No Description Available

Tag No.: K0029

Based on visual observation the facility failed to maintain the separation of hazardous areas from other parts of the building, including the egress corridor. Hazardous areas are required to be constructed to resist the passage of smoke. The deficient practice had the potential to affect 18 of 18 residents.
Finding:
During tour of facility on 1/16/2013 observation revealed unsealed ceiling penetration in both boiler rooms, They consist of unsealed metal pipe and open holes.

No Description Available

Tag No.: K0047

Based on visual observation the facility failed to provide exit lighting along the entire length of the exit access. Exit lights provide visual assurance of the direction of the exit door. The deficient practice practice had the potential to affect 9 of 18 residents.
Finding:
During tour of facility on 1/16/2013 observation revealed no exit sign at cross corridor doors on the new wing and these doors are kept closed .

No Description Available

Tag No.: K0066

Based on visual observation, the facility failed to assure that all smoking areas were supplied with a metal, self-closing container. Cigarette butts shall be extinguished in an approved container in order to prevent accidental combustion. The deficient practice could potentially affect 18 of 18 residents. Finding:
During tour of facility on 1/16/2013 observation revealed, no metal self-closing container type of ashtrays.

LIFE SAFETY CODE STANDARD

Tag No.: K0029

Based on visual observation the facility failed to maintain the separation of hazardous areas from other parts of the building, including the egress corridor. Hazardous areas are required to be constructed to resist the passage of smoke. The deficient practice had the potential to affect 18 of 18 residents.
Finding:
During tour of facility on 1/16/2013 observation revealed unsealed ceiling penetration in both boiler rooms, They consist of unsealed metal pipe and open holes.

LIFE SAFETY CODE STANDARD

Tag No.: K0047

Based on visual observation the facility failed to provide exit lighting along the entire length of the exit access. Exit lights provide visual assurance of the direction of the exit door. The deficient practice practice had the potential to affect 9 of 18 residents.
Finding:
During tour of facility on 1/16/2013 observation revealed no exit sign at cross corridor doors on the new wing and these doors are kept closed .

LIFE SAFETY CODE STANDARD

Tag No.: K0066

Based on visual observation, the facility failed to assure that all smoking areas were supplied with a metal, self-closing container. Cigarette butts shall be extinguished in an approved container in order to prevent accidental combustion. The deficient practice could potentially affect 18 of 18 residents. Finding:
During tour of facility on 1/16/2013 observation revealed, no metal self-closing container type of ashtrays.