electrical panel R2-8-1A-BRD has open spaces that must be filled with breakers or plastic blanks.

No Description Available

Tag No.: K0147

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there are electrical power strips that are interconnected into one another. The following is a list of locations where this occurs:
FAHC Fanny Allen Campus Walk In Care Desk

No Description Available

Tag No.: K0147

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there are outlets that are outlets that are within 6 feet of a water source that are not the Ground Fault Circuit Interruption type outlets. The following is a list of the areas involved:

FAHC Blair Park Campus-Given Lab, room 127, outlets at sink.
FAHC Blair Park Campus-Outpatient Lab, room 353, outlets at sink.
FAHC at 352 Mountain View Drive, Colchester, Plastics, in the breakroom & waiting room, water cooler outlets.

2. Inspection of 192 Tilley Drive in South Burlington revealed that the Data closet 1143 has open conduits. Conduits must be sealed with approved fire stopping material.

LIFE SAFETY CODE STANDARD

Tag No.: K0012

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. FAHC Garden Pavilion Surv Room - Inspection revealed that the spray fire proofing has been removed from the steel beam.

LIFE SAFETY CODE STANDARD

Tag No.: K0018

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that the Fire Barrier wall next to room 793 on Baird 7 has penetrations that must be sealed with approved fire stopping material.

2. Inspection revealed that a conduit within a fire barrier wall near Stair F on Baird 3 needs to be sealed with approved fire stopping material.

LIFE SAFETY CODE STANDARD

Tag No.: K0027

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that self-closing devices were missing from the following locations:

FAHC Main Campus McClure Wing 5th Floor- East pantry door missing self-closing device.
FAHC Main Campus ACC West Pavilion 2nd Floor Room WP2-271 missing self-closing device.
FAHC Main Campus ACC West Pavilion 1st Floor Room WP1-194 missing self-closing device.
FAHC Main Campus Shepardson North 3rd Floor room 378 - door missing self-closing device.

2. Inspection of Baird 5 revealed that a Fire Barrier door near room 524B drags and needs adjustment.

3. Inspection of Baird 3 revealed that the Fire Barrier door near Room 310 does not latch properly.

4. Inspection of Shepardson 6 revealed that the Fire door near room 636 is not closing and must be adjusted.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that in the FAHC Fanny Allen Campus Cafeteria, door G009 was missing from corridor.

LIFE SAFETY CODE STANDARD

Tag No.: K0033

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there was storage at the bottom landing of the egress stairway located in the MRI (Magnetic Resonance Imaging) wing of the FAHC (Fletcher Allen Health Care) Main Campus.

2. Inspection revealed that the Sprinkler system Pre-action valve cabinet was installed at the top of the MRI wing egress stairway located in the MRI wing of FAHC Main Campus.

LIFE SAFETY CODE STANDARD

Tag No.: K0033

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there was storage at the bottom landings of egress stairways (GS03 & GS02) located at the FAHC Fanny Allen Campus.

LIFE SAFETY CODE STANDARD

Tag No.: K0034

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that the South egress stairway exit door for Shepardson 3 South has a delayed egress lock that was installed without authorization of the City of Burlington Fire Marshal.

2. Inspection of Shepardson 5 revealed that the Exit door at the west end of the corridor is on an automatic release set for 30 seconds, but the door is labeled with a 15 second delay.

LIFE SAFETY CODE STANDARD

Tag No.: K0046

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection of Baird 5 revealed that Emergency light unit PNL LM#50 would not operate.

LIFE SAFETY CODE STANDARD

Tag No.: K0051

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that the fire alarm system has violations. These violations are listed below with the location of the violation:

FAHC ACC Main Pavilion 3rd floor at main entrance doors. The fire alarm system pull stations are blocked by wheel chairs and not readily accessible.
FAHC ACC West Pavilion 5th Floor by room WP5-204 - Inadequate smoke detector coverage.
FAHC ACC West Pavilion Room 2nd Floor WP2-237 - Smoke detector less than 3 feet from supply air diffuser.
FAHC Garden Pavilion - Smoke Detector #M3-49 at entrance door less than 3 feet from supply air diffuser.
FAHC ACC Main Pavilion 4th Floor Room MP4-108 - Smoke detector missing.
FAHC Garden Pavilion near Room 2324 - Smoke detector less than 3 feet from supply air diffuser.
FAHC Baird Wing Main Kitchen fire alarm system horn strobe in rear storage room blocked by storage rack.
FAHC ACC Emergency Department Room WP1-186 - Smoke detector less than 3 feet from supply air diffuser.
FAHC ACC East Pavilion 2nd Floor near door EP2-115 - Smoke detector less than 3 feet from supply air diffuser.
FAHC McClure 1 Inergen Fire Suppression System circuit breaker-lock missing. This was written up during the last two annual inspections and was not corrected.

2. Inspection of Baird 4 revealed that smoke detectors in corridors exceed standard spacing with as much as 74 inches between detectors. Additional smoke detectors must be provided.

3. Inspection of Shepardson 6 revealed that four smoke detectors on the unit are located within 1 foot of supply air grill and must be located at least 3 feet from the supply air. Also, the Fire alarm conduit needs approved fire stopping material in the wall next to room 637.

4. Inspection of Shepardson 5 revealed that the Fire Alarm panel shows lobby 401 smoke detector as dirty and needs cleaning. This detector had a solid light on, indicating a trouble.

5. Inspection of Shepardson 4 revealed a smoke detector near room 446 is located within 1 foot of supply air grill and must be located at least 3 feet from the supply air. Also, all smoke detectors in "On-Call Wing Bedrooms" are located within 1 foot of supply air grill.

4.

LIFE SAFETY CODE STANDARD

Tag No.: K0051

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that the fire alarm system has violations. These violations are listed below with the location of the violation:

FAHC/UHC Medical Records Department Room G409 - Smoke detectors not properly spaced.

LIFE SAFETY CODE STANDARD

Tag No.: K0056

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that was storage to close to sprinkler heads and that that are locations with sprinkler heads missing. The following is a list locations where these violations occurred:
FAHC ACC Wing West Pavilion Room EP4-215 has no sprinkler head.

2. Inspection of Baird 3 revealed that the Nurses station has a new suspended lighting system that blocks the sprinkler heads from protecting the area properly. Two additional sprinkler heads are needed in this area.

LIFE SAFETY CODE STANDARD

Tag No.: K0056

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that was storage to close to sprinkler heads and that that are locations with sprinkler heads missing. The following is a list locations where these violations occurred:
FAHC Fanny Allen Campus-Sprinkler head missing above trash compactor door located near the emergency exit on the ground floor.

LIFE SAFETY CODE STANDARD

Tag No.: K0056

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that was storage to close to sprinkler heads and that that are locations with sprinkler heads missing. The following is a list locations where these violations occurred:
a. FAHC/UHC Medical Records Department has storage within 18 inches of sprinkler heads.
b. O ' Brien Community Center in Winooski is missing a sprinkler head in the Aquatic Pool Closet.

LIFE SAFETY CODE STANDARD

Tag No.: K0069

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there is frying being conducted in the Fanny Allen Campus Rehab Dining Rooms without a kitchen hood or fire suppression system.

2. Inspection revealed that the kitchen staff did not know how to manually activate the kitchen hood fire suppression system in the FAHC Fanny Allen Campus Cafeteria.

LIFE SAFETY CODE STANDARD

Tag No.: K0069

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there is frying being conducted without a kitchen hood or suppression system on the customer serving line in the FAHC Main Street Café on Baird 3.

LIFE SAFETY CODE STANDARD

Tag No.: K0106

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there was not an emergency light mounted in the emergency generator room at FAHC Fanny Allen Campus.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there are electrical power strips that are interconnected into one another in the ACC Wing of the FAHC Main Campus. The following is a list of locations where this occurs:
ACC West Pavilion 5th floor Room WP5-238
ACC Main Pavilion 4th floor Vascular Team Station
ACC Main Pavilion 3rd floor West storage room
ACC West Pavilion 1st floor GT Nurses Station & Acute Care Desk
ACC Main Pavilion 2nd Floor Breast Care Reception Desk
ACC East Pavilion 2nd floor rooms EP2-130 & EP2-130A

2. Inspection revealed the use of extension cords as a permanent power supply to equipment. The following is a list of the locations where this occurs:
FAHC Main Campus ACC Wing East Pavilion Room EP5-135
FAHC Main Campus Baird Wing Main Street Café-Extension cord for small freezer
FAHC Main Campus Baird Wing Baird 3 Elevator Lobby near Main Street Café-Extension cord for the wall mounted television.

3. In the FAHC Main Campus ACC Main Pavilion 4th Floor room MP4-198, there are wires above the ceiling return air grill that are not properly supported.

4. Inspection revealed that there are outlets that are outlets that are within 6 feet of a water source that are not the Ground Fault Circuit Interruption type outlets. The following is a list of the areas involved.
McClure 7 Room 7066 outlet to close to sink
McClure 6 Room 664A outlet to close to sink
McClure 4 Room 403G Staff Lounge-GFCI outlet at sink broken
McClure 3 PSCU outlet #3LC1(2) -17
McClure 1 Room 1026 Outlet behind ice machine to close to sink
ACC West Pavilion WP5-186 Breakroom-outlet at sink
ACC West Pavilion 4th floor-outlet #2142-77 at the Nurses Station
ACC West Pavilion 2nd floor-Rooms WP2-456 & WP2-238 outlets to close to sink
ACC West Pavilion 4th floor-Room WP4-231 outlets # ' s R2142(2)-70 & R2141(1)-38
ACC West Pavilion 4th floor-Room WP4-224 outlet #R2141(2)53
ACC East Pavilion 1st floor-Room EP1-115 Clinical Lab outlet #LR2212(1)-6&5
ACC East Pavilion 4th floor-EP4-151 outlet #R2241-23
ACC East Pavilion 4th floor-EP4-141 outlet #R2241-31
ACC East Pavilion 4th floor-EP4-127 outlet #R2242(1)-32
ACC East Pavilion 4th floor-EP4-126 outlet #R2242(1-)31
ACC East Pavilion 2nd floor-HEMOC Waiting Room outlet at water cooler
ACC East Pavilion 2nd floor-outlet #R2222(1)-28
ACC East Pavilion 2nd floor breakroom #R2222(1)-4 near room EP2-212

5. Inspection of Baird 7 revealed the following:
Electrical panel PD1 is not properly labeled (R2-7-4-BRD)
Electrical panel in Room 7012 is not properly labeled.
Electrical panel LS2-7-1-BRD is not properly labeled.
Electrical panel R2-8-1B-BRD has a broken latch. This condition was found on several electrical panels. (Near Stair F)

6. Inspection of Baird 6 revealed the following:
Electrical panel EQ2-6-1BRD is not properly labeled.
Electrical panel R2-6-2B-BRD is not properly labeled.

7. Inspection of Baird 5 revealed the following:
There is a broken outlet cover over the counter in the kitchenette, Room 591B.

8. Inspection of Baird 4 revealed the following:
Electrical panel R2-4-1A-BRD has open spaces that must be filled with breakers or plastic blanks.
Room 451 is a small office and has a metal cabinet pressed against electrical outlet/cords. Outlet must be relocated away from cabinet.

9. Inspection of the Baird Penthouse revealed the following:
Electrical panel R2-8-2B-BRD has open spaces that must be filled with breakers or plastic blanks.
Electrical panel R2-8-1A-BRD has open spaces that must be filled with breakers or plastic blanks.

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there are electrical power strips that are interconnected into one another. The following is a list of locations where this occurs:
FAHC Fanny Allen Campus Walk In Care Desk

LIFE SAFETY CODE STANDARD

Tag No.: K0147

Based on inspection of the hospital and associated buildings from 3/8/11 to 3/11/11:

1. Inspection revealed that there are outlets that are outlets that are within 6 feet of a water source that are not the Ground Fault Circuit Interruption type outlets. The following is a list of the areas involved:

FAHC Blair Park Campus-Given Lab, room 127, outlets at sink.
FAHC Blair Park Campus-Outpatient Lab, room 353, outlets at sink.
FAHC at 352 Mountain View Drive, Colchester, Plastics, in the breakroom & waiting room, water cooler outlets.

2. Inspection of 192 Tilley Drive in South Burlington revealed that the Data closet 1143 has open conduits. Conduits must be sealed with approved fire stopping material.